RYYQ+RYMQ+RXYQ8~20T7Y1B
VRV IV System Air Conditioner
4P329765-1 – 2012.09
Installation and operation manual
50
20. Unit specifications
20.1. General technical specifications
INFORMATION
For technical and electrical details of multi unit
combinations, see technical engineering data.
RXYQ8T
RYYQ8T
RYMQ8T
RXYQ10T
RYYQ10T
RYMQ10T
RXYQ12T
RYYQ12T
RYMQ12T
RXYQ14T
RYYQ14T
RYMQ14T
Casing material
Painted galvanised steel
Dimensions h x w x d
(mm)
1685x930x765
1685x1240
x765
Weight
• RXYQ
(kg)
183
190
304
• RYYQ
(kg)
261
268
364
• RYMQ
(kg)
188
195
309
Operation range
• cooling (min./max.)
(°C)
–5/43
• heating (min./max.)
(°C)
–20/21
Cooling
(a)
(a) Nominal cooling capacities are based on indoor temperature 27°C DB and
19°C WB, outdoor temperature 35°C DB, equivalent refrigerant piping: 5 m, level
difference: 0 m.
• capacity
(kW)
22.4
28.0
33.5
40.0
• EER
4.30
3.84
3.73
3.64
Heating
(b)
(b) Nominal cooling capacities are based on indoor temperature 20°C DB, outdoor
temperature 7°C DB and 6°C WB, equivalent refrigerant piping: 5 m, level
difference: 0 m.
• capacity
(kW)
25.0
31.5
37.5
45.0
• COP
4.54
4.27
4.12
4.02
PED
• category
2
• Most critical part
Accumulator
• PS*V
(bar*l)
325
415
Maximum number of indoor
units connected
(c)
(c) Actual number of units depends on the indoor unit type (VRV DX, Hydrobox,
RA DX, ...) and the connection ratio restriction for the system (50%
≤
CR
≤
130%).
64
Heat exchanger
• type
cross fin
• treatment
anti corrosion
Fan
• type
propeller
• quantity
1
2
• air flow rate
(d)
(d) Nominal at 230 V.
(m
3
/min)
162
175
185
223
• motor
1
2
• model
brushless DC
• output/pcs
(W)
750
Compressor
• quantity
1
2
• model
inverter
• type
hermetically sealed scroll compressor
• crankcase heater
(W)
33
Sound level (nominal)
(e)
• sound power
(f)
(dBA)
78
79
81
• sound pressure
(g)
(dBA)
58
61
Refrigerant
• type
R410A
• charge
(kg)
5.9
6
6.3
10.3
Refrigerant oil
Synthetic (ether) oil
Safety devices
• High pressure switch
• Fan driver overload protector
• Inverter overload protector
• PC board fuse
(e) Sound values are measured in a semi-anechoic room.
(f) Sound power level is an absolute value that a sound generates.
(g) Sound pressure level is a relative value depending on the distance and acoustic
environment. For more details, refer to sound level drawings in the technical data
book.
RXYQ16T
RYYQ16T
RYMQ16T
RXYQ18T
RYYQ18T
RYMQ18T
RXYQ20T
RYYQ20T
RYMQ20T
Casing material
Painted galvanised steel
Dimensions h x w x d
(mm)
1685x1240x765
Weight
• RXYQ
(kg)
304
314
• RYYQ
(kg)
364
398
• RYMQ
(kg)
309
319
Operation range
• cooling (min./max.)
(°C)
–5/43
• heating (min./max.)
(°C)
–20/21
Cooling
(a)
• capacity
(kW)
45.0
50.0
56.0
• EER
3.46
3.40
3.03
Heating
(b)
• capacity
(kW)
50.0
56.0
63.0
• COP
3.91
3.89
3.71
PED
• category
2
• Most critical part
Accumulator
• PS*V
(bar*l)
415
492.5
Maximum number of indoor
units connected
(c)
64
Heat exchanger
• type
cross fin
• treatment
anti corrosion
Fan
• type
propeller
• quantity
2
• air flow rate
(d)
(m
3
/min)
260
251
261
• motor
2
• model
brushless DC
• output/pcs
(W)
750
Compressor
• quantity
2
• model
inverter
• type
hermetically sealed scroll
compressor
• crankcase heater
(W)
33
Sound level (nominal)
(e)
• sound power
(f)
(dBA)
86
88
• sound pressure
(g)
(dBA)
64
65
66
Refrigerant
• type
R410A
• charge
10.4
11.7
11.8
Refrigerant oil
Synthetic (ether) oil
Safety devices
• High pressure switch
• Fan driver overload protector
• Inverter overload protector
• PC board fuse