14 Troubleshooting

Installation and operation manual

29

RXYSQ6T8Y1B9
VRV IV-S system air conditioner
4P482276-1 – 2017.04

13.1

About the refrigerant

This  product  contains  fluorinated  greenhouse  gases.  Do  NOT  vent
gases into the atmosphere.

Refrigerant type: R410A

Global warming potential (GWP) value: 2087.5

NOTICE

In  Europe,  the 

greenhouse  gas  emissions

  of  the  total

refrigerant  charge  in  the  system  (expressed  as  tonnes
CO

2

-equivalent)  is  used  to  determine  the  maintenance

intervals. Follow the applicable legislation.

Formula  to  calculate  the  greenhouse  gas  emissions:

GWP value of the refrigerant × Total refrigerant charge [in
kg] / 1000

Please contact your installer for more information.

WARNING

The refrigerant in the system is safe and normally does not
leak. If the refrigerant leaks in the room, contact with a fire
of  a  burner,  a  heater  or  a  cooker  may  result  in  a  harmful
gas.

Turn  off  any  combustible  heating  devices,  ventilate  the
room and contact the dealer where you purchased the unit.

Do not use the system until a service person confirms that
the portion where the refrigerant leaks is repaired.

13.2

After-sales service and warranty

13.2.1

Warranty period

▪ This  product  includes  a  warranty  card  that  was  filled  in  by  the

dealer  at  the  time  of  installation.  The  completed  card  has  to  be
checked by the customer and stored carefully.

▪ If repairs to the product are necessary within the warranty period,

contact your dealer and keep the warranty card at hand.

13.2.2

Recommended maintenance and
inspection

Since  dust  collects  when  using  the  unit  for  several  years,
performance  of  the  unit  will  deteriorate  to  some  extent.  As  taking
apart and cleaning interiors of units requires technical expertise and
in  order  to  ensure  the  best  possible  maintenance  of  your  units,  we
recommend to enter into a maintenance and inspection contract on
top  of  normal  maintenance  activities.  Our  network  of  dealers  has
access  to  a  permanent  stock  of  essential  components  in  order  to
keep your unit in operation as long as possible. Contact your dealer
for more information.

When asking your dealer for an intervention, always state:

▪ The complete model name of the unit.

▪ The manufacturing number (stated on the nameplate of the unit).

▪ The installation date.

▪ The symptoms or malfunction, and details of the defect.

WARNING

▪ Do not modify, disassemble, remove, reinstall or repair

the unit yourself as incorrect dismantling or installation
may  cause  an  electric  shock  or  fire.  Contact  your
dealer.

▪ In case of accidental refrigerant leaks, make sure there

are  no  naked  flames.  The  refrigerant  itself  is  entirely
safe,  non-toxic  and  non-combustible,  but  it  will
generate  toxic  gas  when  it  accidentally  leaks  into  a
room  where  combustible  air  from  fan  heaters,  gas
cookers,  etc.  is  present.  Always  have  qualified  service
personnel  confirm  that  the  point  of  leakage  has  been
repaired or corrected before resuming operation.

14

Troubleshooting

If one of the following malfunctions occur, take the measures shown
below and contact your dealer.

WARNING
Stop  operation  and  shut  off  the  power  if  anything
unusual occurs (burning smells etc.).

Leaving  the  unit  running  under  such  circumstances  may
cause breakage, electric shock or fire. Contact your dealer.

The system must be repaired by a qualified service person:

Malfunction

Measure

If a safety device such as a fuse, a breaker
or an earth leakage breaker frequently
actuates or the ON/OFF switch does not
properly work.

Turn off the main
power switch.

If water leaks from the unit.

Stop the operation.

The operation switch does not work well.

Turn off the power.

If the user interface display indicates the
unit number, the operation lamp flashes
and the malfunction code appears.

Notify your installer
and report the
malfunction code.

If  the  system  does  not  properly  operate  except  for  the  above
mentioned cases and none of the above mentioned malfunctions is
evident,  investigate  the  system  according  to  the  following
procedures.

Malfunction

Measure

If the system does
not operate at all.

▪ Check if there is no power failure. Wait until

power  is  restored.  If  power  failure  occurs
during  operation,  the  system  automatically
restarts immediately after power is restored.

▪ Check  if  no  fuse  has  blown  or  breaker  is

activated.  Change  the  fuse  or  reset  the
breaker if necessary.

If the system goes
into fan only
operation, but as
soon as it goes into
heating or cooling
operation, the
system stops.

▪ Check  if  air  inlet  or  outlet  of  outdoor  or

indoor  unit  is  not  blocked  by  obstacles.
Remove  any  obstacles  and  make  sure  the
air can flow freely.

▪ Check  if  the  user  interface  display  shows

  (time  to  clean  the  air  filter).  (Refer  to

"13  Maintenance  and  service"  on  page  28

and  "Maintenance"  in  the  indoor  unit
manual.)

The system
operates but
cooling or heating is
insufficient.

▪ Check  if  air  inlet  or  outlet  of  outdoor  or

indoor  unit  is  not  blocked  by  obstacles.
Remove  any  obstacles  and  make  sure  the
air can flow freely.

▪ Check if the air filter is not clogged (refer to

"Maintenance" in the indoor unit manual).

▪ Check the temperature setting.

▪ Check  the  fan  speed  setting  on  your  user

interface.

▪ Check  for  open  doors  or  windows.  Close

doors  and  windows  to  prevent  wind  from
coming in.

▪ Check  if  there  are  too  many  occupants  in

the  room  during  cooling  operation.  Check  if
the heat source of the room is excessive.

▪ Check if direct sunlight enters the room. Use

curtains or blinds.

▪ Check if the air flow angle is proper.

If  after  checking  all  above  items,  it  is  impossible  to  fix  the  problem
yourself, contact your installer and state the symptoms, the complete
model name of the unit (with manufacturing number if possible) and
the installation date (possibly listed on the warranty card).

Summary of Contents for RXYSQ6T8Y1B9

Page 1: ...Installation and operation manual VRV IV S system air conditioner English Installation and operation manual VRV IV S system air conditioner RXYSQ6T8Y1B9...

Page 2: ...1700 1000 500 HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB HD HB H...

Page 3: ...ogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nuro...

Page 4: ...ng the electrical wiring 14 5 7 4 To connect the electrical wiring on the outdoor unit 14 5 8 Finishing the outdoor unit installation 15 5 8 1 To finish the transmission wiring 15 6 Configuration 16 6...

Page 5: ...nce Authorised installers end users INFORMATION This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial use by lay persons Documentat...

Page 6: ...dity conditions make sure to take precautions to keep the drain holes of the unit free by using proper equipment In heating T AO C WB a b 20 15 5 15 10 5 0 5 10 15 20 10 15 20 2527 30 TAI C DB a Warmi...

Page 7: ...Piping between refrigerant branch kit and indoor unit Use the same diameters as the connections liquid gas on the indoor units The diameters of the indoor units are as follows Indoor unit capacity ind...

Page 8: ...To install the outdoor unit 4 M12 5 2 3 To provide drainage Make sure that condensation water can be evacuated properly Install the unit on a base to make sure that there is a proper drainage in orde...

Page 9: ...alve is now closed Closing direction To handle the stop valve cover The stop valve cover is sealed where indicated by the arrow Do NOT damage it After handling the stop valve tighten the stop valve co...

Page 10: ...open the stop valves after installing the refrigerant piping and performing vacuum drying Running the system with the stop valves closed may break the compressor 5 4 Checking the refrigerant piping 5...

Page 11: ...fer to the indoor unit installation manual for more details Leak test and vacuum drying should be done before the power supply is set to the unit If not see also the flow chart earlier described in th...

Page 12: ...e finished properly NOTICE Be sure to turn on the power 6 hours before operation in order to have power running to the crankcase heater and to protect the compressor NOTICE If operation is performed w...

Page 13: ...y operating the outdoor unit by means of the manual additional refrigerant charge mode 5 Connect as shown Make sure valve A is closed p p R410A a c d b A d a Weighing scales b Refrigerant R410A tank s...

Page 14: ...unit near the gas and liquid stop valves 5 7 Connecting the electrical wiring 5 7 1 Field wiring Overview Field wiring consists of power supply always including earth and indoor outdoor communication...

Page 15: ...3 1 a Power supply cable b Transmission wiring cable Connecting to the frame When cables are routed from the unit a protection sleeve for the conduits PG insertions can be inserted at the knockout hol...

Page 16: ...or special operation e g 1 time operation recovery vacuuming setting manual adding refrigerant setting etc In such a case it is required to abort the special operation before normal operation can rest...

Page 17: ...iring Switching between modes Use BS1 to switch between the default situation mode 1 and mode 2 B S 1 5 s B S 1 B S 1 B S 1 a c b a Default situation H1P OFF b Mode 1 H1P flashing c Mode 2 H1P ON BS1...

Page 18: ...an optional accessory is required Value Description H7P Shows the status of power consumption limitation operation OFF Unit is currently not operating under power consumption limitations ON Unit is c...

Page 19: ...gerant charge amount in a manual way without automatic refrigerant charging functionality following setting should be applied default Deactivated Activated To stop the manual additional refrigerant ch...

Page 20: ...al signal is sent to the unit this setting defines the level power consumption limitation that will be applied for step 1 The level is according to the table 60 default 70 80 2 31 Power consumption li...

Page 21: ...t correspond to the voltage on the identification label of the unit Earth wiring Be sure that the earth wires have been connected properly and that the earth terminals are tightened Insulation test of...

Page 22: ...Under centralised control will display on the user interface of indoor units Steps during the automatic system test run procedure Step Description Control before start up pressure equalisation Coolin...

Page 23: ...Suction temperature sensor malfunction R3T A1P X12A R5T A1P X12A Check connection on PCB or actuator Liquid temperature sensor coil malfunction R4T A1P X12A Check connection on PCB or actuator Liquid...

Page 24: ...allowed Multiple rows of units See figure 2 on the inside of the front cover Stacked units max 2 levels See figure 3 on the inside of the front cover A1 A2 A1 If there is danger of drainage dripping...

Page 25: ...2P Printed circuit board inverter BS Push buttons mode set return test reset A1P C Capacitor A2P DS1 DIP switch A1P F1U F2U Fuse T 31 5 A 500 V A1P F1U Fuse T 5 0 A 250 V A2P F3U F4U F5U Fuse T 6 3 A...

Page 26: ...ay be put in action and the air conditioner may not operate Above operation range is only valid in case direct expansion indoor units are connected to the VRV IV S system 12 2 Operating the system 12...

Page 27: ...emperature decrease minimal room cooling The micro computer automatically determines temperature and fan speed cannot be set by the user interface The system does not go into operation if the room tem...

Page 28: ...essary to designate one of the user interfaces as the master user interface The displays of slave user interfaces show change over under centralised control and slave user interfaces automatically fol...

Page 29: ...s gas cookers etc is present Always have qualified service personnel confirm that the point of leakage has been repaired or corrected before resuming operation 14 Troubleshooting If one of the followi...

Page 30: ...over current detected Main code Contents Compressor lock startup Transmission outdoor unit inverter INV transmission trouble INV unbalanced power supply voltage Fin thermistor malfunction Capacity se...

Page 31: ...ystem stops after heating operation Expansion and contraction of plastic parts caused by temperature change make this noise A low sah choro choro sound is heard while the indoor unit is stopped When a...