background image

30

3P362438-1B English

 NOTE

• 

The refrigerant charging port is connected to the piping inside the 
unit. The unit’s internal piping is already factory charged with refrig-
erant, so be careful when connecting the charge hose.

• 

After adding the refrigerant, do not forget to close the lid of the 
refrigerant charging port. The tightening torque for the lid is 8.48 to 
10.3 ft

lbf (11.5 to 13.9 N

m). 

• 

In order to ensure uniform refrigerant distribution, it may take the 
compressor ±10 minutes to start up after the unit has started opera-
tion. This is not a malfunction.

A . 

Adding refrigerant by using the automatic charging function

 INFORMATION

The automatic refrigerant charging has limits as described below. Out 
of these limits, the system cannot operate the automatic refrigerant 
charging:

• 

Outdoor temperature: 32°F (0°C) DB -109°F (43°C) DB.

• 

Indoor temperature: 50°F (10°C) DB - 89°F (32°C) DB.

• 

Total indoor unit capacity:  80% (VRV indoor units only).

6A

   The remaining additional refrigerant charge can be charged by 

operating the outdoor unit by means of the automatic refrigerant 
charge operation mode.
Depending on the ambient limitation conditions (see above), the 
unit will automatically decide which operation mode will be used 

to fulfill the automatic refrigerant charge: cooling or heating. If 
above conditions are fulfilled, cooling operation will be selected. If 

not, heating mode will start.

Procedure

• 

Idle (default) screen is shown.

• 

Push BS2 once, indication 

888

.

• 

Push BS2 for more than 5 seconds, wait while the unit is 
preparing for operation. Segment display indication: 

01

 (pres-

sure control is executed):

 

- In case heating operation is started: indication 

22

 till 

23

 

will be displayed (start up control; waiting stable heating 
operation).

 

- In case cooling operation is started: indication 

02

 till 

03

 

will be displayed (start up control; waiting stable cooling 
operation).

• 

When 

23

 or 

03

 starts flashing (ready for charging), push 

BS2 within 5 minutes. Open valve A. If BS2 is not pushed within 
5 minutes, a malfunction code will appear:

 

- Heating operation: 

26

 will be flashing. Push BS2 to restart 

the procedure.

 

- Cooling operation: malfunction code 

P2

 will appear.

Push BS1 to abort and restart the procedure.

 

Heating (middle segment indicates 

2

)

Charging will continue, the segment indication intermittently 
shows the current low pressure value and the status indication 

23

.

When the remaining additional refrigerant amount is charged, 
close valve A immediately and push BS3 to stop charging opera-
tion.
After BS3 is pushed, the ending code 

26

 will appear. When BS2 

is pushed, the unit will check whether the ambient conditions are 

favorable to execute the test run.

 

- If 

01

02

, or 

03

 appears, push BS1 to finish the auto

-

matic charging function procedure. The ambient conditions 

are favorable to execute the test run.

 

- If the unit indicates 

E-2

, or 

E-3

, the ambient conditions are 

NOT favorable to execute the test run. Push BS1 to finish the 

automatic charging procedure.

 INFORMATION

In case a malfunction code occurred during this automatic charging 
procedure, the unit will stop and indicate 

26

 flashing. Push BS2 to 

restart the procedure. 

Cooling (middle segment indicates 

0

)

Automatic charging will continue, the segment indication shows 
the current low pressure value and the status indication 

03

 

intermittent. 
If the segment indication/user interface of indoor unit shows 

PE

 

code, charging is almost finished. When the unit stops operating, 

close valve A immediately and check whether the segment indi-
cation/user interface of indoor unit shows 

P9

. This indicates the 

automatic charging in cooling program was finished successfully.

 INFORMATION

When the charging amount is little, the 

PE

 code may not be displayed, 

but instead the 

P9

 code will be displayed immediately. 

When the required (calculated) additional refrigerant amount is 
already charged before 

PE

 or 

P9

 indication appears, close valve A and 

wait till 

P9

 is displayed. 

If during the cooling operation for the automatic refrigerant charge 
the ambient conditions go beyond the allowable for this operation 
mode, the unit will indicate on the segment display the code 

E-2

 

in case indoor temperature is out of range or 

E-3

 in case the out-

door temperature is out of range. In this case, when the additional 

refrigerant charging was not finished, step 6A has to be repeated.

 INFORMATION

• 

When a malfunction is detected during the procedure (e.g, in case 
of closed stop valve), a malfunction code will be displayed. In that 

case, refer to 15.5. Malfunction code list on page 39 and solve 

the malfunction accordingly. Resetting the malfunction can be done 
by pushing BS1. The procedure can be restarted from 6A.).

• 

Aborting the automatic refrigerant charge is possible by pushing 
BS1. The unit will stop and return to idle condition.

Perform the test procedure as described in 15.4.2. Test operation on 

page 38.

B . 

Adding refrigerant by using the manual charging function

6B

    The remaining additional refrigerant charge can be charged by 

operating the outdoor unit by means of the manual refrigerant 
charge operation mode:

• 

Turn on the power of the indoor units and outdoor unit.

• 

Take all the precautions mentioned in 

start-up and configura

-

tion

 into account.

• 

Activate outdoor unit setting [2-20]=1 to start manual refriger-

ant charge mode. Refer to page 33 for details.

Result: 

The unit will start operation. Valve A can be opened.

Charging of remaining additional refrigerant can be done.
When the remaining calculated additional refrigerant amount is 
added, close valve A and push BS3 to stop the manual refrig-
erant charging procedure.

 INFORMATION

The manual refrigerant charge operation will automatically stop within 
30 minutes. If charging is not completed after 30 minutes, perform the 
additional refrigerant charging operation again.

Summary of Contents for RXYQ120TTJU

Page 1: ...RXYQ216TTJU RXYQ240TTJU RXYQ264TTJU RXYQ288TTJU RXYQ312TTJU RXYQ336TTJU RXYQ360TTJU RXYQ384TTJU RXYQ408TTJU RXYQ72TYDN RXYQ96TYDN RXYQ120TYDN RXYQ144TYDN RXYQ168TYDN RXYQ192TYDN RXYQ216TYDN RXYQ240TYD...

Page 2: ...RNING Only qualified personnel must carry out the installation work Installation must be done in accordance with this installation manual Improper installation could result in water leakage electric s...

Page 3: ...away from fluorescent lamps as much as possible Indoor units are for indoor installation only Outdoor units can be installed either outdoors or indoors This unit is for indoor use Do not install the a...

Page 4: ...piping material 9 7 3 Selection of piping size 9 7 4 Selection of refrigerant branch kits 10 7 5 System piping length limitations 11 8 Precautions on refrigerant piping 14 8 1 Caution for brazing 14 8...

Page 5: ...unit combinations Standard combinations for VRV IV heat pump system are as indicated in table below where RXYQ192 408 consists of several RXYQ72 168 modules as indicated 72 96 120 144 168 RXYQ72TTJU T...

Page 6: ...following accessories are included The storage location of the accessories is shown in the figure below Accessories assy piping Accessories assy operation and installation manual NOTE Do not throw aw...

Page 7: ...e reasonable protection against such interference However there is no guarantee that inter ference will not occur in a particular installation It is therefore recommended to install the equipment and...

Page 8: ...nopy 2 Construct a pedestal NOTE When operating the unit in a low outdoor ambient temperature with high humidity conditions make sure to take precautions to keep the drainholes of the unit free by usi...

Page 9: ...a Front side Suction side b h2 2 or more Service space h1 2 or more h1 b a 59 in 1500 mm b 19 5 8 in 500 mm In case of an installation site where sides A B C D have obsta cles the wall heights of sid...

Page 10: ...ling of 3 4 in 20 mm wide that adequately bears the weight of the unit A forklift can only be used for transport as long as the unit remains on its pallet as shown above 6 3 Unpacking CAUTION To avoid...

Page 11: ...oundation surface A A 13 16 in 20 mm NOTE There are restrictions on the refrigerant pipe connecting order between outdoor unit in the case of the multi system See 1 2 2 Outdoor unit combinations on pa...

Page 12: ...t size Thickness Select a thickness for the refrigerant piping which complies with national and local laws For piping work follow the maximum tolerated length difference in height and length after a b...

Page 13: ...se 4 First refrigerant branch kit 5 Indoor unit Size up for equivalent length for outdoor indoor units over 295 ft 90 m Outdoor unit capacity type Gas pipe Liquid pipe RXYQ72T type 3 4 in 19 1 mm 7 8...

Page 14: ...gth allowable height difference and al lowable length after branching as indicated below 3 patterns will be discussed including VRV indoor units combined with Mini split indoor units Definitions Actua...

Page 15: ...ple 1 3 unit 8 a i 540 ft 165 m Equivalent length 2 623 ft 190 m Total piping length 3280 ft 1000 m Example 1 1 a b c d e f g h i j k l m n p 3280 ft 1000 m Example 2 1 a b c d e f g h i j k l m n p 3...

Page 16: ...een the nearest indoor from the first branch to the outdoor unit and farthest indoor to the outdoor unit is 130 ft 40 m Example The farthest indoor unit 8 The nearest indoor unit 1 a b c d e f g p a h...

Page 17: ...brazing Blowing through with Dry Nitrogen prevents the creation of large quantities of oxidized film on the inside of the piping An oxidized film ad versely affects valves and compressors in the refri...

Page 18: ...ective plate Stop valve mounting plate 5 Cut off the lower part of the smaller pinched piping with an ap propriate tool such as pipe cutters Let the remaining oil drip out in case the recovery was not...

Page 19: ...tween outdoor units an optional multi con nection piping kit BHFP22P100U 151U is always required When installing the piping follow the instructions in the installation manual that comes with the kit O...

Page 20: ...so that it branches horizontally Installation of the multi connection piping kit A 1 max 15 B 1 C D C 4 3 4 in 120 mm D 19 11 16 in 500 mm 3 Install the joints horizontally so that the caution label...

Page 21: ...field wiring and components must be installed by a licensed elec trician and must comply with relevant local and national regulations Be sure to use a dedicated power circuit Never use a power supply...

Page 22: ...V 460 V 460 V 460 V 460 V 460 V 460 V 27 6A 36 3A 36 3A 55 1A 55 1A 27 6A 36 3A 36 3A 36 3A 36 3A 36 3A 36 3A 55 1A 55 1A 55 1A 55 1A 55 1A 55 1A 55 1A 36 3A 36 3A 36 3A 36 3A 36 3A 55 1A 36 3A 55 1A...

Page 23: ...o an indoor unit is Master unit of the multi system The other units are Sub units In this figure Outdoor unit A is the Master unit Check installation work to ensure proper operation Onsite settings ca...

Page 24: ...Ground terminal 10 Clamp 1 accessory 11 Vinyl tube accessory CAUTION Be sure to use crimp style terminal with insulating sleeves for con nections See the figure below Crimp style terminal Insulating...

Page 25: ...after the stop valve is opened will cause the insulation value to drop Needed tools Gauge manifold Charge hose valve To prevent entry of any impurities and insure sufficient pressure resistance always...

Page 26: ...insulate the pipes may cause leaking or burns Be sure to use insulation designed for HVAC equipment Reinforce the insulation on the refrigerant piping according to the installation environment Conden...

Page 27: ...elow procedure explains how to operate the push buttons to reach the required mode in the menu select the correct setting and modify the value of the setting This procedure can be used any time specia...

Page 28: ...elected push BS1 for more than 5 seconds you can select the wanted setting It is done by pushing BS2 Accessing the selected setting s value is done by pushing BS3 one time Now BS2 is used to select th...

Page 29: ...itional refrigerant to be charged Additional refrigerant to be charged R lbs R should be rounded off in units of 0 1 lbs R X1 f7 8 0 249 X2 f3 4 0 175 X3 f5 8 0 121 X4 f1 2 0 081 X5 f3 8 0 040 X6 f1 4...

Page 30: ...on on page 38 R Q You want to execute automatic refrigerant charge B A Step 4b 5 Manual refrigerant charging method in cooling operation NO YES Step 4b 5 Automatic refrigerant charging method Step 6B...

Page 31: ...38 During gray conditions If following codes appear E 2 indoor temperature out of range and E 3 outdoor temperature out of range In this case perform automatic charg ing procedure again See figure Loc...

Page 32: ...low chart is available which gives an overview of the possibilities and actions to be taken see 14 3 1 Flow chart on page 27 To speed up the process of pre charging refrigerant for large systems it is...

Page 33: ...st run If the unit indicates E 2 or E 3 the ambient conditions are NOT favorable to execute the test run Push BS1 to finish the automatic charging procedure INFORMATION In case a malfunction code occu...

Page 34: ...gauge lines Connect service gauge manifold to the service port between the compressor and the reversing valve in each outdoor unit Run the system for 30 minutes in cooling by the forced operation usi...

Page 35: ...C configuration software Below relevant Monitoring mode mode 1 and Field setting mode mode 2 settings are explained in detail How to access them how to change the value of the settings and how to conf...

Page 36: ...ool Heat selection setting is used in case the optional Cool Heat selector KRC19 26A is used Depending on the outdoor unit setup single outdoor unit setup or multi outdoor unit setup the correct setti...

Page 37: ...or 3 2 26 Low noise operation start time Change 2 26 1 2 or 3 in function of required timing Default value 2 Value 2 26 Start time automatic low noise operation approximately 1 8 00 p m 2 10 00 p m de...

Page 38: ...rt setting Default value 1 Value 2 82 Heating comfort setting 0 Eco 1 Mild default 2 Quick 3 Powerful Change 2 82 0 1 2 or 3 in function of required limitation This setting is used in conjunction with...

Page 39: ...ting opera tion change field setting 2 82 3 This setting is used in conjunction with setting 2 9 Quick Overshoot during heating operation or undershoot during cooling operation is allowed compared to...

Page 40: ...perature evolution A B C D E F A Indoor unit set temperature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during cooling A B 100 70 E Tc C D 120 F 49 C F 115 F 4...

Page 41: ...RMATION Note that during the first running period of the unit required power in put may be higher This phenomenon originates from the compressor that requires a 50 hour run elapse before reaching smoo...

Page 42: ...ction code table After correcting the abnormality press BS3 to reset the malfunction code and retry operation The malfunction code which is displayed on the outdoor unit will indi cate a main malfunct...

Page 43: ...c tion R6T A1P X30A Check connection on printed circuit board or actuator JA 06 08 10 High pressure sensor malfunction S1NPH open circuit A1P X32A Check connection on printed circuit board or actuator...

Page 44: ...02 Faulty wiring to Q1 Q2 or indoor outdoor Connect transmission wiring of indoor unit to TO IN D UNIT F1 F2 and transmission wiring of other outdoor unit to TO OUT D UNIT F1 F2 11 Too many indoor un...

Page 45: ...e i CAUTION When performing service to inverter equipment 1 Do not open the control box cover for 10 minutes after the power supply is turned off 2 Measure the voltage between terminals on the termina...

Page 46: ...y large This assures that the maximum concentration level of refrigerant gas is not exceeded in the unlikely event of major leak in the system and this in accordance to the local applicable regulation...

Page 47: ......

Page 48: ......

Page 49: ...3P362438 1B EM13A019A 1402 FS...

Reviews: