Installation manual

4

RXYSQ6P8Y1B9

VRVIII-S System air conditioner

4P357505-1 – 2013.08

Location of accessories: refer to figure 1.

1

Accessories

3.3.

Optional accessories

To install the above outdoor units, the following optional parts are also
required.

Refrigerant branching kit (for R410A only: Always use an
appropriate kit dedicated for your system.)

To select an optimum refrigerant branching kit, refer to "Example
of connection for VRV indoor units" on page 10.

3.4.

Technical and electrical specifications

Refer to the Engineering Data Book for the complete list of
specifications.

4.

Before installation

4.1.

Precautions for R410A

The refrigerant requires strict cautions for keeping the system
clean, dry and tight.
- Clean and dry
Foreign materials (including mineral oils or moisture) should be
prevented from getting mixed into the system.
- Tight
Read "9. Precautions on refrigerant piping" on page 7 carefully
and follow these procedures correctly.

Since R410A is a mixed refrigerant, the required additional
refrigerant must be charged in its liquid state. (If the refrigerant is
in state of gas, its composition changes and the system will not
work properly).

The connected indoor units must be indoor units designed
exclusively for R410A.

4.2.

Installation

For installation of the indoor unit(s), refer to the indoor unit
installation manual.

Never operate the air conditioner with the discharge pipe
thermistor (R2T), suction pipe thermistor (R3T) and pressure
sensors (S1NPH, S1NPL) removed. Such operation may burn
out the compressor.

Be sure to confirm the model name and the serial no. of the
outer (front) plates when attaching/detaching the plates to avoid
mistakes.

When closing the service panels, take care that the tightening
torque does not exceed 4.1 N•m.

4.3.

Handling

As shown in the figure, bring the unit slowly by grabbing the left and
right grips.

Place your hands on the corner instead of holding the suction inlet in
the side of the casing, otherwise the casing could be deformed.

5.

Selecting installation site

This is a class A product. In a domestic environment this product may
cause radio interference in which case the user may be required to
take adequate measures.

1

Select an installation site where the following conditions are
satisfied and that meets with your customer's approval.

- Places which are well-ventilated.
- Places where the unit does not bother next-door neighbours.
- Safe places which can withstand the unit's weight and 

vibration and where the unit can be installed level.

- Places where there is no possibility of flammable gas or 

product leak.

- Places where servicing space can be well ensured.
- Places where lengths of piping and wiring for indoor units and 

outdoor units are within the allowable ranges.

- Places where water leaking from the unit cannot cause 

damage to the location (e.g. in case of a blocked drain pipe).

- Places where the rain can be avoided as much as possible.

2

When installing the unit in a place exposed to strong wind, pay
special attention to the following.
Strong winds of 5 m/sec or more blowing against the outdoor
unit's air outlet causes short circuit (suction of discharge air),
and this may have the following consequences:
- Deterioration of the operational capacity.
- Frequent frost acceleration in heating operation.
- Disruption of operation due to rise of high pressure.
- When a strong wind blows continuously on the face of the 

unit, the fan can start rotating very fast until it breaks.

Refer to the figures for installation of this unit in a place where
the wind direction can be foreseen.

Drain cap

2

Drain receiver

3

Insulation tape

1

Drain stop

1

Fluorinated greenhouse gases 
label

1

Refnet header

Refnet joint

KHRQ22M29H

KHRQ22M20T

Since design pressure is 4.0 MPa or 40 bar, pipes of larger
wall thickness may be required. Refer to paragraph
"8.1. Selection of piping material" on page 7.

CAUTION

Take care not to let hands or objects come in contact with
rear fins.

WARNING

Make sure to provide for adequate measures in order
to prevent that the outdoor unit be used as a shelter
by small animals.

Small animals making contact with electrical parts can
cause malfunctions, smoke or fire. Please instruct the
customer to keep the area around the unit clean.

4P357505-1.book  Page 4  Tuesday, September 10, 2013  7:59 AM

Summary of Contents for RXYSQ6P8Y1B9

Page 1: ...INSTALLATION MANUAL Installation manual VRVIII S System air conditioner English RXYSQ6P8Y1B9 System air conditioner...

Page 2: ...0 L1 2 H 1 2 H L1 0 L2 2 H 1 2 H L2 L2 H L2 H L2 H L2 H L2 H L2 H 150 500 500 500 500 750 100 100 100 100 200 300 200 100 250 250 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 300 300 300 250 300...

Page 3: ...9 16 V 230 V 16 V 16 V 16 V 2 3 4 1 2 3 4 1 4 5 5 5 380 415 V Y1 1 8 8 9...

Page 4: ...mo estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk...

Page 5: ...operation 19 12 5 Checks in normal operation 20 12 6 Temperature adjustment operation confirmation 20 13 Service mode operation 21 14 Caution for refrigerant leaks 21 14 1 Introduction 21 14 2 Maximu...

Page 6: ...book WARNING Ask your dealer or qualified personnel to carry out installation work Do not install the machine by yourself Improper installation may result in water leakage electric shocks or fire Perf...

Page 7: ...ing may cause water leakage and make the furniture get wet Install the indoor and outdoor units power wire and connecting wire at least 1 meter away from televisions or radios to prevent image interfe...

Page 8: ...tion site This is a class A product In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures 1 Select an installation site w...

Page 9: ...rdance with the foundation drawing in the figure fix the unit securely by means of the foundation bolts Prepare 4 sets of M12 foundation bolts nuts and washers each which are available on the market I...

Page 10: ...s frontward or downward The unit of numeric values is mm When routing the piping backward secure space of 250 mm on the right side of the unit A In case of non stacked installation See figure 4 B In c...

Page 11: ...gerant piping Do not allow anything other than the designated refrigerant to get mixed into the freezing cycle such as air etc If any refrigerant gas leaks while working on the unit ventilate the room...

Page 12: ...trating the center area around the knock out hole using a 6 mm drill See figure 5 Cutting out the two slits makes it possible to install as shown in figure 5 Use a metal saw to cut out the slits After...

Page 13: ...leakage after tightening the cap 10 5 Cautions for handling service port After the work tighten the valve cover in place Tightening torque 11 5 13 9 N m 10 6 Precautions when connecting field piping...

Page 14: ...n size of indoor unit indoor unit refnet joint refnet header Outdoor unit capacity type Refrigerant branch kit name KHRQ22M20T RXYSQ6 Outdoor unit capacity type Refrigerant branch kit name K 54 0 RXYS...

Page 15: ...frigerant more than the specified amount This outdoor unit is factory charged with refrigerant and depending on pipe sizes and pipe lengths some systems require additional charging of refrigerant See...

Page 16: ...s lit up check the type of error based on the error code in the remote controller and correct the error in accordance with 12 4 Test operation on page 19 4 Automatically charge the refrigerant accordi...

Page 17: ...ep 4 2 5 When charging is complete determine the weight of refrigerant that was added and fill in the amount in the Additional refrigerant charge label attached to service precautions plate on the uni...

Page 18: ...ndicates TEST test operation and external control 6 When the specified amount of refrigerant is charged push the BS3 RETURN button Then operation stops The operation automatically stops within 30 minu...

Page 19: ...quipped with an inverter installing a phase advancing capacitor not only will deteriorate power factor improvement effect but also may cause capacitor abnormal heating accident due to high frequency w...

Page 20: ...e it as described under 11 4 Connecting power wire and transmission wires on page 15 Inter unit wiring should be secured as described in 11 4 Connecting power wire and transmission wires on page 15 Se...

Page 21: ...ectrical shock make sure to disconnect the power supply 1 minute or more before servicing the electrical parts Even after 1 minute always measure the voltage at the terminals of main circuit capacitor...

Page 22: ...indicated as follows Setting the push button switch BS1 5 Function of the push button switch which is located on the outdoor unit PCB BS1 MODE For changing the set mode BS2 SET For field setting BS3...

Page 23: ...o Setting mode 1 on page 18 Possible functions A additional refrigerant charging operation B refrigerant recovery operation vacuuming operation C automatic low noise operation setting at nighttime D l...

Page 24: ...ndoor unit will control changeover of the cooling heating operation mode For the details refer to the instruction manual supplied together with the indoor unit 12 6 Temperature adjustment operation co...

Page 25: ...nt of major leak in the system and this in accordance to the local applicable regulations and standards 14 2 Maximum concentration level The maximum charge of refrigerant and the calculation of the ma...

Page 26: ...lest room and so until the result falls short of the maximum concentration 4 Dealing with the situations where the result exceeds the maximum concentration level Where the installation of a facility r...

Page 27: ...3 2 3 5 4 3 2 1 6 8 9 7 2 Y1 3 11 X2M F1 F1 F2 A C B F2 TO IN D UNIT C H SELECTOR X2M TO OUT D UNIT X1M A1P A B C F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 4 5 1 3 2 Y1 13 TO IN D UNIT F1...

Page 28: ...4P357505 1 2013 08 Copyright 2013 Daikin...

Reviews: