6 Installation
Installer reference guide
19
RZAG71~140L7V1B
Split system air conditioners
4P418663-1 – 2016.02
6.7
Connecting the electrical wiring
6.7.1
About connecting the electrical wiring
Typical workflow
Connecting the electrical wiring typically consists of the following
stages:
1
Making sure the power supply system complies with the
electrical specifications of the units.
2
Connecting the electrical wiring to the outdoor unit.
3
Connecting the electrical wiring to the indoor unit.
4
Connecting the main power supply.
6.7.2
About electrical compliance
RZAG
Equipment complying with EN/IEC 61000‑3‑12 (European/
International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage
systems with input current >16 A and ≤75 A per phase.).
6.7.3
Precautions when connecting the
electrical wiring
INFORMATION
Also read the precautions and requirements in the
following chapters:
▪ General safety precautions
▪ Preparation
DANGER: RISK OF ELECTROCUTION
INFORMATION
More information about the legend and the location of the
wiring diagram of the unit can be found in the "Technical
data" chapter.
WARNING
ALWAYS use multicore cable for power supply cables.
CAUTION
For use of units in applications with temperature alarm
settings it is recommended to foresee a delay of 10
minutes for signalling the alarm in case the alarm
temperature is exceeded. The unit may stop for several
minutes during normal operation for "defrosting the unit", or
when in "thermostat stop" operation.
6.7.4
Guidelines when connecting the electrical
wiring
Keep the following in mind:
▪ If stranded conductor wires are being used, install a round crimp-
style terminal on the tip. Place the round crimp-style terminal on
the wire up to the covered part and fasten the terminal with the
appropriate tool.
b
a
a
Stranded conductor wire
b
Round crimp-style terminal
▪ Use the following methods for installing wires:
Wire type
Installation method
Single core wire
c b
c
a
a
A
AA´
A´
a
Curled single core wire
b
Screw
c
Flat washer
Stranded conductor
wire with round
crimp-style terminal
c b
b
a
c
a
B
B
a
Terminal
b
Screw
c
Flat washer
Tightening torques
Item
Tightening torque (N•m)
M4 (X1M)
1.2~1.8
M4 (earth)
1.2~1.4
M5 (X1M)
2.0~3.0
M5 (earth)
2.4~2.9
6.7.5
Specifications of standard wiring
components
Component
RZAG
71
100
125+140
Power supply
cable
MCA
(a)
18.2 A
29.1 A
29.3 A
Voltage
230 V
Phase
1~
Frequency
50 Hz
Wire sizes
Must comply with applicable
legislation
Interconnection cable
Minimum cable section of
2.5 mm² and applicable for
230 V
Recommended field fuse
20 A
32 A
32 A
Earth leakage circuit breaker
Must comply with applicable
legislation
(a)
MCA=Minimum circuit ampacity. Stated values are
maximum values (see electrical data of combination with
indoor units for exact values).
6.7.6
To connect the electrical wiring on the
outdoor unit
NOTICE
▪ Follow the wiring diagram (delivered with the unit,
located at the inside of the service cover).
▪ Make sure the electrical wiring does NOT obstruct
proper reattachment of the service cover.
1
Remove the service cover. See
"6.2.2 To open the outdoor
unit" on page 11
.
2
Strip insulation (20 mm) from the wires.
Summary of Contents for RZAG71L7V1B