background image

 

Installation manual

2

250C7Y1B

Split system air conditioner

4PW34720-1G – 07.2010

2. I

NTRODUCTION

2.1.

Combination

The indoor units can be installed in the following range.

Always use appropriate indoor units compatible with R410A.
To learn which models of indoor units are compatible with
R410A, refer to the product catalogs.

For installation of the indoor unit(s), refer to the installation
manual delivered with the indoor unit(s).

2.2.

Standard supplied accessories

Refer to 

figure 2

.

2.3.

Optional accessories

This outdoor unit requires the pipe branching kit (optional) when
using a twin, triple or double twin application. Refer to catalogues for
details.

2.4.

Technical and Electrical specifications

Refer to the Engineering Data Book for the complete list of
specifications.

3. M

AIN

 

COMPONENTS

For main components and function of the main components, refer to
the Engineering Data Book.

4. S

ELECTION

 

OF

 

LOCATION

This is a class A product. In a domestic environment this product may
cause radio interference in which case the user may be required to
take adequate measures.

The inverter units should be installed in a location that meets the
following requirements:

1

The foundation is strong enough to support the weight of the unit
and the floor is flat to prevent vibration and noise generation. If
not, the unit may fall over and cause injury.

2

The space around the unit is adequate for servicing and the
minimum space for air inlet and air outlet is available. (Refer to

figure 1

 and choose one of the possibilities).

In case of an installation site where only the sides A+B have
obstacles, the wall heights have no influence on any indicated
service space dimensions.

3

Make sure to provide for adequate measures in order to prevent
that the outdoor unit be used as a shelter by small animals.

Small animals making contact with electrical parts can cause
malfunctions, smoke or fire. Please instruct the customer to
keep the area around the unit clean.

4

There is no danger of fire due to leakage of inflammable gas.

5

Ensure that water cannot cause any damage to the location in
case it drips out the unit (e.g. in case of a blocked drain pipe).

6

The piping length between the outdoor unit and the indoor unit
may not exceed the allowable piping length.

7

Select the location of the unit in such a way that neither the
discharged air nor the sound generated by the unit disturb
anyone.

Precautions for R410A

The refrigerant requires strict cautions for keeping the
system clean, dry and tight.
-

Clean and dry
Foreign materials (including mineral oils or
moisture) should be prevented from getting mixed
into the system.

-

Tight
Read 

"7.6. Precautions on refrigerant piping" on

page 5

 carefully and follow these procedures

correctly.

Since R410A is a mixed refrigerant, the required
additional refrigerant must be charged in its liquid
state. (If the refrigerant is in state of gas, its
composition changes and the system will not work
properly).

The connected indoor units must be indoor units
designed exclusively for R410A.

Read 

"7. Refrigerant piping" on page 4

 carefully and follow

these procedures correctly.

Since design pressure is 4.0 MPa or 40 bar, pipes of larger
wall thickness may be required. Refer to paragraph

"7.1. Selection of piping material" on page 4

.

RZQ200

RZQ250

Gas line piping (1)

1

1

Gas line piping (2)

1

1

Liquid line piping (1)

1

1

Liquid line piping (2)

1

1

Installation manual

1

1

Additional refrigerant charge label

1

1

Fluorinated greenhouse gases 
label

1

1

Multilingual fluorinated greenhouse 
gases label

1

1

1

Installation manual

2

Accessory pipes

This unit, both indoor and outdoor, is suitable for
installation in a commercial and light industrial
environment. If installed as a house-hold appliance it could
cause electromagnetic inteference.

Make sure to provide for adequate measures in order
to prevent that the outdoor unit be used as a shelter
by small animals.

Small animals making contact with electrical parts can
cause malfunctions, smoke or fire. Please instruct the
customer to keep the area around the unit clean.

A B C D

Sides along the installation site with obstacles

Suction side

Summary of Contents for RZQ200C7Y1B

Page 1: ...INSTALLATION MANUAL RZQ200C7Y1B RZQ250C7Y1B Split system air conditioner ...

Page 2: ...H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 H1 H2 L7 L1 L6 L5 L4 L3 L2 4 3 1 3 4 2 2 mm 5 3 1 0 0 0 1000 1 50 0 1500 1500 2 1 2 10 14 A 1 3 0 3 0 4 2 3 1 E B C D H A 18 16 17 h1 h2 1500 500 1 2 3 4 5 1 2 3 1 2 3 4 5 4 1 2 4 5 3 5 3 3 1 13 6 9 8 1 2 4 3 5 14 15 16 12 11 10 7 3 2 8 6 4 8 1 3 2 7 8 9 8 10 11 8 8 8 5 9 1 A B 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 ...

Page 3: ...responsabilidade que os modelos de ar condicionado a que esta declaração se refere 09 u заявляет исключительно под свою ответственность что модели кондиционеров воздуха к которым относится настоящее заявление 10 q erklærer under eneansvar at klimaanlægmodellerne som denne deklaration vedrører 11 s deklarerar i egenskap av huvudansvarig att luftkonditioneringsmodellerna som berörs av denna deklarat...

Page 4: ...atalapainepuolen lämpötila L C TSmax Suurinta sallittua painetta PS vastaava kyllästyslämpötila M C Kylmäaine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi 14 Maximální přípustný tlak PS K bar Minimální maximální přípustná teplota TS TSmin Minimální teplota na nízkotlaké straně L C TSmax Saturovaná teplota odpovídající maximálnímu přípustnému tlaku PS...

Page 5: ...ontside panel is not in place overheat of the terminals electric shocks or a fire may be caused If refrigerant gas leaks during installation work ventilate the area immediately Toxic gas may be produced if refrigerant gas comes into contact with fire After completing the installation work check to make sure that there is no leakage of refrigerant gas Toxic gas may be produced if refrigerant gas leak...

Page 6: ... 4 There is no danger of fire due to leakage of inflammable gas 5 Ensure that water cannot cause any damage to the location in case it drips out the unit e g in case of a blocked drain pipe 6 The piping length between the outdoor unit and the indoor unit may not exceed the allowable piping length 7 Select the location of the unit in such a way that neither the discharged air nor the sound generated ...

Page 7: ...oise generated from radio frequency energy The equipment complies to specifications that are designed to provide reasonable protection against such interference However there is no guarantee that interference will not occur in a particular installation It is therefore recommended to install the equipment and electric wires keeping proper distances away from stereo equipment personal computers etc S...

Page 8: ...rant piping Therefore use the phosphor copper brazing filler metal BCuP which does not require flux Flux has extremely harmful influence on refrigerant piping systems For instance if the chlorine based flux is used it will cause pipe corrosion or in particular if the flux contains fluorine it will damage the refrigerant oil Be sure to perform a nitrogen blow when brazing Brazing without performing nitro...

Page 9: ...g Perform a visual check on quality of residual oil in existing refrigerant piping This check is extremely important because using existing piping with deteriorated oil will cause compressor breakdown Put some residual oil of the pipes you want to reuse on a piece of white paper or on the white surface of an oil checking reference card and compare that oil color with the circled color of the oil c...

Page 10: ...all gas and oil is recovered from the pinched piping disconnect the charge hose and close the service ports 5 In case the pinched piping lower part looks like detail in the illustration follow instructions as per procedure steps 7 8 In case the pinched piping lower part looks like detail in the illustration follow instructions as per procedure steps 6 7 8 6 Cut off the lower part of the smaller pi...

Page 11: ... over a long period of time rainwater may enter the pipe during work After evacuating the system for 2 hours pressurize the system to 0 05 MPa vacuum break with nitrogen gas and evacuate the system again using the vacuum pump for 1 hour to 100 7 kPa vacuum drying If the system cannot be evacuated to 100 7 kPa within 2 hours repeat the operation of vacuum break and vacuum drying Then after leaving ...

Page 12: ...t leaks are present 7 12 Additional refrigerant charge Important information regarding the refrigerant used This product contains fluorinated greenhouse gases covered by the Kyoto Protocol Do not vent gases into the atmosphere Refrigerant type R410A GWP 1 value 1975 1 GWP global warming potential Please fill in with indelible ink the factory refrigerant charge of the product the additional refrigera...

Page 13: ...pipe length of that pipe diameter by multiplying that length by the appropriate calculation coefficient Take note of the calculated weight 6 Repeat step 5 for other pipe diameters in function of other pipe diameter pipe lengths downstream to the indoor units and add up all calculated weights 7 The sum of all calculated weights is the total required additional refrigerant charge for your installatio...

Page 14: ...sible when the power supply is switched off 2 Turn the power supply on and charge only the amount of lacking refrigerant 3 Completely open the gas line stop valve See figure 15 and refer to Airtightness test and vacuum drying on page 7 for nomenclature of the parts in figure 15 Valve A must be left fully closed Make sure the liquid stop valve is totally shut If it is open the refrigerant cannot be c...

Page 15: ... wiring must be carried out in accordance with the wiring diagrams and the instructions given below Be sure to use a dedicated power circuit Never use a power supply shared by another appliance This can lead to electrical shock or fire Insufficient capacity of the power supply circuit or improper electrical construction may lead to electric shocks or fire Do not operate until refrigerant piping work ...

Page 16: ... hard plastic piping is used Telephone ground wires and lightning rods dangerous when struck by lightning due to abnormal rise in electrical potential in the grounding This unit uses an inverter and therefore generates noise which will have to be reduced to avoid interfering with other devices The outer casing of the product may take on an electrical charge due to leaked electrical current which w...

Page 17: ...en routing out the ground wires from the left side 10 Grounding wire 11 When wiring pay attention not to detach the acoustic insulators from the compressor Precautions when installing power wiring Use round pressure terminals for connections to the power terminal block When none are available follow the instructions below Do not connect wiring of different thicknesses to the power terminal block S...

Page 18: ...not pass near each other keeping them at least 50 mm apart Proximity may cause electrical interference malfunctions and breakage Be sure to connect the power wiring to the power wiring terminal block and secure it as described under Field line connection on page 13 Inter unit wiring should be secured as described in Field line connection in chapter 8 5 Examples on page 13 Secure the wiring with th...

Page 19: ...s and buttons Led state Throughout the manual the state of the LEDs is indicated as follows Setting the DIP switches Setting the push button switch BS1 5 Function of the push button switch which is located on the outdoor unit PCB A1P Setting the mode 2 The set mode can be changed by pressing the button for 5 seconds The setting mode will change to setting mode 2 and the H1P LED will be ON w Exitin...

Page 20: ...d wire Is the wiring as mentioned on the wiring diagram Make sure no wiring has been forgotten and that there are no missing phases or reverse phases Is the unit properly grounded Are any of the wiring attachment screws loose Is the insulation resistance at least 2 MΩ Use a 500 V mega tester when measuring insulation Do not use a mega tester for circuits which are not 230 V Refrigerant piping Is t...

Page 21: ...ply and the outdoor unit with the circuit breaker After the power supply to one side is cut off cut off the power supply to the other side within 10 minutes Otherwise the communication between the indoor and outdoor unit may become abnormal and the expansion valves will be completely closed again 3 Recover the refrigerant by a refrigerant reclaimer For details see the operation manual delivered wi...

Page 22: ...d so until the result falls short of the maximum concentration 4 Dealing with the situations where the result exceeds the maximum concentration level Where the installation of a facility results in a concentration in excess of the maximum concentration level then it will be necessary to revise the system 5 Please consult your supplier 12 DISPOSAL REQUIREMENTS Dismantling of the unit treatment of t...

Page 23: ...20 22 21 19 1 2 5 3 3 5 4 4 1 2 3 4 5 24 23 5 1 7 10 3 2 9 6 6 7 4 11 8 6 NOTES 3 1 2 3 2 6 4 A 3 2 1 6 5 4 3 L1 L2 L3 N 1 3 4 2 8 9 6 5 7 20 21 22 23 24 19 ...

Page 24: ...4PW34720 1G 07 2010 Copyright 2006 Daikin ...

Reviews: