250C7Y1B
Split system air conditioner
4PW34720-1G – 07.2010

Installation manual

3

8

Make sure that the air inlet and outlet of the unit are not
positioned towards the main wind direction. Frontal wind will
disturb the operation of the unit. If necessary, use a windscreen
to block the wind.

9

Do not install or operate the unit on locations where air contains
high levels of salt, like e.g. in the vicinity of oceans.

10

During installation, avoid the possibility that children can mount
on the unit or place any object on the unit.

Falling or tumble may result in injury.

11

The equipment is not intended for use in a potentially explosive
atmosphere.

5. I

NSPECTING

 

AND

 

HANDLING

 

THE

 

UNIT

At delivery, the package should be checked and any damage should
be reported immediately to the carrier claims agent.

When handling the unit, take into account the following:

1

Fragile, handle the unit with care.

Keep the unit upright in order to avoid compressor

damage.

2

Choose in advance the path along which the unit is to be
brought in.

3

Bring the unit as close as possible to its final installation position
in its original package to prevent damage during transport. 

(See

figure 4)

4

Lift the unit preferably with a crane and 2 belts of at least 8 m
long. 

(See figure 4)

Always use protectors to prevent belt damage and pay attention
to the position of the unit's centre of gravity.

5

If a forklift is to be used, preferably
transport the unit with pallet first,
then pass the forklift arms through
the large rectangular openings on
the bottom of the unit. 

5.1

From the moment you use a forklift to
move the unit to its final position, lift
the unit under the pallet.

5.2

Once at final position, unpack the unit and pass the forklift arms
through the large rectangular openings on the bottom of the unit.

6. U

NPACKING

 

AND

 

PLACING

 

THE

 

UNIT

Remove the four screws fixing the unit to the pallet.

Make sure the unit is installed level on a sufficiently strong base
to prevent vibration and noise.

Fasten the unit in place using four anchor bolts M12.

Make sure the base under the unit is more than 765 mm.

The unit must be installed on a solid longitudinal foundation
(steelbeam frame or concrete) as indicated in 

figure 5

.

Support the unit with a foundation of 66 mm width or more. (The
support leg of the unit is 66 mm width).

The equipment described in this manual may cause
electronic noise generated from radio-frequency
energy. The equipment complies to specifications that
are designed to provide reasonable protection against
such interference. However, there is no guarantee that
interference will not occur in a particular installation.
It is therefore recommended to install the equipment
and electric wires keeping proper distances away from
stereo equipment, personal computers, etc... 

(See

figure 3)

.

In extreme circumstances you should keep distances
of 3 m or more and use conduit tubes for power and
transmission lines.

In heavy snowfall areas, select an installation site
where snow will not affect operation of the unit.

The refrigerant R410A itself is nontoxic, nonflammable
and is safe. If the refrigerant should leak however, its
concentration may exceed the allowable limit
depending on room size. Due to this it could be
necessary to take measures against leakage.

Do not install in the following locations.

Locations where acidic or alkaline vapour is
present.

Locations where sulfurous acids and other
corrosive gases may be present in the atmosphere.
Copper piping and soldered joints may corrode,
causing refrigerant to leak.

Locations where there is mist of mineral oil, oil
spray or vapor for example a kitchen.
Plastic parts may deteriorate, and cause them to
fall out or water to leak.

Locations where the air contains high levels of salt
such as that near the ocean.

Locations where flammable gases may leak, where
thinner, gasoline, and other volatile substances are
handled, or where carbon dust and other
incendiary substances are found in the
atmosphere.
Leaked gas may accumulate around the unit,
causing an explosion.

Locations where equipment that produces electro-
magnetic waves is found.
The electromagnetic waves may cause the control
system to malfunction, preventing normal
operation.

Locations where voltage fluctuates a lot, such as
that in factories.

In vehicles or vessels.

During installation, take strong winds, typhoons or
earthquakes into account.
Improper installation may result in fall over of the unit.

1

Personal computer or radio

2

Fuse

3

Earth leakage breaker

4

Remote controller

5

Indoor unit

1

Packaging material

2

Opening (large)

3

Belt sling

4

Opening (small) (40x45)

5

Protector

NOTE

Use a belt sling of 

20 mm wide that adequately

bears the weight of the unit.

NOTE

Use filler cloth on the forklift arms to prevent
damaging the unit. If the paint on the bottom
frame peels off, the anti corrosion effect may
decrease.

Model

A

B

250

930

792

Do not use stands to support the corners. 

(See figure 6)

X

Not allowed

O

Allowed

Summary of Contents for RZQ200C7Y1B

Page 1: ...INSTALLATION MANUAL RZQ200C7Y1B RZQ250C7Y1B Split system air conditioner ...

Page 2: ...H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 H1 H2 L7 L1 L6 L5 L4 L3 L2 4 3 1 3 4 2 2 mm 5 3 1 0 0 0 1000 1 50 0 1500 1500 2 1 2 10 14 A 1 3 0 3 0 4 2 3 1 E B C D H A 18 16 17 h1 h2 1500 500 1 2 3 4 5 1 2 3 1 2 3 4 5 4 1 2 4 5 3 5 3 3 1 13 6 9 8 1 2 4 3 5 14 15 16 12 11 10 7 3 2 8 6 4 8 1 3 2 7 8 9 8 10 11 8 8 8 5 9 1 A B 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 ...

Page 3: ...responsabilidade que os modelos de ar condicionado a que esta declaração se refere 09 u заявляет исключительно под свою ответственность что модели кондиционеров воздуха к которым относится настоящее заявление 10 q erklærer under eneansvar at klimaanlægmodellerne som denne deklaration vedrører 11 s deklarerar i egenskap av huvudansvarig att luftkonditioneringsmodellerna som berörs av denna deklarat...

Page 4: ...atalapainepuolen lämpötila L C TSmax Suurinta sallittua painetta PS vastaava kyllästyslämpötila M C Kylmäaine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi 14 Maximální přípustný tlak PS K bar Minimální maximální přípustná teplota TS TSmin Minimální teplota na nízkotlaké straně L C TSmax Saturovaná teplota odpovídající maximálnímu přípustnému tlaku PS...

Page 5: ...ontside panel is not in place overheat of the terminals electric shocks or a fire may be caused If refrigerant gas leaks during installation work ventilate the area immediately Toxic gas may be produced if refrigerant gas comes into contact with fire After completing the installation work check to make sure that there is no leakage of refrigerant gas Toxic gas may be produced if refrigerant gas leak...

Page 6: ... 4 There is no danger of fire due to leakage of inflammable gas 5 Ensure that water cannot cause any damage to the location in case it drips out the unit e g in case of a blocked drain pipe 6 The piping length between the outdoor unit and the indoor unit may not exceed the allowable piping length 7 Select the location of the unit in such a way that neither the discharged air nor the sound generated ...

Page 7: ...oise generated from radio frequency energy The equipment complies to specifications that are designed to provide reasonable protection against such interference However there is no guarantee that interference will not occur in a particular installation It is therefore recommended to install the equipment and electric wires keeping proper distances away from stereo equipment personal computers etc S...

Page 8: ...rant piping Therefore use the phosphor copper brazing filler metal BCuP which does not require flux Flux has extremely harmful influence on refrigerant piping systems For instance if the chlorine based flux is used it will cause pipe corrosion or in particular if the flux contains fluorine it will damage the refrigerant oil Be sure to perform a nitrogen blow when brazing Brazing without performing nitro...

Page 9: ...g Perform a visual check on quality of residual oil in existing refrigerant piping This check is extremely important because using existing piping with deteriorated oil will cause compressor breakdown Put some residual oil of the pipes you want to reuse on a piece of white paper or on the white surface of an oil checking reference card and compare that oil color with the circled color of the oil c...

Page 10: ...all gas and oil is recovered from the pinched piping disconnect the charge hose and close the service ports 5 In case the pinched piping lower part looks like detail in the illustration follow instructions as per procedure steps 7 8 In case the pinched piping lower part looks like detail in the illustration follow instructions as per procedure steps 6 7 8 6 Cut off the lower part of the smaller pi...

Page 11: ... over a long period of time rainwater may enter the pipe during work After evacuating the system for 2 hours pressurize the system to 0 05 MPa vacuum break with nitrogen gas and evacuate the system again using the vacuum pump for 1 hour to 100 7 kPa vacuum drying If the system cannot be evacuated to 100 7 kPa within 2 hours repeat the operation of vacuum break and vacuum drying Then after leaving ...

Page 12: ...t leaks are present 7 12 Additional refrigerant charge Important information regarding the refrigerant used This product contains fluorinated greenhouse gases covered by the Kyoto Protocol Do not vent gases into the atmosphere Refrigerant type R410A GWP 1 value 1975 1 GWP global warming potential Please fill in with indelible ink the factory refrigerant charge of the product the additional refrigera...

Page 13: ...pipe length of that pipe diameter by multiplying that length by the appropriate calculation coefficient Take note of the calculated weight 6 Repeat step 5 for other pipe diameters in function of other pipe diameter pipe lengths downstream to the indoor units and add up all calculated weights 7 The sum of all calculated weights is the total required additional refrigerant charge for your installatio...

Page 14: ...sible when the power supply is switched off 2 Turn the power supply on and charge only the amount of lacking refrigerant 3 Completely open the gas line stop valve See figure 15 and refer to Airtightness test and vacuum drying on page 7 for nomenclature of the parts in figure 15 Valve A must be left fully closed Make sure the liquid stop valve is totally shut If it is open the refrigerant cannot be c...

Page 15: ... wiring must be carried out in accordance with the wiring diagrams and the instructions given below Be sure to use a dedicated power circuit Never use a power supply shared by another appliance This can lead to electrical shock or fire Insufficient capacity of the power supply circuit or improper electrical construction may lead to electric shocks or fire Do not operate until refrigerant piping work ...

Page 16: ... hard plastic piping is used Telephone ground wires and lightning rods dangerous when struck by lightning due to abnormal rise in electrical potential in the grounding This unit uses an inverter and therefore generates noise which will have to be reduced to avoid interfering with other devices The outer casing of the product may take on an electrical charge due to leaked electrical current which w...

Page 17: ...en routing out the ground wires from the left side 10 Grounding wire 11 When wiring pay attention not to detach the acoustic insulators from the compressor Precautions when installing power wiring Use round pressure terminals for connections to the power terminal block When none are available follow the instructions below Do not connect wiring of different thicknesses to the power terminal block S...

Page 18: ...not pass near each other keeping them at least 50 mm apart Proximity may cause electrical interference malfunctions and breakage Be sure to connect the power wiring to the power wiring terminal block and secure it as described under Field line connection on page 13 Inter unit wiring should be secured as described in Field line connection in chapter 8 5 Examples on page 13 Secure the wiring with th...

Page 19: ...s and buttons Led state Throughout the manual the state of the LEDs is indicated as follows Setting the DIP switches Setting the push button switch BS1 5 Function of the push button switch which is located on the outdoor unit PCB A1P Setting the mode 2 The set mode can be changed by pressing the button for 5 seconds The setting mode will change to setting mode 2 and the H1P LED will be ON w Exitin...

Page 20: ...d wire Is the wiring as mentioned on the wiring diagram Make sure no wiring has been forgotten and that there are no missing phases or reverse phases Is the unit properly grounded Are any of the wiring attachment screws loose Is the insulation resistance at least 2 MΩ Use a 500 V mega tester when measuring insulation Do not use a mega tester for circuits which are not 230 V Refrigerant piping Is t...

Page 21: ...ply and the outdoor unit with the circuit breaker After the power supply to one side is cut off cut off the power supply to the other side within 10 minutes Otherwise the communication between the indoor and outdoor unit may become abnormal and the expansion valves will be completely closed again 3 Recover the refrigerant by a refrigerant reclaimer For details see the operation manual delivered wi...

Page 22: ...d so until the result falls short of the maximum concentration 4 Dealing with the situations where the result exceeds the maximum concentration level Where the installation of a facility results in a concentration in excess of the maximum concentration level then it will be necessary to revise the system 5 Please consult your supplier 12 DISPOSAL REQUIREMENTS Dismantling of the unit treatment of t...

Page 23: ...20 22 21 19 1 2 5 3 3 5 4 4 1 2 3 4 5 24 23 5 1 7 10 3 2 9 6 6 7 4 11 8 6 NOTES 3 1 2 3 2 6 4 A 3 2 1 6 5 4 3 L1 L2 L3 N 1 3 4 2 8 9 6 5 7 20 21 22 23 24 19 ...

Page 24: ...4PW34720 1G 07 2010 Copyright 2006 Daikin ...

Reviews: