11

10.8.

Leak test and vacuum drying

The units were checked for leaks by the manufacturer.

See  figure 6 or figure 7 and refer to "10.9. Additional refrigerant
charge" on page 11 for nomenclature of the parts in figure 6 or
figure 7.

Confirm that the gas and liquid line stop valves are firmly closed
before pressure test or vacuuming.

Make sure that valve A is completely open.

Air tight test and vacuum drying

Air tight test: Make sure to use nitrogen gas. (For the service
port position, refer to "10.2. Cautions for handling stop valve" on
page 9.

Pressurize the liquid and gas pipes to 4.0 MPa (40 bar) (do not
pressurize more than 4.0 MPa (40 bar)). If the pressure does not
drop within 24 hours, the system passes the test. If the pressure
drops, check where the nitrogen leaks from.

Vacuum drying: Use a vacuum pump which can evacuate to –
100.7 kPa (5 Torr, –755 mm Hg)

1.

Evacuate the system from the liquid and gas pipes by using a
vacuum pump for more than 2 hours and bring the system to –
100.7 kPa. After keeping the system under that condition for
more than 1 hour, check if the vacuum gauge rises or not. If it
rises, the system may either contain moisture inside or have
leaks.

2.

Following should be executed if there is a possibility of moisture
remaining inside the pipe (if piping work is carried out during the
raining season or over a long period of time, rainwater may enter
the pipe during work).
After evacuating the system for 2 hours, pressurize the system
to 0.05 MPa (vacuum break) with nitrogen gas and evacuate the
system again using the vacuum pump for 1 hour to –100.7 kPa
(vacuum drying). If the system cannot be evacuated to
–100.7 kPa within 2 hours, repeat the operation of vacuum
break and vacuum drying.
Then, after leaving the system in vacuum for 1 hour, confirm that
the vacuum gauge does not rise.

10.9.

Additional refrigerant charge

See figure 7.

1

Pressure reducing valve

2

Nitrogen

3

Tank

4

Siphon system

5

Measuring instrument

6

Vacuum pump

7

Valve A

8

Gas line stop valve

9

Outdoor unit

10

Liquid line stop valve

11

Indoor unit

12

Stop valve service port

13

Charge hose

To avoid compressor breakdown. Do not charge the refrigerant
more than the specified amount.

This outdoor unit is factory charged with refrigerant and
depending on pipe sizes and pipe lengths some systems require
additional charging of refrigerant. See "10.7. Example of
connection for VRV indoor units" on page 10 for VRV indoor
units.

In case re-charge is required, refer to the nameplate of the unit.
The nameplate states the type of refrigerant and necessary
amount.

Precautions when adding R410A

Be sure to charge the specified amount of refrigerant in liquid state to
the liquid pipe.

Since this refrigerant is a mixed refrigerant, adding it in gas form may
cause the refrigerant composition to change, preventing normal
operation.

Before charging, check whether the refrigerant cylinder is
equipped with a siphon tube or not.

10.10. Important information regarding the refrigerant 

used

This product contains fluorinated greenhouse gases covered by the
Kyoto Protocol. Do not vent gases into the atmosphere.

Refrigerant type:R410A
GWP

(1)

 value:1975

(1)

 GWP = global warming potential

Please fill in with indelible ink,



 the factory refrigerant charge of the product,



 the additional refrigerant amount charged in the field and



+



 

the total refrigerant charge

on the fluorinated greenhouse gases label supplied with the product.

WARNING

Refrigerant cannot be charged until field wiring has
been completed.

Refrigerant may only be charged after performing the
leak test and the vacuum drying (see above).

When charging a system, care shall be taken that its
maximum permissible charge is never exceeded, in
view of the danger of liquid hammer.

Charging with an unsuitable substance may cause
explosions and accidents, so always ensure that the
appropriate refrigerant (R410A) is charged.

Refrigerant containers shall be opened slowly

Always use protective gloves and protect your eyes
when charging refrigerant.

When performing service on the unit requiring the
refrigerant system to be opened, refrigerant must be
evacuated according to local regulations.

Do not use the automatic refrigerant charging function
while working on the indoor units.
When using the automatic refrigerant charging
function, the indoor units operate automatically as well
as the outdoor unit.

When the electric is on, please close the front panel when
leaving the unit.

Charge the liquid 

refrigerant with the 

cylinder in upright 

position.

Charge the liquid 

refrigerant with the 

cylinder in up-side-down 

position.

4P357505-1.book  Page 11  Tuesday, September 10, 2013  7:59 AM

Summary of Contents for RXYSQ6P8Y1B9

Page 1: ...INSTALLATION MANUAL Installation manual VRVIII S System air conditioner English RXYSQ6P8Y1B9 System air conditioner...

Page 2: ...0 L1 2 H 1 2 H L1 0 L2 2 H 1 2 H L2 L2 H L2 H L2 H L2 H L2 H L2 H 150 500 500 500 500 750 100 100 100 100 200 300 200 100 250 250 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 300 300 300 250 300...

Page 3: ...9 16 V 230 V 16 V 16 V 16 V 2 3 4 1 2 3 4 1 4 5 5 5 380 415 V Y1 1 8 8 9...

Page 4: ...mo estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk...

Page 5: ...operation 19 12 5 Checks in normal operation 20 12 6 Temperature adjustment operation confirmation 20 13 Service mode operation 21 14 Caution for refrigerant leaks 21 14 1 Introduction 21 14 2 Maximu...

Page 6: ...book WARNING Ask your dealer or qualified personnel to carry out installation work Do not install the machine by yourself Improper installation may result in water leakage electric shocks or fire Perf...

Page 7: ...ing may cause water leakage and make the furniture get wet Install the indoor and outdoor units power wire and connecting wire at least 1 meter away from televisions or radios to prevent image interfe...

Page 8: ...tion site This is a class A product In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures 1 Select an installation site w...

Page 9: ...rdance with the foundation drawing in the figure fix the unit securely by means of the foundation bolts Prepare 4 sets of M12 foundation bolts nuts and washers each which are available on the market I...

Page 10: ...s frontward or downward The unit of numeric values is mm When routing the piping backward secure space of 250 mm on the right side of the unit A In case of non stacked installation See figure 4 B In c...

Page 11: ...gerant piping Do not allow anything other than the designated refrigerant to get mixed into the freezing cycle such as air etc If any refrigerant gas leaks while working on the unit ventilate the room...

Page 12: ...trating the center area around the knock out hole using a 6 mm drill See figure 5 Cutting out the two slits makes it possible to install as shown in figure 5 Use a metal saw to cut out the slits After...

Page 13: ...leakage after tightening the cap 10 5 Cautions for handling service port After the work tighten the valve cover in place Tightening torque 11 5 13 9 N m 10 6 Precautions when connecting field piping...

Page 14: ...n size of indoor unit indoor unit refnet joint refnet header Outdoor unit capacity type Refrigerant branch kit name KHRQ22M20T RXYSQ6 Outdoor unit capacity type Refrigerant branch kit name K 54 0 RXYS...

Page 15: ...frigerant more than the specified amount This outdoor unit is factory charged with refrigerant and depending on pipe sizes and pipe lengths some systems require additional charging of refrigerant See...

Page 16: ...s lit up check the type of error based on the error code in the remote controller and correct the error in accordance with 12 4 Test operation on page 19 4 Automatically charge the refrigerant accordi...

Page 17: ...ep 4 2 5 When charging is complete determine the weight of refrigerant that was added and fill in the amount in the Additional refrigerant charge label attached to service precautions plate on the uni...

Page 18: ...ndicates TEST test operation and external control 6 When the specified amount of refrigerant is charged push the BS3 RETURN button Then operation stops The operation automatically stops within 30 minu...

Page 19: ...quipped with an inverter installing a phase advancing capacitor not only will deteriorate power factor improvement effect but also may cause capacitor abnormal heating accident due to high frequency w...

Page 20: ...e it as described under 11 4 Connecting power wire and transmission wires on page 15 Inter unit wiring should be secured as described in 11 4 Connecting power wire and transmission wires on page 15 Se...

Page 21: ...ectrical shock make sure to disconnect the power supply 1 minute or more before servicing the electrical parts Even after 1 minute always measure the voltage at the terminals of main circuit capacitor...

Page 22: ...indicated as follows Setting the push button switch BS1 5 Function of the push button switch which is located on the outdoor unit PCB BS1 MODE For changing the set mode BS2 SET For field setting BS3...

Page 23: ...o Setting mode 1 on page 18 Possible functions A additional refrigerant charging operation B refrigerant recovery operation vacuuming operation C automatic low noise operation setting at nighttime D l...

Page 24: ...ndoor unit will control changeover of the cooling heating operation mode For the details refer to the instruction manual supplied together with the indoor unit 12 6 Temperature adjustment operation co...

Page 25: ...nt of major leak in the system and this in accordance to the local applicable regulations and standards 14 2 Maximum concentration level The maximum charge of refrigerant and the calculation of the ma...

Page 26: ...lest room and so until the result falls short of the maximum concentration 4 Dealing with the situations where the result exceeds the maximum concentration level Where the installation of a facility r...

Page 27: ...3 2 3 5 4 3 2 1 6 8 9 7 2 Y1 3 11 X2M F1 F1 F2 A C B F2 TO IN D UNIT C H SELECTOR X2M TO OUT D UNIT X1M A1P A B C F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 4 5 1 3 2 Y1 13 TO IN D UNIT F1...

Page 28: ...4P357505 1 2013 08 Copyright 2013 Daikin...

Reviews: