background image

Installation and operation manual

59

RYYQ+RYMQ+RXYQ8~20T7Y1B

VRV IV System Air Conditioner

4P329765-1 – 2012.09

8.

Maintenance

8.1.

Maintenance after a long stop period (e.g., at the 
beginning of the season)

Check and remove everything that might be blocking inlet and
outlet vents of indoor units and outdoor units.

Clean air filters and casings of indoor units

(9)

. Refer to the

operation manual supplied with the indoor units for details on
how to proceed and make sure to install cleaned air filters back
in the same position.

Turn on the power at least 6 hours before operating the unit in
order to ensure smoother operation. As soon as the power is
turned on, the user interface display appears.

8.2.

Maintenance before a long stop period (e.g., at the 
end of the season)

Let the indoor units run in fan only operation for about half a day
in order to dry the interior of the units. Refer to 

"6.1. Cooling,

heating, fan only, and automatic operation" on page 55

 for

details on fan only operation.

Turn off the power. The user interface display disappears.

Clean air filters and casings of indoor units

(9)

. Refer to the

operation manual supplied with the indoor units for details on
how to proceed and make sure to install cleaned air filters back
in the same position.

9.

Symptoms that are not air conditioner 
troubles

Following symptoms are not air conditioner troubles:

Symptom 1: The system does not operate

The air conditioner does not start immediately after the ON/OFF
button on the user interface is pressed. If the operation lamp
lights, the system is in normal condition. To prevent overloading
of the compressor motor, the air conditioner starts 5 minutes
after it is turned ON again in case it was turned OFF just before.
The same starting delay occurs after the operation mode
selector button was used.

If "Under Centralized Control" is displayed on the user interface
and pressing the operation button causes the display to blink for
a few seconds indicating that the central device is controlling the
unit. The blinking display indicates that the user interface cannot
be used.

The system does not start immediately after the power supply is
turned on. Wait one minute until the micro computer is prepared
for operation.

Symptom 2: Cool/Heat cannot be changed over

When the display shows 

 

(change-over under centralized

control), it shows that this is a slave user interface.

When the cool/heat changeover remote control switch is
installed and the display shows 

 (change-over under

centralized control). This is because cool/heat changeover is
controlled by the cool/ heat changeover remote control switch.
Ask your dealer where the remote control switch is installed.

Symptom 3: Fan operation is possible, but cooling and heating
do not work

Immediately after the power is turned on. The micro computer is
getting ready to operate and is performing a communication
check with all indoor units. Please wait 12 minutes (max.) till this
process is finished.

Symptom 4: The fan strength does not correspond to the setting

The fan speed does not change even if the fan speed
adjustment button in pressed. During heating operation, when
the room temperature reaches the set temperature, the outdoor
unit goes off and the indoor unit changes to whisper fan speed.
This is to prevent cold air blowing directly on occupants of the
room. The fan speed will not change even if the button is
pressed, when another indoor unit is in heating operation.

Symptom 5: The fan direction does not correspond to the
setting

The fan direction does not correspond with the user interface
display. The fan direction does not swing. This is because the
unit is being controlled by the micro computer.

Symptom 6: White mist comes out of a unit

Symptom 6.1: Indoor unit

When humidity is high during cooling operation
If the interior of an indoor unit is extremely contaminated, the
temperature distribution inside a room becomes uneven. It is
necessary to clean the interior of the indoor unit. Ask your dealer
for details on cleaning the unit. This operation requires a
qualified service person.

Immediately after the cooling operation stops and if the room
temperature and humidity are low. This is because warm
refrigerant gas flows back into the indoor unit and generates
steam. 

Symptom 6.2: Indoor unit, outdoor unit

When the system is changed over to heating operation after
defrost operation. Moisture generated by defrost becomes
steam and is exhausted.

Symptom 7: The user interface display reads "

U4

" or "

U5

" and

stops, but then restarts after a few minutes

This is because the user interface is intercepting noise from
electric appliances other than the air conditioner. The noise
prevents communication between the units, causing them to
stop. Operation automatically restarts when the noise ceases.

Symptom 8: Noise of air conditioners

Symptom 8.1: Indoor unit

A "zeen" sound is heard immediately after the power supply is
turned on. 
The electronic expansion valve inside an indoor unit starts
working and makes the noise. Its volume will reduce in about
one minute.

A continuous low "shah" sound is heard when the system is in
cooling operation or at a stop.
When the drain pump (optional accessories) is in operation, this
noise is heard.

A "pishi-pishi" squeaking sound is heard when the system stops
after heating operation.
Expansion and contraction of plastic parts caused by
temperature change make this noise.

A low "sah", "choro-choro" sound is heard while the indoor unit is
stopped.
When the other indoor unit is in operation, this noise is heard. In
order to prevent oil and refrigerant from remaining in the system,
a small amount of refrigerant is kept flowing.

CAUTION

Pay attention to the fan.

It is dangerous to inspect the unit while the fan is running.

Be sure to turn off the main switch and to remove the fuses
from the control circuit located in the outdoor unit.

(9) Contact your installer or maintenance person to clean air filters 

and casings of the indoor unit. Maintenance tips and 
procedures for cleaning are provided in the 
installation/operation manuals of dedicated indoor units.

Summary of Contents for RYYQ8T7Y1B

Page 1: ...8T7Y1B RYYQ10T7Y1B RYYQ12T7Y1B RYYQ14T7Y1B RYYQ16T7Y1B RYYQ18T7Y1B RYYQ20T7Y1B RYMQ8T7Y1B RYMQ10T7Y1B RYMQ12T7Y1B RYMQ14T7Y1B RYMQ16T7Y1B RYMQ18T7Y1B RYMQ20T7Y1B RXYQ8T7Y1B RXYQ10T7Y1B RXYQ12T7Y1B RXY...

Page 2: ...6 12 20 19 18 22 8 18 4 5 3 3 6 17 4 5 16 22 20 19 7 8 9 15 1 18 12 13 11 R3T R6T R5T R7T R1T R4T R21T 1 2 14 13 11 11 5 4 4 5 6 12 10 7 9 15 16 20 19 18 22 8 18 3 sv INV INV HPS sv sv HPS M2F M M1F M...

Page 3: ...1C M1F S1NPH S1NPL S1PH HPS 3 6 17 4 5 16 20 21 19 7 8 15 1 18 12 13 11 R3T R6T R5T R7T R1T R4T R21T R22T 1 2 14 13 11 11 6 12 10 7 15 16 8 18 5 4 4 5 3 sv M sv INV INV sv M2F M M1F M2C M1C Y1E S1NPH...

Page 4: ...i den Tekniske Konstruksjonsfilen D og gjennom positiv bed mmelse av E Anvendt modul F G Risikokategori H Se ogs neste side 13 jotka on esitetty asiakirjassa A ja jotka B on hyv ksynyt Sertifikaatin C...

Page 5: ...PS vastav k llastunud temperatuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksimal...

Page 6: ...onnecting the PC configurator to the outdoor unit 31 14 Charging refrigerant 31 14 1 Precautions 31 14 2 Important information regarding the refrigerant used 32 14 3 Calculating the additional refrige...

Page 7: ...service In Europe EN 378 provides the necessary guidance for this logbook 3 Introduction 3 1 General information This installation manual concerns the VRV IV full inverter driven heat pump system Mode...

Page 8: ...door unit combinations Single unit stand alone outdoor unit can be chosen from two ranges The RYYQ model continuous heating or RXYQ model non continuous heating The RYYQ models provide continuous comf...

Page 9: ...ccessories supplied with this unit See location 1 in the figure below for reference to where following accessories are supplied with the unit See location 1 in the figure above for reference to where...

Page 10: ...ection 25 4 28 6 25 4 28 6 25 4 28 6 Bottom connection 25 4 28 6 25 4 28 6 25 4 28 6 Liquid pipe Front connection 12 7 15 9 Bottom connection 12 7 15 9 Equalizer pipe a a Only for RYMQ models Front co...

Page 11: ...F 6 Accumulator 7 Expansion valve main Y1E 8 Expansion valve subcool heat exchanger Y2E 9 Expansion valve storage vessel Y3E 10 Subcool heat exchanger 11 Oil separator 12 Solenoid valve oil accumulato...

Page 12: ...in a potentially explosive atmosphere Select the location of the unit in such a way that the sound generated by the unit does not disturb anyone and the location is selected according the applicable l...

Page 13: ...t improper installation may result in the unit turning over 6 2 Weather related precautions Select a place where the rain can be avoided as much as possible Be sure that the air inlet of the unit is n...

Page 14: ...y indicated service space dimensions 4 15x22 5 515 76 765 76 272 328 373 930 97 107 131 179 259 276 122 766 729 137 1685 mm R X Y Y M Q8 12 4 15x22 5 97 272 328 373 1240 107 131 179 259 276 122 1685 7...

Page 15: ...npacking Relief the unit from its packing material Take care not to damage the unit when removing the shrink foil with a cutter 1 Remove the 4 bolts fixing the unit to its pallet 2 Make sure that all...

Page 16: ...rain waste water from around the unit During heating operation and when the outdoor temperatures are negative the drained water from the outdoor unit will freeze up If the water drainage is not taken...

Page 17: ...of the main pipes 1 Outdoor unit 2 Main pipes 3 Increase 4 First refrigerant branch kit 5 Indoor unit The pipe thickness of the refrigerant piping shall comply with the applicable legislation The mini...

Page 18: ...ctions Make sure to perform the piping installation within the range of the maximum allowable pipe length allowable level difference and allowable length after branching as indicated below Three patte...

Page 19: ...g kit Actual piping length 165 m 135 m Example 1 1 unit 8 a b c d e f g p 165 m Example 2 1 unit 8 a b c d e f g p 135 m Example 1 2 unit 6 a b h 165 m unit 8 a i k 165 m Example 1 3 unit 8 a i 165 m...

Page 20: ...height difference Maximum allowable length after branch The pipe length from the first refrigerant branch kit to the indoor unit 50 m Example b g l 50 m If the piping length between the first branch...

Page 21: ...allation manual delivered with the kit 9 6 2 Possible installation patterns and configurations The piping between the outdoor units must be routed level or slightly upward to avoid the risk of oil ret...

Page 22: ...oxidants when brazing the pipe joints Residue can clog pipes and break equipment Do not use flux when brazing copper to copper refrigerant piping Use phosphor copper brazing filler alloy BCuP which d...

Page 23: ...ped out before continuing with the connection of the field piping in case the recovery was not complete 10 2 3 Connecting refrigerant piping to the outdoor unit Connection from the stop valves to the...

Page 24: ...op valve Make sure to keep both stop valves open during operation The figure below shows the name of each part required in handling the stop valve The stop valve is factory closed 10 3 2 How to use th...

Page 25: ...top valves are firmly closed before performing leak test or vacuum drying See 10 4 4 Setup on page 21 and 10 4 Leak test and vacuum drying on page 20 10 4 3 Installation of refrigerant piping leak tes...

Page 26: ...temperature of 70 C for liquid piping and polyethylene foam which can withstand a temperature of 120 C for gas piping Reinforce the insulation on the refrigerant piping according to the installation e...

Page 27: ...sure to install an earth leakage protector in accordance with the applicable legislation Failure to do so may cause electric shock or fire Be sure to use a dedicated power circuit never use a power s...

Page 28: ...Thermistor subcool liq pipe R6T Thermistor heat exc gas pipe R7T Thermistor heat exc de icer R8T Thermistor M2C body S1NPH Pressure sensor high S1NPL Pressure sensor low S1PH S2PH Pressure switch high...

Page 29: ...esult in communication error CAUTION Do not apply excessive force when opening the electronic component box cover Excessive force can deform the cover resulting in entering of water to cause equipment...

Page 30: ...In Out terminals on the PC board in the outdoor unit After installing the transmission wires inside the unit wrap them along with the on site refrigerant pipes using finishing tape as shown in figure...

Page 31: ...ith tie wraps to low voltage wiring See figures below items 2 and 6 1 Transmission wiring 2 Fix wiring with tie wrap 3 Possible power supply wire entrance hole 6 4 Possible transmission wire entrance...

Page 32: ...ole 7 5 Alternative power supply routing 12 6 3 Precautions when knocking out knockout holes To punch a knockout hole hit on it with a hammer After knocking out the holes we recommend removing any bur...

Page 33: ...the indoor units is connected 12 7 2 Connection of wiring to terminals Transmission wiring in outdoor unit 1 Fix to the indicated plastic brackets using field supplied clamping material 2 Wiring betwe...

Page 34: ...mponent box service cover Operate the switches and push buttons with an insulated stick such as a closed ball point pen to avoid touching of live parts Make sure to re attach the inspection cover into...

Page 35: ...accordingly The communication wiring should be checked at first Accessing modes BS1 is used to change the mode you want to access Access mode 1 Push BS1 one time Segment indication changes to Access...

Page 36: ...gain by pushing BS3 To leave the monitoring function push BS1 2 times you will return to the default situation when shipped from factory 13 2 2 Operating the DIP switches By operating the DIP switches...

Page 37: ...ith connection ratio limitation has to be respected More detailed information can be found in technical engineering data INFORMATION National implementation of EU regulation on certain fluorinated gre...

Page 38: ...to test run see 15 5 Test operation on page 44 R Q R Q R Q You want to execute automatic refrigerant charge B A Step 4b 5 Manual refrigerant charging method in cooling operation NO YES Step 4b 5 Auto...

Page 39: ...tomatically PE charging nearly finished P9 charging finished OR P kg was added during autocharge R Q P Close valve A Push BS1 to leave program Charging is finished Fill in the amount on the additional...

Page 40: ...charging then close valve C and go to step 5 Follow step 6 depending on the chosen charging method 5 After pre charging perform the refrigerant charge operation as shown below and charge the remainin...

Page 41: ...user interface of indoor unit shows P9 This indicates the automatic charging in cooling program was finished successfully If during the cooling operation for the automatic refrigerant charge the ambi...

Page 42: ...es and vibrations when starting up the unit 2 Field wiring Be sure that the field wiring has been carried out according to the instructions described in the chapter 12 Electrical wiring work on page 2...

Page 43: ...he unit s logic The master unit should be used to input field settings in mode 2 1 1 shows the status of low noise operation 1 unit is currently operating under low noise restrictions 0 unit is curren...

Page 44: ...matic leak detection operation 1 normal execution of leak detection operation occurred 2 operation conditions during leak detection operation were not satisfied ambient temperature was not within the...

Page 45: ...omatic refrigerant charging functionality following setting should be applied Further instructions regarding the different ways to charge additional refrigerant into your system can be found in chapte...

Page 46: ...ion approximately 1 6h00 2 7h00 3 8h00 default Value 2 30 Power consumption limitation approximately 1 60 2 65 3 70 default 4 75 5 80 6 85 7 90 8 95 Value 2 31 Power consumption limitation approximate...

Page 47: ...and comfort for the particular application Several patterns are available and explained below Modify the parameters to the needs of your building and to realize the best balance between energy consum...

Page 48: ...ant temperature in order to achieve the required room temperature very fast The overshoot is allowed from the start up moment In case of cooling operation the evaporating temperature is allowed to go...

Page 49: ...the electrical component box inspection opening service cover 2 Make sure all field settings you want are set see 15 2 Monitoring function and field settings on page 38 3 Turn ON the power to the outd...

Page 50: ...eration The malfunction code which is displayed on the outdoor unit will indicate a main malfunction code and a sub code The sub code indicates more detailed information about the malfunction code The...

Page 51: ...e A1P X20A X28A X40A Check connection P1 01 02 03 INV1 unbalanced power supply voltage Check if power supply is within range 07 08 09 INV2 unbalanced power supply voltage Check if power supply is with...

Page 52: ...set Check following items before retrying autocharge procedure Check if the gas side stop valve is opened correctly Check if the valve of the refrigerant cylinder is opened Check if the air inlet and...

Page 53: ...that air conditioning facilities are installed in a room which is sufficiently large This assures that the maximum concentration level of refrigerant gas is not exceeded in the unlikely event of major...

Page 54: ...here is a room division but there is an opening between the rooms sufficiently large to permit a free flow of air back and forth 1 Opening between the rooms 2 Partition Where there is an opening witho...

Page 55: ...W 750 Compressor quantity 1 2 model inverter type hermetically sealed scroll compressor crankcase heater W 33 Sound level nominal e sound power f dBA 78 79 81 sound pressure g dBA 58 61 Refrigerant t...

Page 56: ...the ground fault circuit interrupter earth leakage circuit breaker A 20 25 32 Total overcurrent amps TOCA e e TOCA means the total value of each OC set A 17 3 24 6 35 4 Full load amps FLA f f FLA nomi...

Page 57: ...ant how to install configure operate and or maintain the product or application Dealer Sales distributor for products as per the subject of this manual Installer Technical skilled person who is qualif...

Page 58: ...hotbed for small animals which can enter the unit Once in the unit such animals can cause malfunctions smoke or fire when making contact with electrical parts Ask your dealer for improvement repair a...

Page 59: ...problems may happen For checking and adjusting the internal parts contact your dealer Do not touch the heat exchanger fins These fins are sharp and could result in cutting injuries NOTICE Never put an...

Page 60: ...bove operation range is only valid in case direct expansion indoor units are connected to the VRV IV system Special operation ranges are valid in case of using Hydrobox units or AHU They can be found...

Page 61: ...to decrease the humidity in your room with minimal temperature decrease minimal room cooling The micro computer automatically determines temperature and fan speed cannot be set by the user interface...

Page 62: ...w to designate the master user interface In case only VRV DX indoor units and Hydrobox units are connected to the VRV IV system 1 Press the operation mode selector button of the current master user in...

Page 63: ...al Keep the indoor unit and user interface at least 1 m away from televisions radios stereos and other similar equipment Failing to do so may cause static or distorted pictures Do not place items unde...

Page 64: ...ocess is finished Symptom 4 The fan strength does not correspond to the setting The fan speed does not change even if the fan speed adjustment button in pressed During heating operation when the room...

Page 65: ...from the unit Measure Stop the operation The operation switch does not work well Measure Turn off the power If the user interface display indicates the unit number the operation lamp flashes and the m...

Page 66: ...acement cycle of wear parts Table 2 Replacement Cycle list Moving and discarding the unit Contact your dealer for removing and reinstalling the total unit Moving units requires technical expertise Thi...

Page 67: ...E5 Compressor lock detection outdoor E7 Fan motor malfunction outdoor E9 Electronic expansion valve malfunction outdoor F3 Discharge temperature malfunction outdoor F4 Abnormal suction temperature out...

Page 68: ......

Page 69: ......

Page 70: ......

Page 71: ...S1NPL S1NPH S1PH HPS R8T 10 12HP 3 6 17 4 5 20 19 7 8 15 1 18 12 13 11 1 2 11 11 14 13 6 12 10 7 15 20 19 18 8 18 3 5 4 4 5 M sv sv INV INV sv M1C M2C M1F M M2F S1NPH S1NPL S1PH S2PH HPS R6T R5T R7T...

Page 72: ...4P329765 1 2012 09 Copyright 2012 Daikin 4P329765 1 0000000U...

Reviews: