4 About the units and options

Installer reference guide

7

RZAG71~140L7V1B
Split system air conditioners
4P418663-1 – 2016.02

4

About the units and options

4.1

Overview: About the units and
options

This chapter contains information about:

▪ Identifying the outdoor unit

▪ Combining the outdoor unit with options

INFORMATION

For  year‑round  cooling  applications  with  low  indoor
humidity  conditions,  such  as  Electronic  Data  Processing
rooms,  contact  your  dealer  or  see  the  engineering
databook or the service manual.

4.2

Identification

NOTICE

When installing or servicing several units at the same time,
make  sure  NOT  to  switch  the  service  panels  between
different models.

4.2.1

Identification label: Outdoor unit

Location

Model identification

RZAG:  Contains  components  (insulation…)  to  prevent  freeze-up  in
areas  with  low  ambient  temperature  and  high  humidity.  Possible  to
connect an optional bottom plate heater.

Example: 

R Z A G 140 L7 V1 B [*]

Code

Explanation

R

Air-cooled split outdoor unit

Z

Inverter

A

Refrigerant R32

G

GQI-Eco series

71~140

Capacity class

L7

Model series

V1

Power supply

B

European market

[*]

Minor model change indication

4.3

Combining units and options

4.3.1

Possible options for the outdoor unit

Bottom plate heater (EKBPH140L7)

▪ Prevents freeze-up of the bottom plate.

▪ Recommended  in  areas  with  low  ambient  temperature  and  high

humidity.

▪ If you install EKBPH140L7 in combination with RZAG71, you also

have to install the demand adaptor kit.

▪ For  installation  instructions,  see  the  installation  manual  of  the

bottom plate heater.

Demand adaptor kit (SB.KRP58M51)

▪ Can be used for the following:

▪ Low noise: To lower the operation sound of the outdoor unit.

▪ I-demand  function:  To  limit  the  power  consumption  from  the

system  (example:  budget  control,  limit  power  consumption
during peak moments…).

▪ In  combination  with  a  bottom  plate  heater  (see  above)(only  for

RZAG71).

▪ For  installation  instructions,  see  the  installation  manual  of  the

demand adaptor kit.

5

Preparation

5.1

Overview: Preparation

This chapter describes what you have to do and know before going
on-site.

It contains information about:

▪ Preparing the installation site

▪ Preparing the refrigerant piping

▪ Preparing the electrical wiring

5.2

Preparing installation site

Do NOT install the unit in places often used as work place. In case
of  construction  works  (e.g.  grinding  works)  where  a  lot  of  dust  is
created, the unit must be covered.

Choose the installation location with sufficient place for carrying the
unit in and out of the site.

5.2.1

Installation site requirements of the
outdoor unit

INFORMATION

Also read the following requirements:

▪ General  installation  site  requirements.  See  the

"General safety precautions" chapter.

▪ Service  space  requirements.  See  the  "Technical  data"

chapter.

▪ Refrigerant 

piping 

requirements 

(length, 

height

difference). See further in this "Preparation" chapter.

CAUTION

Appliance not accessible to the general public, install it in a
secured area, protected from easy access.

This  unit,  both  indoor  and  outdoor,  is  suitable  for
installation 

in 

commercial 

and 

light 

industrial

environment.

Summary of Contents for RZAG71L7V1B

Page 1: ...Installer reference guide Split system air conditioners English Installer reference guide Split system air conditioners RZAG71L7V1B RZAG100L7V1B RZAG125L7V1B RZAG140L7V1B...

Page 2: ...ping to the outdoor unit 14 6 4 9 To determine if oil traps are required 15 6 5 Checking the refrigerant piping 16 6 5 1 About checking the refrigerant piping 16 6 5 2 Precautions when checking the re...

Page 3: ...me to return to normal temperature If you must touch it wear protective gloves Do NOT touch any accidental leaking refrigerant WARNING Provide adequate measures to prevent that the unit can be used as...

Page 4: ...n pipe sizes and pipe lengths some systems require additional charging of refrigerant Only use tools exclusively for the refrigerant type used in the system this to ensure pressure resistance and prev...

Page 5: ...high frequency electric noise to avoid unnecessary opening of the earth leakage protector NOTICE Precautions when laying power wiring Do not connect wiring of different thicknesses to the power termi...

Page 6: ...ter it is installed Hand over to the user What to give and explain to the user Maintenance and service How to maintain and service the units Troubleshooting What to do in case of problems Disposal How...

Page 7: ...e demand adaptor kit For installation instructions see the installation manual of the bottom plate heater Demand adaptor kit SB KRP58M51 Can be used for the following Low noise To lower the operation...

Page 8: ...ns the measured value might be higher than the sound pressure level mentioned in Sound spectrum in the data book due to environmental noise and sound reflections INFORMATION The sound pressure level i...

Page 9: ...able for 1 8 m Floor standing units 1 8 m Wall mounted units 3 Use the graph or table to determine the minimum floor area m kg 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200...

Page 10: ...temperature Humidity Minimum thickness 30 C 75 to 80 RH 15 mm 30 C 80 RH 20 mm 5 4 Preparing electrical wiring 5 4 1 About preparing electrical wiring INFORMATION Also read the precautions and requir...

Page 11: ...oviding drainage 4 Preventing the outdoor unit from falling over 5 Protecting the unit against snow and wind by installing a snow cover and baffle plates See Preparing installation site in 5 Preparati...

Page 12: ...ting efficiency To prevent this 1 Drill a 4 and remove the knockout hole b b a b 4 6 mm 2 Remove the burrs and paint the edges and areas around the edges using repair paint to prevent rusting 6 3 6 To...

Page 13: ...Piping size mm Tightening torque N m Flare dimensions A mm Flare shape mm 9 5 33 39 12 8 13 2 R 0 4 0 8 45 2 90 2 A 15 9 63 75 19 3 19 7 6 4 4 Pipe bending guidelines Use a pipe bender for bending All...

Page 14: ...sure will be low e g when cooling will be performed while the outside air temperature is low sufficiently seal the flare nut in the stop valve on the gas line with silicon sealant to prevent freezing...

Page 15: ...ARNING Provide adequate measures to prevent that the unit can be used as a shelter by small animals Small animals that make contact with electrical parts can cause malfunctions smoke or fire NOTICE Pr...

Page 16: ...nt R32 tank siphon system e Vacuum pump f Liquid line stop valve g Gas line stop valve A Valve A B Valve B C Valve C Valve State of valve Valve A Open Valve B Open Valve C Open Liquid line stop valve...

Page 17: ...gerant piping is performed NOTICE Before completely recharging perform vacuum drying on the outdoor unit s internal refrigerant piping as well To do so use the internal service port of the outdoor uni...

Page 18: ...efrigerant Setup See 6 5 3 Checking refrigerant piping Setup on page 16 6 6 7 To charge refrigerant WARNING Only use R32 as refrigerant Other substances may cause explosions and accidents R32 contains...

Page 19: ...unit or when in thermostat stop operation 6 7 4 Guidelines when connecting the electrical wiring Keep the following in mind If stranded conductor wires are being used install a round crimp style termi...

Page 20: ...Interconnection cable Connecting to the frame When cables are routed from the unit a protection sleeve for the conduits PG insertions can be inserted at the knockout hole When you do not use a wire c...

Page 21: ...Cooling operation mode Perform the test run in cooling operation mode so that stop valves failing to open can be detected Even if the user interface was set to heating operation mode the unit will ru...

Page 22: ...heck operation for 3 minutes 4 Check operation of the airflow direction Action Result 1 Press Return Setting Return Setting Air Volume direction Air Volume Direction Position 0 Low 2 Select Position 0...

Page 23: ...efore performing any maintenance or service work touch a metal part of the unit in order to eliminate static electricity and to protect the PCB 9 3 Checklist for yearly maintenance of the outdoor unit...

Page 24: ...are open 3 Press the pump down button BS4 for at least 8 seconds BS4 is located on the PCB in the outdoor unit see wiring diagram Result The compressor and outdoor unit fan start automatically and the...

Page 25: ...s Outdoor unit RZAG71 dimensions in mm h e e f g e f g a b d c 3D103893 i 52 13 67 53 223 95 55 84 55 19 80 145 53 95 19 89 142 53 95 88 60 28 990 940 32 345 340 350 160 620 160 37 91 30 320 30 37 52...

Page 26: ...13 53 223 95 55 345 340 350 160 620 160 37 52 30 320 30 37 91 40 32 191 154 179 36 6 19 99 16 58 16 71 67 3D103894 a Gas pipe connection 15 9 flare connection b Liquid pipe connection 9 5 flare conne...

Page 27: ...B D 100 100 B D E HB HD HB HD HB HU 250 750 1000 500 HU HB HU 250 1000 1000 500 HB HU HD HU HD HU HB HD HB HD HB HD HB HD HD HU 100 1000 1000 500 HU HD HU 200 1000 1000 500 HD HU HU a b 100 100 c d e...

Page 28: ...If there is danger of drainage dripping and freezing between the upper and lower units A2 Then install a roof between the upper and lower units Install the upper unit high enough above the lower unit...

Page 29: ...ver f Stop valve with service port liquid g Stop valve with service port gas h Cable tie mountings to fix the field wiring with cable ties to ensure stress relief i Compressor accumulator A1P Printed...

Page 30: ...ervice port liquid g Stop valve with service port gas h Cable tie mountings to fix the field wiring with cable ties to ensure stress relief i Compressor accumulator A1P Printed circuit board main M1C...

Page 31: ...witch box cooling f Pressure regulating valve g Heat exchanger h Internal service port 5 16 i Check valve j Compressor accumulator k Liquid receiver l Capillary tube M1C Motor compressor R1T Thermisto...

Page 32: ...A P P P L1R A1P X1M HAP A2P F8U F7U E1H HAP L1R K10R K11M V2R R7T F6U K13R R4 V1D R5 X106A V1R 2 1 6 8 6 Q1DI DS1 X1M t 3 MS W V U Electronic component assembly Position of elements Rear view Front v...

Page 33: ...Reactor M1C Motor compressor M1F Motor fan PS Switching power supply Q1DI Earth leakage circuit breaker 30 mA R2 R5 R6 Resistor R1T Thermistor air R2T Thermistor discharge R3T Thermistor suction R4T T...

Page 34: ...2 3 1 Electronic component assembly Position of elements Rear view Front view See note 7 See note 7 Position of compressor terminal Notes 1 Symbols see below 2 Colours see below 3 This wiring diagram...

Page 35: ...S Switching power supply Q1DI Earth leakage circuit breaker 30 mA R1 R5 Resistor R1T Thermistor air R2T Thermistor discharge R3T Thermistor suction R4T Thermistor heat exchanger inlet R5T Thermistor h...

Page 36: ...direction Horizontal Motor Quantity 1 2 Model Brushless DC motor Output 94 W Drive Direct drive Compressor Quantity 1 Motor Type Hermetically sealed swing compressor Starting method Inverter driven Op...

Page 37: ...acity control method Inverter controlled Safety devices Manual high pressure switch Automatic high pressure switch low pressure switch fan driver overload protector fuse Electrical specifications RZAG...

Page 38: ...service to the product Installation manual Instruction manual specified for a certain product or application explaining how to install configure and maintain it Operation manual Instruction manual sp...

Page 39: ......

Page 40: ...4P418663 1 2016 02 Copyright 2016 Daikin...

Reviews: