Wiring

 WARNING

1) Do not use tapped wires, stranded wires (

CAUTION (1)

), extension cords, or starburst connections, as they may cause over-

heating, electrical shock, or fire.

2) Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the 

terminal block.) Doing so may cause electric shock or fire.

3) Be sure to install an earth leak detector. (One that can handle higher harmonics.)

(This unit uses an inverter, which means that it must be used an earth leak detector capable handling harmonics in order to 
prevent malfunctioning of the earth leak detector itself.)

4) Use an all-pole disconnection type breaker with at least 3mm between the contact point gaps.

5) The earth leakage circuit breaker must operate at 30mA or lower.

• Do not turn ON the safety breaker until all work is completed.

1) Strip the insulation from the wire (20mm).
2) Connect the connection wires between the 

indoor and outdoor units 

so that the termi-

nal numbers match

. Tighten the terminal 

screws securely. We recommend a flathead 
screwdriver be used to tighten the screws. 
The screws are packed with the terminal 
board.

 CAUTION (1)

In case using stranded wires is unavoidable for some reason, 
make sure to install the round crimp-style terminals on the tip. 

Place the round crimp-style terminals on the wires up to the 
covered part and secure in place.

1
2
3

1 2 3

L N

Safety 
breaker 
20A

Earth leakage 
circuit breaker

Earth

When wire length exceeds 10m, 
use 2.0mm diameter wires.

H05VV

Firmly fix the wires with 
the terminal screws.

Outdoor unit

Indoor 
unit

Power supply
50Hz 220-240V

Firmly fix the wires with 
the terminal screws.

Use 2.0mm diameter wires.

1

2

3

1

2

3

Use the specified wire type 
and connect it securely.

Firmly secure wire retainer 
so wire terminations will 
not receive external stress.

Shape wires so 
that the service 
lid fit securely.

Power supply
terminal block

Stranded wire

Round crimp-style
terminal

01_EN_3P190651-2C.fm  Page 9  Tuesday, March 13, 2007  4:35 PM

Summary of Contents for RXR28EV1B9

Page 1: ...V1B9 Installation manual R410A Split series Montaj k lavuzlar R410A Split serisi Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Montagehandleiding R410A Split syst...

Page 2: ...TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ E...

Page 3: ...e on the electrical covers or panels Install covers over the wires Incomplete cover installation may cause terminal overheating electrical shock or fire If any refrigerant has leaked out during the in...

Page 4: ...s to prevent interference to images and sounds Noises may be heard even if they are more than 3 meter away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere o...

Page 5: ...e from entering it until it is connected to the indoor unit and outdoor unit ducts Do not bend the humidifying hose more than 90 C C C C C D E F C C C No refrigerant needs to be added if the piping do...

Page 6: ...drain water may freeze impairing heating performance 3 Flaring the pipe end 1 Cut the pipe end with a pipe cutter 2 Remove burrs with the cut surface facing downward so that the chips do not enter the...

Page 7: ...onment 4 Use a vacuum pump for R410A exclusively Using the same vacuum pump for different refrigerants may damage the vacuum pump or the unit If using additional refrigerant perform air purging from t...

Page 8: ...tion 3 Do vacuum pumping and make sure that the compound pressure gauge reads 0 1MPa 76cmHg The vacuum pump should run for at least 10 min 4 Close gauge manifold s low pressure valve Lo and stop vacuu...

Page 9: ...t n 2 the additional refrigerant amount charged in the field and n 1 2 the total refrigerant charge on the refrigerant charge label supplied with the product Important information regarding the refrig...

Page 10: ...o the outdoor humidifying duct 2 Apply a binding band to prevent the humidifying hose from coming off 2 Connecting the cut humidifying hoses When installing the cut humidifying hoses follow the instru...

Page 11: ...m the wire 20mm 2 Connect the connection wires between the indoor and outdoor units so that the termi nal numbers match Tighten the terminal screws securely We recommend a flathead screwdriver be used...

Page 12: ...ooling heating function Refrigerant gas and liquid pipes and indoor drain hose extension are ther mally insulated Water leakage Draining line is properly installed Water leakage System is properly ear...

Page 13: ...0704 HT 3P190651 2C M06B104C Two dimensional bar code is a code for manufacturing...

Reviews: