6 Installation

Installer reference guide

16

RZAG71~140L7V1B

Split system air conditioners

4P418663-1 – 2016.02

6.5

Checking the refrigerant piping

6.5.1

About checking the refrigerant piping

The outdoor unit's 

internal

 refrigerant piping has been factory tested

for  leaks.  You  only  have  to  check  the  outdoor  unit's 

external

refrigerant piping.

Before checking the refrigerant piping

Make  sure  the  refrigerant  piping  is  connected  between  the  outdoor
unit and the indoor unit.

Typical workflow

Checking  the  refrigerant  piping  typically  consists  of  the  following
stages:

1

Checking for leaks in the refrigerant piping.

2

Performing  vacuum  drying  to  remove  all  moisture,  air  or
nitrogen from the refrigerant piping.

If  there  is  a  possibility  of  moisture  being  present  in  the  refrigerant
piping  (for  example,  water  may  have  entered  the  piping),  first  carry
out  the  vacuum  drying  procedure  below  until  all  moisture  has  been
removed.

6.5.2

Precautions when checking the
refrigerant piping

INFORMATION

Also  read  the  precautions  and  requirements  in  the
following chapters:

▪ General safety precautions

▪ Preparation

NOTICE

Use  a  2-stage  vacuum  pump  with  a  non-return  valve  that
can  evacuate  to  a  gauge  pressure  of  −⁠100.7  kPa  (5  Torr
absolute). Make sure the pump oil does not flow oppositely
into the system while the pump is not working.

NOTICE

Use  this  vacuum  pump  for  R32  exclusively.  Using  the
same  pump  for  other  refrigerants  may  damage  the  pump
and the unit.

NOTICE

▪ Connect  the  vacuum  pump  to 

both

  the  service  port  of

the  gas  stop  valve  and  the  service  port  of  the  liquid
stop valve to increase efficiency.

▪ Make sure that the gas stop valve and liquid stop valve

are  firmly  closed  before  performing  the  leak  test  or
vacuum drying.

6.5.3

Checking refrigerant piping: Setup

p< p>

N2

C

b

c

e

a

g

f

d

A

B

a

Pressure reducing valve

b

Nitrogen

c

Weighing scales

d

Refrigerant R32 tank (siphon system)

e

Vacuum pump

f

Liquid line stop valve

g

Gas line stop valve

A

Valve A

B

Valve B

C

Valve C

Valve

State of valve

Valve A

Open

Valve B

Open

Valve C

Open

Liquid line stop valve

Close

Gas line stop valve

Close

NOTICE

Indoor units should also be leak and vacuum tested. Keep
any  possible  (field  supplied)  field  piping  valves  open  as
well.

6.5.4

To check for leaks

NOTICE

Do NOT exceed the unit's maximum working pressure (see
"PS High" on the unit name plate).

NOTICE

Make  sure  to  use  a  recommended  bubble  test  solution
from  your  wholesaler.  Do  not  use  soap  water,  which  may
cause cracking of flare nuts (soap water may contain salt,
which  absorbs  moisture  that  will  freeze  when  the  piping
gets  cold),  and/or  lead  to  corrosion  of  flared  joints  (soap
water  may  contain  ammonia  which  causes  a  corrosive
effect between the brass flare nut and the copper flare).

1

Charge the system with nitrogen gas up to a gauge pressure of
at  least  200  kPa  (2  bar).  It  is  recommended  to  pressurize  to
3000 kPa (30 bar) in order to detect small leaks.

2

Check  for  leaks  by  applying  the  bubble  test  solution  to  all
connections.

3

Discharge all nitrogen gas.

INFORMATION

After opening the stop valve, it is possible that the pressure
in the refrigerant piping does NOT increase. This might be
caused  by  e.g.  the  closed  state  of  the  expansion  valve  in
the outdoor unit circuit, but does NOT present any problem
for correct operation of the unit.

6.5.5

To perform vacuum drying

1

Vacuum the system until the pressure on the manifold indicates
−0.1 MPa (−1 bar).

2

Leave as is for 4-5 minutes and check the pressure:

If the pressure…

Then…

Does not change

There is no moisture in the
system. This procedure is
finished.

Increases

There is moisture in the
system. Go to the next step.

3

Evacuate  for  at  least  2  hours  to  a  pressure  on  the  manifold  of
−0.1 MPa (−1 bar).

4

After  turning  OFF  the  pump,  check  the  pressure  for  at  least
1 hour.

5

If you do NOT reach the target vacuum or cannot maintain the
vacuum for 1 hour, do the following:

▪ Check for leaks again.
▪ Perform vacuum drying again.

Summary of Contents for RZAG71L7V1B

Page 1: ...Installer reference guide Split system air conditioners English Installer reference guide Split system air conditioners RZAG71L7V1B RZAG100L7V1B RZAG125L7V1B RZAG140L7V1B...

Page 2: ...ping to the outdoor unit 14 6 4 9 To determine if oil traps are required 15 6 5 Checking the refrigerant piping 16 6 5 1 About checking the refrigerant piping 16 6 5 2 Precautions when checking the re...

Page 3: ...me to return to normal temperature If you must touch it wear protective gloves Do NOT touch any accidental leaking refrigerant WARNING Provide adequate measures to prevent that the unit can be used as...

Page 4: ...n pipe sizes and pipe lengths some systems require additional charging of refrigerant Only use tools exclusively for the refrigerant type used in the system this to ensure pressure resistance and prev...

Page 5: ...high frequency electric noise to avoid unnecessary opening of the earth leakage protector NOTICE Precautions when laying power wiring Do not connect wiring of different thicknesses to the power termi...

Page 6: ...ter it is installed Hand over to the user What to give and explain to the user Maintenance and service How to maintain and service the units Troubleshooting What to do in case of problems Disposal How...

Page 7: ...e demand adaptor kit For installation instructions see the installation manual of the bottom plate heater Demand adaptor kit SB KRP58M51 Can be used for the following Low noise To lower the operation...

Page 8: ...ns the measured value might be higher than the sound pressure level mentioned in Sound spectrum in the data book due to environmental noise and sound reflections INFORMATION The sound pressure level i...

Page 9: ...able for 1 8 m Floor standing units 1 8 m Wall mounted units 3 Use the graph or table to determine the minimum floor area m kg 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200...

Page 10: ...temperature Humidity Minimum thickness 30 C 75 to 80 RH 15 mm 30 C 80 RH 20 mm 5 4 Preparing electrical wiring 5 4 1 About preparing electrical wiring INFORMATION Also read the precautions and requir...

Page 11: ...oviding drainage 4 Preventing the outdoor unit from falling over 5 Protecting the unit against snow and wind by installing a snow cover and baffle plates See Preparing installation site in 5 Preparati...

Page 12: ...ting efficiency To prevent this 1 Drill a 4 and remove the knockout hole b b a b 4 6 mm 2 Remove the burrs and paint the edges and areas around the edges using repair paint to prevent rusting 6 3 6 To...

Page 13: ...Piping size mm Tightening torque N m Flare dimensions A mm Flare shape mm 9 5 33 39 12 8 13 2 R 0 4 0 8 45 2 90 2 A 15 9 63 75 19 3 19 7 6 4 4 Pipe bending guidelines Use a pipe bender for bending All...

Page 14: ...sure will be low e g when cooling will be performed while the outside air temperature is low sufficiently seal the flare nut in the stop valve on the gas line with silicon sealant to prevent freezing...

Page 15: ...ARNING Provide adequate measures to prevent that the unit can be used as a shelter by small animals Small animals that make contact with electrical parts can cause malfunctions smoke or fire NOTICE Pr...

Page 16: ...nt R32 tank siphon system e Vacuum pump f Liquid line stop valve g Gas line stop valve A Valve A B Valve B C Valve C Valve State of valve Valve A Open Valve B Open Valve C Open Liquid line stop valve...

Page 17: ...gerant piping is performed NOTICE Before completely recharging perform vacuum drying on the outdoor unit s internal refrigerant piping as well To do so use the internal service port of the outdoor uni...

Page 18: ...efrigerant Setup See 6 5 3 Checking refrigerant piping Setup on page 16 6 6 7 To charge refrigerant WARNING Only use R32 as refrigerant Other substances may cause explosions and accidents R32 contains...

Page 19: ...unit or when in thermostat stop operation 6 7 4 Guidelines when connecting the electrical wiring Keep the following in mind If stranded conductor wires are being used install a round crimp style termi...

Page 20: ...Interconnection cable Connecting to the frame When cables are routed from the unit a protection sleeve for the conduits PG insertions can be inserted at the knockout hole When you do not use a wire c...

Page 21: ...Cooling operation mode Perform the test run in cooling operation mode so that stop valves failing to open can be detected Even if the user interface was set to heating operation mode the unit will ru...

Page 22: ...heck operation for 3 minutes 4 Check operation of the airflow direction Action Result 1 Press Return Setting Return Setting Air Volume direction Air Volume Direction Position 0 Low 2 Select Position 0...

Page 23: ...efore performing any maintenance or service work touch a metal part of the unit in order to eliminate static electricity and to protect the PCB 9 3 Checklist for yearly maintenance of the outdoor unit...

Page 24: ...are open 3 Press the pump down button BS4 for at least 8 seconds BS4 is located on the PCB in the outdoor unit see wiring diagram Result The compressor and outdoor unit fan start automatically and the...

Page 25: ...s Outdoor unit RZAG71 dimensions in mm h e e f g e f g a b d c 3D103893 i 52 13 67 53 223 95 55 84 55 19 80 145 53 95 19 89 142 53 95 88 60 28 990 940 32 345 340 350 160 620 160 37 91 30 320 30 37 52...

Page 26: ...13 53 223 95 55 345 340 350 160 620 160 37 52 30 320 30 37 91 40 32 191 154 179 36 6 19 99 16 58 16 71 67 3D103894 a Gas pipe connection 15 9 flare connection b Liquid pipe connection 9 5 flare conne...

Page 27: ...B D 100 100 B D E HB HD HB HD HB HU 250 750 1000 500 HU HB HU 250 1000 1000 500 HB HU HD HU HD HU HB HD HB HD HB HD HB HD HD HU 100 1000 1000 500 HU HD HU 200 1000 1000 500 HD HU HU a b 100 100 c d e...

Page 28: ...If there is danger of drainage dripping and freezing between the upper and lower units A2 Then install a roof between the upper and lower units Install the upper unit high enough above the lower unit...

Page 29: ...ver f Stop valve with service port liquid g Stop valve with service port gas h Cable tie mountings to fix the field wiring with cable ties to ensure stress relief i Compressor accumulator A1P Printed...

Page 30: ...ervice port liquid g Stop valve with service port gas h Cable tie mountings to fix the field wiring with cable ties to ensure stress relief i Compressor accumulator A1P Printed circuit board main M1C...

Page 31: ...witch box cooling f Pressure regulating valve g Heat exchanger h Internal service port 5 16 i Check valve j Compressor accumulator k Liquid receiver l Capillary tube M1C Motor compressor R1T Thermisto...

Page 32: ...A P P P L1R A1P X1M HAP A2P F8U F7U E1H HAP L1R K10R K11M V2R R7T F6U K13R R4 V1D R5 X106A V1R 2 1 6 8 6 Q1DI DS1 X1M t 3 MS W V U Electronic component assembly Position of elements Rear view Front v...

Page 33: ...Reactor M1C Motor compressor M1F Motor fan PS Switching power supply Q1DI Earth leakage circuit breaker 30 mA R2 R5 R6 Resistor R1T Thermistor air R2T Thermistor discharge R3T Thermistor suction R4T T...

Page 34: ...2 3 1 Electronic component assembly Position of elements Rear view Front view See note 7 See note 7 Position of compressor terminal Notes 1 Symbols see below 2 Colours see below 3 This wiring diagram...

Page 35: ...S Switching power supply Q1DI Earth leakage circuit breaker 30 mA R1 R5 Resistor R1T Thermistor air R2T Thermistor discharge R3T Thermistor suction R4T Thermistor heat exchanger inlet R5T Thermistor h...

Page 36: ...direction Horizontal Motor Quantity 1 2 Model Brushless DC motor Output 94 W Drive Direct drive Compressor Quantity 1 Motor Type Hermetically sealed swing compressor Starting method Inverter driven Op...

Page 37: ...acity control method Inverter controlled Safety devices Manual high pressure switch Automatic high pressure switch low pressure switch fan driver overload protector fuse Electrical specifications RZAG...

Page 38: ...service to the product Installation manual Instruction manual specified for a certain product or application explaining how to install configure and maintain it Operation manual Instruction manual sp...

Page 39: ......

Page 40: ...4P418663 1 2016 02 Copyright 2016 Daikin...

Reviews: