background image

4 Preparation

Installation and operation manual

7

RXYSQ6T8Y1B9
VRV IV-S system air conditioner
4P482276-1 – 2017.04

4.2.3

To select the piping size

Determine the proper size referring to following tables and reference
figure (only for indication).

A

B-1

B-2

C-1

C-2

C-3

C-4

1

3-1

3-2

3-3

3-4

VRV DX

2

2

2

1

Outdoor unit

2

Refrigerant branch kits

3-1~3-4

VRV DX indoor units

A

Piping between outdoor unit and (first) refrigerant branch
kit

B-1 B-2

Piping between refrigerant branch kits

C-1~C-4

Piping between refrigerant branch kit and indoor unit

In  case  the  required  pipe  sizes  (inch  sizes)  are  not  available,  it  is
also allowed to use other diameters (mm sizes), taken the following
into account:
▪ Select the pipe size nearest to the required size.
▪ Use  the  suitable  adapters  for  the  change-over  from  inch  to  mm

pipes (field supply).

▪ The  additional  refrigerant  calculation  has  to  be  adjusted  as

mentioned  in 

"5.6.2  To  determine  the  additional  refrigerant

amount" on page 12

.

A: Piping between outdoor unit and (first)
refrigerant branch kit

When the equivalent pipe length between outdoor and indoor units is
90 m or more, the size of the main gas pipe must be increased (size-
up).  If  the  recommended  gas  pipe  (size-up)  is  not  available,  you
must  use  the  standard  size  (which  might  result  in  a  small  capacity
decrease).

a

e

b

c

d

a

Outdoor unit

b

Main gas pipe

c

Increase

d

First refrigerant branch kit

e

Indoor unit

Outdoor unit

capacity type (HP)

Piping outer diameter size (mm)

Gas pipe

Liquid pipe

Standard

Size-up

6

19.1

22.2

9.5

B: Piping between refrigerant branch kits

Choose  from  the  following  table  in  accordance  with  the  indoor  unit
total  capacity  type,  connected  downstream.  Do  not  let  the
connection  piping  exceed  the  refrigerant  piping  size  chosen  by  the
general system model name.

Indoor unit capacity

index

Piping outer diameter size (mm)

Gas pipe

Liquid pipe

<150

15.9

9.5

150≤x≤176

19.1

Example: 

Downstream capacity for B-1 = capacity index of unit 3-1

+ capacity index of unit 3-2

C: Piping between refrigerant branch kit and
indoor unit

Use  the  same  diameters  as  the  connections  (liquid,  gas)  on  the
indoor units. The diameters of the indoor units are as follows:

Indoor unit capacity

index

Piping outer diameter size (mm)

Gas pipe

Liquid pipe

15~50

12.7

6.4

63~140

15.9

9.5

4.2.4

To select refrigerant branch kits

For  piping  example,  refer  to 

"4.2.3  To  select  the  piping  size"  on

page 7

.

Refnet joint at first branch (counting from outdoor unit)

When using refnet joints at the first branch counted from the outdoor
unit  side,  choose  from  the  following  table  in  accordance  with  the
capacity of the outdoor unit. 

Example: 

Refnet joint A→B‑1.

Outdoor unit capacity type (HP)

Refrigerant branch kit

6

KHRQ22M20T

Refnet joints at other branches

For refnet joints other than the first branch, select the proper branch
kit  model  based  on  the  total  capacity  index  of  all  indoor  units
connected  after  the  refrigerant  branch. 

Example: 

Refnet  joint

B‑1→C‑1.

Indoor unit capacity index

Refrigerant branch kit

<176

KHRQ22M20T

Refnet headers

Concerning  refnet  headers,  choose  from  the  following  table  in
accordance  with  the  total  capacity  of  all  the  indoor  units  connected
below the refnet header.

Indoor unit capacity index

Refrigerant branch kit

<176

KHRQ22M29H

INFORMATION

Maximum 8 branches can be connected to a header.

4.3

Preparing electrical wiring

4.3.1

Safety device requirements

The  power  supply  must  be  protected  with  the  required  safety
devices, i.e. a main switch, a slow blow fuse on each phase and an
earth leakage protector in accordance with the applicable legislation.

Selection and sizing of the wiring should be done in accordance with
the applicable legislation based on the information mentioned in the
table below.

Model

Minimum circuit

ampacity

Recommended

fuses

Power supply

RXYSQ6_Y1

14.1 A

16 A

3N~ 50 Hz

380-415 V

Transmission wiring

Transmission wiring

Vinyl cords with 0.75 to 1.25 mm²

sheath or cables (2‑core wires)

Maximum wiring length
(= distance between outdoor and
furthest indoor unit)

300 m

Total wiring length
(= distance between outdoor and
all indoors)

600 m

If the total transmission wiring exceeds these limits, it may
result in communication error.

Summary of Contents for RXYSQ6T8Y1B9

Page 1: ...Installation and operation manual VRV IV S system air conditioner English Installation and operation manual VRV IV S system air conditioner RXYSQ6T8Y1B9...

Page 2: ...1700 1000 500 HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB HD HB H...

Page 3: ...ogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nuro...

Page 4: ...ng the electrical wiring 14 5 7 4 To connect the electrical wiring on the outdoor unit 14 5 8 Finishing the outdoor unit installation 15 5 8 1 To finish the transmission wiring 15 6 Configuration 16 6...

Page 5: ...nce Authorised installers end users INFORMATION This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial use by lay persons Documentat...

Page 6: ...dity conditions make sure to take precautions to keep the drain holes of the unit free by using proper equipment In heating T AO C WB a b 20 15 5 15 10 5 0 5 10 15 20 10 15 20 2527 30 TAI C DB a Warmi...

Page 7: ...Piping between refrigerant branch kit and indoor unit Use the same diameters as the connections liquid gas on the indoor units The diameters of the indoor units are as follows Indoor unit capacity ind...

Page 8: ...To install the outdoor unit 4 M12 5 2 3 To provide drainage Make sure that condensation water can be evacuated properly Install the unit on a base to make sure that there is a proper drainage in orde...

Page 9: ...alve is now closed Closing direction To handle the stop valve cover The stop valve cover is sealed where indicated by the arrow Do NOT damage it After handling the stop valve tighten the stop valve co...

Page 10: ...open the stop valves after installing the refrigerant piping and performing vacuum drying Running the system with the stop valves closed may break the compressor 5 4 Checking the refrigerant piping 5...

Page 11: ...fer to the indoor unit installation manual for more details Leak test and vacuum drying should be done before the power supply is set to the unit If not see also the flow chart earlier described in th...

Page 12: ...e finished properly NOTICE Be sure to turn on the power 6 hours before operation in order to have power running to the crankcase heater and to protect the compressor NOTICE If operation is performed w...

Page 13: ...y operating the outdoor unit by means of the manual additional refrigerant charge mode 5 Connect as shown Make sure valve A is closed p p R410A a c d b A d a Weighing scales b Refrigerant R410A tank s...

Page 14: ...unit near the gas and liquid stop valves 5 7 Connecting the electrical wiring 5 7 1 Field wiring Overview Field wiring consists of power supply always including earth and indoor outdoor communication...

Page 15: ...3 1 a Power supply cable b Transmission wiring cable Connecting to the frame When cables are routed from the unit a protection sleeve for the conduits PG insertions can be inserted at the knockout hol...

Page 16: ...or special operation e g 1 time operation recovery vacuuming setting manual adding refrigerant setting etc In such a case it is required to abort the special operation before normal operation can rest...

Page 17: ...iring Switching between modes Use BS1 to switch between the default situation mode 1 and mode 2 B S 1 5 s B S 1 B S 1 B S 1 a c b a Default situation H1P OFF b Mode 1 H1P flashing c Mode 2 H1P ON BS1...

Page 18: ...an optional accessory is required Value Description H7P Shows the status of power consumption limitation operation OFF Unit is currently not operating under power consumption limitations ON Unit is c...

Page 19: ...gerant charge amount in a manual way without automatic refrigerant charging functionality following setting should be applied default Deactivated Activated To stop the manual additional refrigerant ch...

Page 20: ...al signal is sent to the unit this setting defines the level power consumption limitation that will be applied for step 1 The level is according to the table 60 default 70 80 2 31 Power consumption li...

Page 21: ...t correspond to the voltage on the identification label of the unit Earth wiring Be sure that the earth wires have been connected properly and that the earth terminals are tightened Insulation test of...

Page 22: ...Under centralised control will display on the user interface of indoor units Steps during the automatic system test run procedure Step Description Control before start up pressure equalisation Coolin...

Page 23: ...Suction temperature sensor malfunction R3T A1P X12A R5T A1P X12A Check connection on PCB or actuator Liquid temperature sensor coil malfunction R4T A1P X12A Check connection on PCB or actuator Liquid...

Page 24: ...allowed Multiple rows of units See figure 2 on the inside of the front cover Stacked units max 2 levels See figure 3 on the inside of the front cover A1 A2 A1 If there is danger of drainage dripping...

Page 25: ...2P Printed circuit board inverter BS Push buttons mode set return test reset A1P C Capacitor A2P DS1 DIP switch A1P F1U F2U Fuse T 31 5 A 500 V A1P F1U Fuse T 5 0 A 250 V A2P F3U F4U F5U Fuse T 6 3 A...

Page 26: ...ay be put in action and the air conditioner may not operate Above operation range is only valid in case direct expansion indoor units are connected to the VRV IV S system 12 2 Operating the system 12...

Page 27: ...emperature decrease minimal room cooling The micro computer automatically determines temperature and fan speed cannot be set by the user interface The system does not go into operation if the room tem...

Page 28: ...essary to designate one of the user interfaces as the master user interface The displays of slave user interfaces show change over under centralised control and slave user interfaces automatically fol...

Page 29: ...s gas cookers etc is present Always have qualified service personnel confirm that the point of leakage has been repaired or corrected before resuming operation 14 Troubleshooting If one of the followi...

Page 30: ...over current detected Main code Contents Compressor lock startup Transmission outdoor unit inverter INV transmission trouble INV unbalanced power supply voltage Fin thermistor malfunction Capacity se...

Page 31: ...ystem stops after heating operation Expansion and contraction of plastic parts caused by temperature change make this noise A low sah choro choro sound is heard while the indoor unit is stopped When a...

Page 32: ...4P482276 1 2017 04 Copyright 2017 Daikin 4P482276 1 0000000R...

Reviews: