8 Hand-over to the user

Installer reference guide

23

RZAG71~140L7V1B
Split system air conditioners
4P418663-1 – 2016.02

Error code

Possible cause

U2

▪ There is a voltage imbalance.

▪ There  is  a  missing  phase  in  case  of

three-phase  power  supply  units. 

Note:

Operation  will  be  impossible.  Turn  OFF
the power, recheck the wiring, and switch
two of the three electrical wires.

U4 or UF

The inter-unit branch wiring is not correct.

UA

The outdoor and indoor unit are
incompatible.

8

Hand-over to the user

Once the test run is finished and the unit operates properly, please
make sure the following is clear for the user:

▪ Make  sure  that  the  user  has  the  printed  documentation  and  ask

him/her to keep it for future reference. Inform the user that he can
find the complete documentation on the url as earlier described in
this manual.

▪ Explain the user how to properly operate the system and what to

do in case of problems.

▪ Show the user what to do in relation to maintaining the unit.

9

Maintenance and service

NOTICE

Maintenance  must  be  done  by  an  authorised  installer  or
service agent.

We  recommend  to  do  maintenance  at  least  once  a  year.
However,  applicable  legislation  might  require  shorter
maintenance intervals.

NOTICE

In  Europe,  the 

greenhouse  gas  emissions

  of  the  total

refrigerant  charge  in  the  system  (expressed  as  tonnes
CO

2

-equivalent)  is  used  to  determine  the  maintenance

intervals. Follow the applicable legislation.

Formula  to  calculate  the  greenhouse  gas  emissions:

GWP value of the refrigerant × Total refrigerant charge [in
kg] / 1000

9.1

Overview: Maintenance and
service

This chapter contains information about:

▪ The yearly maintenance of the outdoor unit

9.2

Maintenance safety precautions

DANGER: RISK OF ELECTROCUTION

DANGER: RISK OF BURNING

NOTICE: Risk of electrostatic discharge

Before performing any maintenance or service work, touch
a metal part of the unit in order to eliminate static electricity
and to protect the PCB.

9.3

Checklist for yearly maintenance
of the outdoor unit

Check the following at least once a year:

▪ Outdoor unit heat exchanger.

The  heat  exchanger  of  the  outdoor  unit  can  get  blocked  up  due  to
dust,  dirt,  leaves,  etc.  It  is  recommended  to  clean  the  heat
exchanger  yearly.  A  blocked  heat  exchanger  can  lead  to  too  low
pressure or too high pressure leading to worse performance.

10

Troubleshooting

10.1

Overview: Troubleshooting

In case of problems:

▪ See 

"7.5 Error codes when performing a test run" on page 22

.

▪ See the service manual.

Before troubleshooting

Carry  out  a  thorough  visual  inspection  of  the  unit  and  look  for
obvious defects such as loose connections or defective wiring.

10.2

Precautions when troubleshooting

WARNING

▪ When  carrying  out  an  inspection  on  the  switch  box  of

the unit, always make sure that the unit is disconnected
from the mains. Turn off the respective circuit breaker.

▪ When a safety device was activated, stop the unit and

find  out  why  the  safety  device  was  activated  before
resetting  it.  NEVER  bridge  safety  devices  or  change
their  values  to  a  value  other  than  the  factory  default
setting.  If  you  are  unable  to  find  the  cause  of  the
problem, call your dealer.

DANGER: RISK OF ELECTROCUTION

WARNING

Prevent  hazard  due  to  the  inadvertent  resetting  of  the
thermal  cut-out:  this  appliance  must  NOT  be  supplied
through  an  external  switching  device,  such  as  a  timer,  or
connected to a circuit that is regularly turned ON and OFF
by the utility.

DANGER: RISK OF BURNING

11

Disposal

11.1

Overview: Disposal

Typical workflow

Disposing of the system typically consists of the following stages:

1

Pumping down the system.

2

Dismantling the system according to the applicable legislation.

3

Treating  the  refrigerant,  oil  and  other  parts  according  to  the
applicable legislation.

INFORMATION

For more details, see the service manual.

Summary of Contents for RZAG71L7V1B

Page 1: ...Installer reference guide Split system air conditioners English Installer reference guide Split system air conditioners RZAG71L7V1B RZAG100L7V1B RZAG125L7V1B RZAG140L7V1B...

Page 2: ...ping to the outdoor unit 14 6 4 9 To determine if oil traps are required 15 6 5 Checking the refrigerant piping 16 6 5 1 About checking the refrigerant piping 16 6 5 2 Precautions when checking the re...

Page 3: ...me to return to normal temperature If you must touch it wear protective gloves Do NOT touch any accidental leaking refrigerant WARNING Provide adequate measures to prevent that the unit can be used as...

Page 4: ...n pipe sizes and pipe lengths some systems require additional charging of refrigerant Only use tools exclusively for the refrigerant type used in the system this to ensure pressure resistance and prev...

Page 5: ...high frequency electric noise to avoid unnecessary opening of the earth leakage protector NOTICE Precautions when laying power wiring Do not connect wiring of different thicknesses to the power termi...

Page 6: ...ter it is installed Hand over to the user What to give and explain to the user Maintenance and service How to maintain and service the units Troubleshooting What to do in case of problems Disposal How...

Page 7: ...e demand adaptor kit For installation instructions see the installation manual of the bottom plate heater Demand adaptor kit SB KRP58M51 Can be used for the following Low noise To lower the operation...

Page 8: ...ns the measured value might be higher than the sound pressure level mentioned in Sound spectrum in the data book due to environmental noise and sound reflections INFORMATION The sound pressure level i...

Page 9: ...able for 1 8 m Floor standing units 1 8 m Wall mounted units 3 Use the graph or table to determine the minimum floor area m kg 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200...

Page 10: ...temperature Humidity Minimum thickness 30 C 75 to 80 RH 15 mm 30 C 80 RH 20 mm 5 4 Preparing electrical wiring 5 4 1 About preparing electrical wiring INFORMATION Also read the precautions and requir...

Page 11: ...oviding drainage 4 Preventing the outdoor unit from falling over 5 Protecting the unit against snow and wind by installing a snow cover and baffle plates See Preparing installation site in 5 Preparati...

Page 12: ...ting efficiency To prevent this 1 Drill a 4 and remove the knockout hole b b a b 4 6 mm 2 Remove the burrs and paint the edges and areas around the edges using repair paint to prevent rusting 6 3 6 To...

Page 13: ...Piping size mm Tightening torque N m Flare dimensions A mm Flare shape mm 9 5 33 39 12 8 13 2 R 0 4 0 8 45 2 90 2 A 15 9 63 75 19 3 19 7 6 4 4 Pipe bending guidelines Use a pipe bender for bending All...

Page 14: ...sure will be low e g when cooling will be performed while the outside air temperature is low sufficiently seal the flare nut in the stop valve on the gas line with silicon sealant to prevent freezing...

Page 15: ...ARNING Provide adequate measures to prevent that the unit can be used as a shelter by small animals Small animals that make contact with electrical parts can cause malfunctions smoke or fire NOTICE Pr...

Page 16: ...nt R32 tank siphon system e Vacuum pump f Liquid line stop valve g Gas line stop valve A Valve A B Valve B C Valve C Valve State of valve Valve A Open Valve B Open Valve C Open Liquid line stop valve...

Page 17: ...gerant piping is performed NOTICE Before completely recharging perform vacuum drying on the outdoor unit s internal refrigerant piping as well To do so use the internal service port of the outdoor uni...

Page 18: ...efrigerant Setup See 6 5 3 Checking refrigerant piping Setup on page 16 6 6 7 To charge refrigerant WARNING Only use R32 as refrigerant Other substances may cause explosions and accidents R32 contains...

Page 19: ...unit or when in thermostat stop operation 6 7 4 Guidelines when connecting the electrical wiring Keep the following in mind If stranded conductor wires are being used install a round crimp style termi...

Page 20: ...Interconnection cable Connecting to the frame When cables are routed from the unit a protection sleeve for the conduits PG insertions can be inserted at the knockout hole When you do not use a wire c...

Page 21: ...Cooling operation mode Perform the test run in cooling operation mode so that stop valves failing to open can be detected Even if the user interface was set to heating operation mode the unit will ru...

Page 22: ...heck operation for 3 minutes 4 Check operation of the airflow direction Action Result 1 Press Return Setting Return Setting Air Volume direction Air Volume Direction Position 0 Low 2 Select Position 0...

Page 23: ...efore performing any maintenance or service work touch a metal part of the unit in order to eliminate static electricity and to protect the PCB 9 3 Checklist for yearly maintenance of the outdoor unit...

Page 24: ...are open 3 Press the pump down button BS4 for at least 8 seconds BS4 is located on the PCB in the outdoor unit see wiring diagram Result The compressor and outdoor unit fan start automatically and the...

Page 25: ...s Outdoor unit RZAG71 dimensions in mm h e e f g e f g a b d c 3D103893 i 52 13 67 53 223 95 55 84 55 19 80 145 53 95 19 89 142 53 95 88 60 28 990 940 32 345 340 350 160 620 160 37 91 30 320 30 37 52...

Page 26: ...13 53 223 95 55 345 340 350 160 620 160 37 52 30 320 30 37 91 40 32 191 154 179 36 6 19 99 16 58 16 71 67 3D103894 a Gas pipe connection 15 9 flare connection b Liquid pipe connection 9 5 flare conne...

Page 27: ...B D 100 100 B D E HB HD HB HD HB HU 250 750 1000 500 HU HB HU 250 1000 1000 500 HB HU HD HU HD HU HB HD HB HD HB HD HB HD HD HU 100 1000 1000 500 HU HD HU 200 1000 1000 500 HD HU HU a b 100 100 c d e...

Page 28: ...If there is danger of drainage dripping and freezing between the upper and lower units A2 Then install a roof between the upper and lower units Install the upper unit high enough above the lower unit...

Page 29: ...ver f Stop valve with service port liquid g Stop valve with service port gas h Cable tie mountings to fix the field wiring with cable ties to ensure stress relief i Compressor accumulator A1P Printed...

Page 30: ...ervice port liquid g Stop valve with service port gas h Cable tie mountings to fix the field wiring with cable ties to ensure stress relief i Compressor accumulator A1P Printed circuit board main M1C...

Page 31: ...witch box cooling f Pressure regulating valve g Heat exchanger h Internal service port 5 16 i Check valve j Compressor accumulator k Liquid receiver l Capillary tube M1C Motor compressor R1T Thermisto...

Page 32: ...A P P P L1R A1P X1M HAP A2P F8U F7U E1H HAP L1R K10R K11M V2R R7T F6U K13R R4 V1D R5 X106A V1R 2 1 6 8 6 Q1DI DS1 X1M t 3 MS W V U Electronic component assembly Position of elements Rear view Front v...

Page 33: ...Reactor M1C Motor compressor M1F Motor fan PS Switching power supply Q1DI Earth leakage circuit breaker 30 mA R2 R5 R6 Resistor R1T Thermistor air R2T Thermistor discharge R3T Thermistor suction R4T T...

Page 34: ...2 3 1 Electronic component assembly Position of elements Rear view Front view See note 7 See note 7 Position of compressor terminal Notes 1 Symbols see below 2 Colours see below 3 This wiring diagram...

Page 35: ...S Switching power supply Q1DI Earth leakage circuit breaker 30 mA R1 R5 Resistor R1T Thermistor air R2T Thermistor discharge R3T Thermistor suction R4T Thermistor heat exchanger inlet R5T Thermistor h...

Page 36: ...direction Horizontal Motor Quantity 1 2 Model Brushless DC motor Output 94 W Drive Direct drive Compressor Quantity 1 Motor Type Hermetically sealed swing compressor Starting method Inverter driven Op...

Page 37: ...acity control method Inverter controlled Safety devices Manual high pressure switch Automatic high pressure switch low pressure switch fan driver overload protector fuse Electrical specifications RZAG...

Page 38: ...service to the product Installation manual Instruction manual specified for a certain product or application explaining how to install configure and maintain it Operation manual Instruction manual sp...

Page 39: ......

Page 40: ...4P418663 1 2016 02 Copyright 2016 Daikin...

Reviews: