FUNCTION CONTROL
34
2.3 Heating Mode
Heating mode operation is as follows.
T
amb
≤
T
set
-1
C: Heating mode will be entered. The compressor and outdoor unit fan will
run and indoor unit fan will run at setting speed and the mode of cold-blast air prevention.
T
amb
≥
T
set
+1
C: The compressor and outdoor unit fan will stop but the 4-way valve will be
still energized. Indoor unit fan will run at the mode of blowing surplus heat.
T
set
-1
C<T
amb
<T
set
+1
C: Previous running status will be kept.
(running at
blowing
surplus heat)
(running when
meeting
condition)
Manual