18.2. Maximum concentration level
The maximum charge of refrigerant and the calculation of the
maximum concentration of refrigerant is directly related to the
humanly occupied space in to which it could leak.
The unit of measurement of the concentration is kg/m
3
(the weight in
kg of the refrigerant gas in 1 m
3
volume of the occupied space).
Compliance to the local applicable regulations and standards for the
maximum allowable concentration level is required.
According to the appropriate European Standard, the maximum
allowed concentration level of refrigerant to a humanly space for
R410A is limited to 0.44 kg/m
3
.
1
Direction of the refrigerant flow
2
Room where refrigerant leak has occurred (outflow of all
the refrigerant from the system)
Pay special attention to places, such as basements etc., where
refrigerant can stay, since refrigerant is heavier than air.
18.3. Procedure for checking maximum concentration
Check the maximum concentration level in accordance with steps 1
to 4 below and take whatever action is necessary to comply.
1
Calculate the amount of refrigerant (kg) charged to each system
separately.
2
Calculate the volume of the room (m
3
) where the indoor unit is
installed.
In a case such as the following, calculate the volume of (A), (B)
as a single room or as the smallest room.
A
Where there are no smaller room divisions:
B
Where there is a room division, but there is an opening
between the rooms sufficiently large to permit a free flow of
air back and forth.
1
Opening between the rooms
2
Partition
(Where there is an opening without a door or where there
are openings above and below the door which are each
equivalent in size to 0.15% or more of the floor area.)
3
Calculating the refrigerant density using the results of the
calculations in steps 1 and 2 above.
If the result of the above calculation exceeds the maximum
concentration level, a ventilation opening to the adjacent room
shall be made.
4
Calculate the refrigerant density taking the volume of the room
where the indoor unit is installed and the adjacent room.
Install ventilation openings in the door of adjacent rooms until
the refrigerant density is smaller than the maximum
concentration level.
19. Disposal requirements
Dismantling of the unit, treatment of the refrigerant, of oil and of other
parts must be done in accordance with relevant local and national
legislation.
Amount of
refrigerant in a
single unit system
(amount of
refrigerant with
which the system
is charged before
leaving the factory)
+
Additional charging
amount (amount of
refrigerant added
locally in
accordance with
the length or
diameter of the
refrigerant piping)
=
Total
amount of
refrigerant
(kg) in the
system
NOTICE
Where a single refrigerant facility is divided into 2 entirely
independent refrigerant systems, use the amount of
refrigerant with which each separate system is charged.
2
1
Total volume of refrigerant in
the refrigerant system
≤
Maximum concentration
level (kg/m
3
)
Size (m
3
) of smallest room in
which there is an indoor unit
installed
1
2
Summary of Contents for RYYQ8T7Y1B
Page 68: ......
Page 69: ......
Page 70: ......
Page 72: ...4P329765 1 2012 09 Copyright 2012 Daikin 4P329765 1 0000000U...