![background image](http://html1.mh-extra.com/html/daikin/rxyq120ttju/rxyq120ttju_installation-manual_2459964035.webp)
32
3P362438-1B English
2
Field wiring
Be sure that the field wiring has been carried out according to the
instructions described in 9. Field wiring on page 18, according to
the wiring diagrams and according to the applicable legislation.
3
Power supply voltage
Check the power supply voltage on the local supply panel. The
voltage must correspond to the voltage on the identification label
of the unit.
4
Ground wiring
Be sure that the ground wires have been connected properly and
that the ground terminals are tightened.
5
Insulation test of the main power circuit
Using a megatester for 500 V, check that the insulation resistance
of 1 MΩ or more is attained by applying a voltage of 500 V DC
between power terminals and ground. Never use the megatester
for the transmission wiring.
6
Fuses, circuit breakers, or protection devices
Check that the fuses, circuit breakers, or the locally installed pro-
tection devices are of the size and type specified in 9. Field wiring
on page 18. Be sure that neither a fuse nor a protection device
has been bypassed.
7
Internal wiring
Visually check the control box and the inside of the unit on loose
connections or damaged electrical components.
8
Pipe size and pipe insulation
Be sure that correct pipe sizes are installed and that the insulation
work is properly executed.
9
Stop valves
Be sure that the stop valves are open on both liquid and gas side.
10
Damaged equipment
Check the inside of the unit on damaged components or squeezed
pipes.
11
Refrigerant leak
Check the inside of the unit on refrigerant leakage. If there is a
refrigerant leak, try to repair the leak. If the repair is unsuccess-
ful, call your local dealer. Do not touch any refrigerant which has
leaked out from refrigerant piping connections. This may result in
frostbite.
12
Oil leak
Check the compressor for oil leakage. If there is an oil leak, try
to repair the leak. If the repairing is unsuccessful, call your local
dealer.
13
Air inlet/outlet
Check that the air inlet and outlet of the unit is not obstructed by
paper sheets, cardboard, or any other material.
14
Record the contents of field setting.
Record them on the accessory
REQUEST FOR THE INDICATION
label.
And attach the label on the back side of the front panel.
15
Record the installation date.
Record the installation date on the accessory
REQUEST FOR
THE INDICATION
label.
And attach the label on the back side of the front panel.
15 .2 .
Monitoring function and field settings
The operation of the outdoor unit can further be defined by changing
some field settings. Next to making field settings it is also possible to
confirm the current operation parameters of the unit.
The setting can also be performed via the PC configuration software.
Below relevant Monitoring mode (mode 1) and Field setting mode
(mode 2) settings are explained in detail. How to access them, how to
change the value of the settings and how to confirm them is explained
in 13. Making field settings on page 23. In that chapter, an example
is given on how to make a setting. It is advised to check this procedure
before accessing, checking and changing below settings.
Once the default situation of the segment indication is confirmed (see
13. Making field settings on page 23), the mode 1 and mode 2 can
be accessed.
Making settings is done via the master outdoor unit.
15 .2 .1 . Mode 1
Mode 1 can be used to monitor the current situation of the outdoor
unit. Some field setting contents can be monitored as well.
Below the settings in mode 1 are explained.
[1-0]=
shows whether the unit you check is a master, sub 1 or sub 2
unit
• No indication=undefined situation
•
0=outdoor unit is master unit
•
1=outdoor unit is sub 1 unit
•
2=outdoor unit is sub 2 unit
Master, sub 1 and sub 2 indications are relevant in multiple
outdoor unit system configurations. The allocation of which
outdoor unit is master, sub 1 or sub 2 are decided by the
unit’s logic.
The master unit should be used to input field settings in
mode 2 .
[1-1]=
shows the status of low noise operation.
•
1=unit is currently operating under low noise restrictions
•
0=unit is currently not operating under low noise restric-
tions
Low noise operation reduces the sound generated by the
unit compared to nominal operating conditions.
Low noise operation can be set in mode 2. There are two
methods to activate low noise operation of the outdoor unit
system.
The first method is to enable an automatic low noise opera
-
tion during night time by field setting. The unit will operate at
the selected low noise level during the selected time frames.
The second method is to enable low noise operation based
on an external input. For this operation an optional acces
-
sory is required.
[1-2]=
shows the status of power consumption limitation operation.
•
1=unit is currently operating under power consumption
limitation
•
0=unit is currently not operating under power consump-
tion limitations
Power consumption limitation reduces the power consump-
tion of the unit compared to nominal operating conditions.
Power consumption limitation can be set in mode 2. There
are two methods to activate power consumption limitation of
the outdoor unit system.
The first method is to enable a forced power consumption
limitation by field setting. The unit will always operate at the
selected power consumption limitation.
The second method is to enable power consumption
limitation based on an external input. For this operation an
optional accessory is required.
[1-5]=
shows the current T
e
target parameter position.
Refer to 15.3. Energy saving and optimum operation on
page 35 for more details about the contents of this value.