background image

Installation manual

12

RXYSQ6P8Y1B9

VRVIII-S System air conditioner

4P357505-1 – 2013.08

The filled out label must be adhered on the inside of the product and
in the proximity of the product charging port (e.g. on the inside of the
service cover).

1

factory refrigerant charge of the product:
see unit name plate

2

additional refrigerant
amount charged in the field

3

total refrigerant charge

4

Contains fluorinated greenhouse gases covered by the 
Kyoto Protocol

5

outdoor unit

6

refrigerant cylinder and manifold for charging

10.11. 3 procedures for adding refrigerant

Procedure 1: Adding refrigerant by using the automatic 
refrigerant charging function (recommended)

How to connect the tank?

1

Liquid stop valve

2

Gas line stop valve

3

To indoor unit

4

Service port for adding refrigerant

5

Valve A

6

R410A tank

7

Measuring instrument

8

Pipe fixing plate

When the refrigerant tank is connected and the specified operation is
performed, the appropriate amount of refrigerant will be charged into
the system. After charging, the system will stop automatically. The
refrigerant must be charged according to the procedure described
below.

Automatic refrigerant charging procedure

1

Open the liquid and gas side stop valves completely.

2

Turn on the power of the outdoor unit and indoor units.

3

Make sure that the led on the PCB (A1P and A2P) on the
outdoor unit are as shown in the table below. This indicates that
the system is operating normally.

Led state

Throughout the manual the state of the leds is indicated as
follows:

If H2P is lit up, check the type of error based on the error code in
the remote controller and correct the error in accordance with
"12.4. Test operation" on page 19.

4

Automatically charge the refrigerant according to the procedure
described below.

4.1

Press 

BS4 TEST

 once.

NOTICE

National implementation of EU regulation on certain
fluorinated greenhouse gases may require to provide the
appropriate official national language on the unit.
Therefore, an additional multilingual fluorinated
greenhouse gases label is supplied with the unit.

Sticking instructions are illustrated on the backside of that
label.

3

5

6

2

1

4

3

6

7

1 2

8

4

5

Y1

CAUTION

Make sure to turn ON the power 6 hours before
starting the operation. This is necessary to warm the
crankcase by the electric heater.

Automatic charging is able to charge 6 kg/hour
refrigerant at an outside temperature of 0°C to 24 kg/
hour refrigerant at an outside temperature of 35°C.
The charging time depends on the amount of charged
refrigerant and on the outside temperature.

Automatic refrigerant charging is 

NOT

 possible if the

following restrictions are exceeded:

Outside temperature: 0°C DB~43°C DB

Indoor temperature: 0°C DB~32°C DB

Indoor unit connection capacity: 50%~110%

WARNING

Note that valve A must be closed!

NOTICE

When an indoor unit is connected to the refrigerant
system and the indoor unit is turned off, automatic
charging will fail.

MODE

TEST/HWL

IND

MASTER

SLA

V

E

L.N.O.P

.

DEMAND

H1P H2P H3P H4P H5P H6P H7P

x x w x x x x

x

OFF

w

ON

c

blinking

c

ON or OFF

DANGER: RISK OF ELECTROCUTION

Do not touch anything else than the push-buttons (BS1~5)
on the PCB (A2P) when making the settings. These
settings must be done with the power ON.

H1P H2P H3P H4P H5P H6P H7P

w w w w w w w

4P357505-1.book  Page 12  Tuesday, September 10, 2013  7:59 AM

Summary of Contents for RXYSQ6P8Y1B9

Page 1: ...INSTALLATION MANUAL Installation manual VRVIII S System air conditioner English RXYSQ6P8Y1B9 System air conditioner...

Page 2: ...0 L1 2 H 1 2 H L1 0 L2 2 H 1 2 H L2 L2 H L2 H L2 H L2 H L2 H L2 H 150 500 500 500 500 750 100 100 100 100 200 300 200 100 250 250 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 300 300 300 250 300...

Page 3: ...9 16 V 230 V 16 V 16 V 16 V 2 3 4 1 2 3 4 1 4 5 5 5 380 415 V Y1 1 8 8 9...

Page 4: ...mo estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk...

Page 5: ...operation 19 12 5 Checks in normal operation 20 12 6 Temperature adjustment operation confirmation 20 13 Service mode operation 21 14 Caution for refrigerant leaks 21 14 1 Introduction 21 14 2 Maximu...

Page 6: ...book WARNING Ask your dealer or qualified personnel to carry out installation work Do not install the machine by yourself Improper installation may result in water leakage electric shocks or fire Perf...

Page 7: ...ing may cause water leakage and make the furniture get wet Install the indoor and outdoor units power wire and connecting wire at least 1 meter away from televisions or radios to prevent image interfe...

Page 8: ...tion site This is a class A product In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures 1 Select an installation site w...

Page 9: ...rdance with the foundation drawing in the figure fix the unit securely by means of the foundation bolts Prepare 4 sets of M12 foundation bolts nuts and washers each which are available on the market I...

Page 10: ...s frontward or downward The unit of numeric values is mm When routing the piping backward secure space of 250 mm on the right side of the unit A In case of non stacked installation See figure 4 B In c...

Page 11: ...gerant piping Do not allow anything other than the designated refrigerant to get mixed into the freezing cycle such as air etc If any refrigerant gas leaks while working on the unit ventilate the room...

Page 12: ...trating the center area around the knock out hole using a 6 mm drill See figure 5 Cutting out the two slits makes it possible to install as shown in figure 5 Use a metal saw to cut out the slits After...

Page 13: ...leakage after tightening the cap 10 5 Cautions for handling service port After the work tighten the valve cover in place Tightening torque 11 5 13 9 N m 10 6 Precautions when connecting field piping...

Page 14: ...n size of indoor unit indoor unit refnet joint refnet header Outdoor unit capacity type Refrigerant branch kit name KHRQ22M20T RXYSQ6 Outdoor unit capacity type Refrigerant branch kit name K 54 0 RXYS...

Page 15: ...frigerant more than the specified amount This outdoor unit is factory charged with refrigerant and depending on pipe sizes and pipe lengths some systems require additional charging of refrigerant See...

Page 16: ...s lit up check the type of error based on the error code in the remote controller and correct the error in accordance with 12 4 Test operation on page 19 4 Automatically charge the refrigerant accordi...

Page 17: ...ep 4 2 5 When charging is complete determine the weight of refrigerant that was added and fill in the amount in the Additional refrigerant charge label attached to service precautions plate on the uni...

Page 18: ...ndicates TEST test operation and external control 6 When the specified amount of refrigerant is charged push the BS3 RETURN button Then operation stops The operation automatically stops within 30 minu...

Page 19: ...quipped with an inverter installing a phase advancing capacitor not only will deteriorate power factor improvement effect but also may cause capacitor abnormal heating accident due to high frequency w...

Page 20: ...e it as described under 11 4 Connecting power wire and transmission wires on page 15 Inter unit wiring should be secured as described in 11 4 Connecting power wire and transmission wires on page 15 Se...

Page 21: ...ectrical shock make sure to disconnect the power supply 1 minute or more before servicing the electrical parts Even after 1 minute always measure the voltage at the terminals of main circuit capacitor...

Page 22: ...indicated as follows Setting the push button switch BS1 5 Function of the push button switch which is located on the outdoor unit PCB BS1 MODE For changing the set mode BS2 SET For field setting BS3...

Page 23: ...o Setting mode 1 on page 18 Possible functions A additional refrigerant charging operation B refrigerant recovery operation vacuuming operation C automatic low noise operation setting at nighttime D l...

Page 24: ...ndoor unit will control changeover of the cooling heating operation mode For the details refer to the instruction manual supplied together with the indoor unit 12 6 Temperature adjustment operation co...

Page 25: ...nt of major leak in the system and this in accordance to the local applicable regulations and standards 14 2 Maximum concentration level The maximum charge of refrigerant and the calculation of the ma...

Page 26: ...lest room and so until the result falls short of the maximum concentration 4 Dealing with the situations where the result exceeds the maximum concentration level Where the installation of a facility r...

Page 27: ...3 2 3 5 4 3 2 1 6 8 9 7 2 Y1 3 11 X2M F1 F1 F2 A C B F2 TO IN D UNIT C H SELECTOR X2M TO OUT D UNIT X1M A1P A B C F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 4 5 1 3 2 Y1 13 TO IN D UNIT F1...

Page 28: ...4P357505 1 2013 08 Copyright 2013 Daikin...

Reviews: