background image

RXYSQ6P8Y1B9

VRVIII-S System air conditioner

4P357505-1 – 2013.08

Installation manual

7

2.

In case of installing multiple units (2 units or more) in lateral
connection per row.

Relation of dimensions between H, A and L is shown in the table
below.

8.

Refrigerant pipe size and allowable 
pipe length

To persons in charge of piping work:

Be sure to open the stop valve after piping installing and
vacuuming is complete. (Running the system with the valve
closed may break the compressor.)

It is forbidden to discharge refrigerant into the atmosphere.
Collect the refrigerant in accordance with the freon collection
and destruction law.

Do not use flux when brazing the refrigerant piping.
For brazing, use phosphor copper brazing filler metal (BCuP)
which does not require a flux.
(If a chlorine flux is used, the piping will corrode, and if the flux
contains fluoride, it will cause the coolant oil to deteriorate,
adversely affecting the coolant piping system.

8.1.

Selection of piping material

Foreign materials inside pipes (including oils for fabrication)
must be 

30 mg/10 m.

Construction material: phosphoric acid deoxidized seamless
copper for refrigerant.

Temper grade: use piping with temper grade in function of the
pipe diameter as listed in table below.

The pipe thickness of the refrigerant piping should comply with
relevant local and national regulations. The minimal pipe
thickness for R410A piping must be in accordance with the table
below.

O = Annealed
1/2H = Half hard

Make sure to use the particular branches of piping that have
been selected.

In case the required pipe sizes (inch sizes) are not available, it is
also allowed to use other diameters (mm sizes), taken the
following into account:

select the pipe size nearest to the required size.

use the suitable adapters for the change-over from inch to
mm pipes (field supply).

9.

Precautions on refrigerant piping

Do not allow anything other than the designated refrigerant to
get mixed into the freezing cycle, such as air, etc. If any
refrigerant gas leaks while working on the unit, ventilate the
room thoroughly right away.

Use R410A only when adding refrigerant

Installation tools:

Make sure to use installation tools (gauge manifold charge hose,
etc.) that are exclusively used for R410A installations to
withstand the pressure and to prevent foreign materials (e.g.
mineral oils and moisture) from mixing into the system.

Vacuum pump:

Use a 2-stage vacuum pump with a non-return valve
Make sure the pump oil does not flow oppositely into the system
while the pump is not working.
Use a vacuum pump which can evacuate to –100.7 kPa (5 Torr,
–755 mm Hg).

In order to prevent dirt, liquid or dust from entering the piping,
cure the piping with a pinch or taping.

Great caution is needed when passing copper tubes through
walls.

For handling of stop valves, refer to "10.3. How to use the stop
valve" on page 9.

Only use the flare nuts included with the unit. Using different
flare nuts may cause the refrigerant to leak.

Always use the supplied copper gasket when connecting the
gas pipe supplied with the unit. See "10. Refrigerant piping" on
page 8.

9.1.

Cautions for brazing

Be sure to carry out a nitrogen blow when brazing.
Brazing without carrying out nitrogen replacement or releasing
nitrogen into the piping will create large quantities of oxidized
film on the inside of the pipes, adversely affecting valves and
compressors in the refrigerating system and preventing normal
operation.

L

A

L

H

0<L

1/2H

250

1/2H<L

H

300

H<L

Installation impossible

WARNING

All field piping must be installed by a licensed refrigeration
technician and must comply with relevant local and
national regulations.

Pipe Ø

Temper grade of piping 

material

Minimal thickness t 

(mm)

6.4 / 9.5 / 12.7

O

0.80

15.9

O

1

19.1

1/2H

1

1500

600

3000

A

H

L

Installation period

Protection method

More than a month

Pinch the pipe

Less than a month

Pinch or tape the pipe

Regardless of the 

period

4P357505-1.book  Page 7  Tuesday, September 10, 2013  7:59 AM

Summary of Contents for RXYSQ6P8Y1B9

Page 1: ...INSTALLATION MANUAL Installation manual VRVIII S System air conditioner English RXYSQ6P8Y1B9 System air conditioner...

Page 2: ...0 L1 2 H 1 2 H L1 0 L2 2 H 1 2 H L2 L2 H L2 H L2 H L2 H L2 H L2 H 150 500 500 500 500 750 100 100 100 100 200 300 200 100 250 250 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 300 300 300 250 300...

Page 3: ...9 16 V 230 V 16 V 16 V 16 V 2 3 4 1 2 3 4 1 4 5 5 5 380 415 V Y1 1 8 8 9...

Page 4: ...mo estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk...

Page 5: ...operation 19 12 5 Checks in normal operation 20 12 6 Temperature adjustment operation confirmation 20 13 Service mode operation 21 14 Caution for refrigerant leaks 21 14 1 Introduction 21 14 2 Maximu...

Page 6: ...book WARNING Ask your dealer or qualified personnel to carry out installation work Do not install the machine by yourself Improper installation may result in water leakage electric shocks or fire Perf...

Page 7: ...ing may cause water leakage and make the furniture get wet Install the indoor and outdoor units power wire and connecting wire at least 1 meter away from televisions or radios to prevent image interfe...

Page 8: ...tion site This is a class A product In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures 1 Select an installation site w...

Page 9: ...rdance with the foundation drawing in the figure fix the unit securely by means of the foundation bolts Prepare 4 sets of M12 foundation bolts nuts and washers each which are available on the market I...

Page 10: ...s frontward or downward The unit of numeric values is mm When routing the piping backward secure space of 250 mm on the right side of the unit A In case of non stacked installation See figure 4 B In c...

Page 11: ...gerant piping Do not allow anything other than the designated refrigerant to get mixed into the freezing cycle such as air etc If any refrigerant gas leaks while working on the unit ventilate the room...

Page 12: ...trating the center area around the knock out hole using a 6 mm drill See figure 5 Cutting out the two slits makes it possible to install as shown in figure 5 Use a metal saw to cut out the slits After...

Page 13: ...leakage after tightening the cap 10 5 Cautions for handling service port After the work tighten the valve cover in place Tightening torque 11 5 13 9 N m 10 6 Precautions when connecting field piping...

Page 14: ...n size of indoor unit indoor unit refnet joint refnet header Outdoor unit capacity type Refrigerant branch kit name KHRQ22M20T RXYSQ6 Outdoor unit capacity type Refrigerant branch kit name K 54 0 RXYS...

Page 15: ...frigerant more than the specified amount This outdoor unit is factory charged with refrigerant and depending on pipe sizes and pipe lengths some systems require additional charging of refrigerant See...

Page 16: ...s lit up check the type of error based on the error code in the remote controller and correct the error in accordance with 12 4 Test operation on page 19 4 Automatically charge the refrigerant accordi...

Page 17: ...ep 4 2 5 When charging is complete determine the weight of refrigerant that was added and fill in the amount in the Additional refrigerant charge label attached to service precautions plate on the uni...

Page 18: ...ndicates TEST test operation and external control 6 When the specified amount of refrigerant is charged push the BS3 RETURN button Then operation stops The operation automatically stops within 30 minu...

Page 19: ...quipped with an inverter installing a phase advancing capacitor not only will deteriorate power factor improvement effect but also may cause capacitor abnormal heating accident due to high frequency w...

Page 20: ...e it as described under 11 4 Connecting power wire and transmission wires on page 15 Inter unit wiring should be secured as described in 11 4 Connecting power wire and transmission wires on page 15 Se...

Page 21: ...ectrical shock make sure to disconnect the power supply 1 minute or more before servicing the electrical parts Even after 1 minute always measure the voltage at the terminals of main circuit capacitor...

Page 22: ...indicated as follows Setting the push button switch BS1 5 Function of the push button switch which is located on the outdoor unit PCB BS1 MODE For changing the set mode BS2 SET For field setting BS3...

Page 23: ...o Setting mode 1 on page 18 Possible functions A additional refrigerant charging operation B refrigerant recovery operation vacuuming operation C automatic low noise operation setting at nighttime D l...

Page 24: ...ndoor unit will control changeover of the cooling heating operation mode For the details refer to the instruction manual supplied together with the indoor unit 12 6 Temperature adjustment operation co...

Page 25: ...nt of major leak in the system and this in accordance to the local applicable regulations and standards 14 2 Maximum concentration level The maximum charge of refrigerant and the calculation of the ma...

Page 26: ...lest room and so until the result falls short of the maximum concentration 4 Dealing with the situations where the result exceeds the maximum concentration level Where the installation of a facility r...

Page 27: ...3 2 3 5 4 3 2 1 6 8 9 7 2 Y1 3 11 X2M F1 F1 F2 A C B F2 TO IN D UNIT C H SELECTOR X2M TO OUT D UNIT X1M A1P A B C F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 4 5 1 3 2 Y1 13 TO IN D UNIT F1...

Page 28: ...4P357505 1 2013 08 Copyright 2013 Daikin...

Reviews: