![background image](http://html1.mh-extra.com/html/daikin/rxysq6p8y1b9/rxysq6p8y1b9_installation-manual_2459977010.webp)
Installation manual
6
RXYSQ6P8Y1B9
VRVIII-S System air conditioner
4P357505-1 – 2013.08
6.2.
Method for removing transportation stay
The yellow transportation stay installed over the compressor leg for
protecting the unit during transport must be removed. Proceed as
shown in figure 3 and described below.
A
Compressor
B
Fixing nut
C
Transportation stay
1
Slightly loosen each fixing nut (B).
2
Remove the transportation stay (C) as shown in figure 3.
3
Tighten the fixing nut (B) again.
6.3.
Method for installing drain piping
Depending on installation site, it may be required to install drain plug
for drainage (supplied with the unit).
In cold areas, do not use a drain hose with the outdoor unit.
Otherwise, drain water may freeze, impairing the heating
performance.
1
See the figure below for installation of the drain plug.
A
Drain socket
B
Drain cap
C
Drain receiver
D
Insulation tape
E
Drain stop
2
Connect a field supplied vinyl hose (internal diameter of 25 mm)
to the drain socket (A).
If the hose is too long and hangs down, fix it carefully to prevent
kinks.
7.
Installation servicing space
The connection piping outlet direction in the installation shown in
figure 4 is frontward or downward. The unit of numeric values is
mm.
When routing the piping backward, secure space of
≥
250 mm on
the right side of the unit.
(A) In case of non-stacked installation (See figure 4)
(B) In case of stacked installation
1.
In case obstacles exist in front of the outlet side.
2.
In case obstacles exist in front of the air inlet.
C) In case of multiple-row installation (for roof top use, etc.)
1.
In case of installing one unit per row.
CAUTION
If the unit is operated with the transportation stay attached,
abnormal vibration or noise may be generated.
NOTICE
If drain holes of the outdoor unit are covered by a mounting
base or by floor surface, raise the unit in order to provide a
free space of more than 100 mm under the outdoor unit.
E
E
B
A
B
D
C
C
C
B
A
B
D
Suction side obstacle
1
In these cases, close the
bottom of the installation
frame to prevent the
discharged air from
being bypassed
Discharge side obstacle
Left side obstacle
2
In these cases, only
2 units can be installed.
Right side obstacle
3
In these cases, no
restriction of height L1.
Top side obstacle
This situation is not
allowed
Obstacle is present
NOTICE
Do not stack more than one unit.
About 100 mm is required as the dimension for laying
the upper outdoor unit's drain pipe.
Get the portion A sealed so that air from the outlet
does not bypass.
1000
100
A
300
100
A
1000
200
2000
100
4P357505-1.book Page 6 Tuesday, September 10, 2013 7:59 AM