background image

6 Configuration

Installation and operation manual

18

RXYSQ6T8Y1B9

VRV IV-S system air conditioner

4P482276-1 – 2017.04

6.1.6

To use mode 2

In mode 2 you can make field settings to configure the system.

Example: 7‑LEDs display – Mode 2

You  can  change  the  value  of  setting  [2‑8]  (=  T

e

  target  temperature

during cooling operation) to 4 (= 8°C) as follows:

#

Action

Button/display

1

Start from the default
situation.

2

Select mode 2.

BS1 [5 s]

3

Select setting 8.

("X×" depends on the setting
that you want to select.)

BS2 [X×]

(= binary 8)

4

Select value 4 (= 8°C).

a

: Display the current value.

b

: Change to 4. ("X×"

depends on the current
value, and the value that you
want to select.)

c

: Enter the value in the

system.

d

: Confirm. The system starts

operating according to the
setting.

BS2 [X×]

b

a

BS3 [1×]

c

BS3 [1×]

d

BS3 [1×]

5

Quit mode 2.

BS1 [1×]

6.1.7

Mode 1 (and default situation): Monitoring
settings

In  mode  1  (and  in  default  situation)  you  can  read  out  some
information.

7‑LEDs display – Default situation (H1P OFF)

You can read out the following information:

Value / Description

H6P

Shows the status of low noise operation.

OFF

Unit is currently not operating under low noise
restrictions.

ON

Unit is currently operating under low noise
restrictions.

Low noise operation reduces the sound generated by the
unit compared to nominal operating conditions.

Low noise operation can be set in mode 2. There are two
methods to activate low noise operation of the outdoor unit
system.

▪ The  first  method  is  to  enable  an  automatic  low  noise

operation  during  night  time  by  field  setting.  The  unit  will
operate  at  the  selected  low  noise  level  during  the
selected time frames.

▪ The  second  method  is  to  enable  low  noise  operation

based on an external input. For this operation an optional
accessory is required.

Value / Description

H7P

Shows the status of power consumption limitation operation.

OFF

Unit is currently not operating under power
consumption limitations.

ON

Unit is currently operating under power consumption
limitation.

Power consumption limitation reduces the power
consumption of the unit compared to nominal operating
conditions.

Power consumption limitation can be set in mode 2. There
are two methods to activate power consumption limitation of
the outdoor unit system.

▪ The first method is to enable a forced power consumption

limitation  by  field  setting.  The  unit  will  always  operate  at
the selected power consumption limitation.

▪ The  second  method  is  to  enable  power  consumption

limitation  based  on  an  external  input.  For  this  operation
an optional accessory is required.

7‑LEDs display – Mode 1 (H1P flashing)

You can read out the following information:

Setting

(

)

Value / Description

[1‑5] 

Shows the total number of
connected indoor units.

It can be convenient to check if
the total number of indoor units
which are installed match the
total number of indoor units
which are recognised by the
system. In case there is a
mismatch, it is advised to check
the communication wiring path
between outdoor and indoor units
(F1/F2 communication line).

[1‑14] 

Shows the latest malfunction
code.

When the latest malfunction
codes were reset by accident on
an indoor unit user interface, they
can be checked again through
this monitoring settings.

For the content or reason behind
the malfunction code see

"8.1 Solving problems based on
error codes" on page 22

, where

most relevant malfunction codes
are explained. Detailed
information about malfunction
codes can be consulted in the
service manual of this unit.

To obtain more detailed
information about the malfunction
code, press BS2 up to 3 times.

[1‑15] 

Shows the 2nd last malfunction
code.

[1‑16] 

Shows the 3rd last malfunction
code.

Summary of Contents for RXYSQ6T8Y1B9

Page 1: ...Installation and operation manual VRV IV S system air conditioner English Installation and operation manual VRV IV S system air conditioner RXYSQ6T8Y1B9...

Page 2: ...1700 1000 500 HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB HD HB H...

Page 3: ...ogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nuro...

Page 4: ...ng the electrical wiring 14 5 7 4 To connect the electrical wiring on the outdoor unit 14 5 8 Finishing the outdoor unit installation 15 5 8 1 To finish the transmission wiring 15 6 Configuration 16 6...

Page 5: ...nce Authorised installers end users INFORMATION This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial use by lay persons Documentat...

Page 6: ...dity conditions make sure to take precautions to keep the drain holes of the unit free by using proper equipment In heating T AO C WB a b 20 15 5 15 10 5 0 5 10 15 20 10 15 20 2527 30 TAI C DB a Warmi...

Page 7: ...Piping between refrigerant branch kit and indoor unit Use the same diameters as the connections liquid gas on the indoor units The diameters of the indoor units are as follows Indoor unit capacity ind...

Page 8: ...To install the outdoor unit 4 M12 5 2 3 To provide drainage Make sure that condensation water can be evacuated properly Install the unit on a base to make sure that there is a proper drainage in orde...

Page 9: ...alve is now closed Closing direction To handle the stop valve cover The stop valve cover is sealed where indicated by the arrow Do NOT damage it After handling the stop valve tighten the stop valve co...

Page 10: ...open the stop valves after installing the refrigerant piping and performing vacuum drying Running the system with the stop valves closed may break the compressor 5 4 Checking the refrigerant piping 5...

Page 11: ...fer to the indoor unit installation manual for more details Leak test and vacuum drying should be done before the power supply is set to the unit If not see also the flow chart earlier described in th...

Page 12: ...e finished properly NOTICE Be sure to turn on the power 6 hours before operation in order to have power running to the crankcase heater and to protect the compressor NOTICE If operation is performed w...

Page 13: ...y operating the outdoor unit by means of the manual additional refrigerant charge mode 5 Connect as shown Make sure valve A is closed p p R410A a c d b A d a Weighing scales b Refrigerant R410A tank s...

Page 14: ...unit near the gas and liquid stop valves 5 7 Connecting the electrical wiring 5 7 1 Field wiring Overview Field wiring consists of power supply always including earth and indoor outdoor communication...

Page 15: ...3 1 a Power supply cable b Transmission wiring cable Connecting to the frame When cables are routed from the unit a protection sleeve for the conduits PG insertions can be inserted at the knockout hol...

Page 16: ...or special operation e g 1 time operation recovery vacuuming setting manual adding refrigerant setting etc In such a case it is required to abort the special operation before normal operation can rest...

Page 17: ...iring Switching between modes Use BS1 to switch between the default situation mode 1 and mode 2 B S 1 5 s B S 1 B S 1 B S 1 a c b a Default situation H1P OFF b Mode 1 H1P flashing c Mode 2 H1P ON BS1...

Page 18: ...an optional accessory is required Value Description H7P Shows the status of power consumption limitation operation OFF Unit is currently not operating under power consumption limitations ON Unit is c...

Page 19: ...gerant charge amount in a manual way without automatic refrigerant charging functionality following setting should be applied default Deactivated Activated To stop the manual additional refrigerant ch...

Page 20: ...al signal is sent to the unit this setting defines the level power consumption limitation that will be applied for step 1 The level is according to the table 60 default 70 80 2 31 Power consumption li...

Page 21: ...t correspond to the voltage on the identification label of the unit Earth wiring Be sure that the earth wires have been connected properly and that the earth terminals are tightened Insulation test of...

Page 22: ...Under centralised control will display on the user interface of indoor units Steps during the automatic system test run procedure Step Description Control before start up pressure equalisation Coolin...

Page 23: ...Suction temperature sensor malfunction R3T A1P X12A R5T A1P X12A Check connection on PCB or actuator Liquid temperature sensor coil malfunction R4T A1P X12A Check connection on PCB or actuator Liquid...

Page 24: ...allowed Multiple rows of units See figure 2 on the inside of the front cover Stacked units max 2 levels See figure 3 on the inside of the front cover A1 A2 A1 If there is danger of drainage dripping...

Page 25: ...2P Printed circuit board inverter BS Push buttons mode set return test reset A1P C Capacitor A2P DS1 DIP switch A1P F1U F2U Fuse T 31 5 A 500 V A1P F1U Fuse T 5 0 A 250 V A2P F3U F4U F5U Fuse T 6 3 A...

Page 26: ...ay be put in action and the air conditioner may not operate Above operation range is only valid in case direct expansion indoor units are connected to the VRV IV S system 12 2 Operating the system 12...

Page 27: ...emperature decrease minimal room cooling The micro computer automatically determines temperature and fan speed cannot be set by the user interface The system does not go into operation if the room tem...

Page 28: ...essary to designate one of the user interfaces as the master user interface The displays of slave user interfaces show change over under centralised control and slave user interfaces automatically fol...

Page 29: ...s gas cookers etc is present Always have qualified service personnel confirm that the point of leakage has been repaired or corrected before resuming operation 14 Troubleshooting If one of the followi...

Page 30: ...over current detected Main code Contents Compressor lock startup Transmission outdoor unit inverter INV transmission trouble INV unbalanced power supply voltage Fin thermistor malfunction Capacity se...

Page 31: ...ystem stops after heating operation Expansion and contraction of plastic parts caused by temperature change make this noise A low sah choro choro sound is heard while the indoor unit is stopped When a...

Page 32: ...4P482276 1 2017 04 Copyright 2017 Daikin 4P482276 1 0000000R...

Reviews: