background image

7

English

Outdoor Unit Installation

7.

Refrigerant piping work.

7-1 Cautions on pipe handling. 

1)Protect the open end of the pipe against dust and moisture.
2)All pipe bends should be as gentle as possible. Use a pipe bender 

for bending.
(Bending radius should be 30 to 40mm or larger.)

7-2 Selection of copper and heat insulation materials.

When using commercial copper pipes and fittings, observe the following:
1) Insulation material:  Polyethylene foam 

Heat transfer rate:  0.041 to 0.052W/mK (0.035 to 0.045kcal/mh°C)

Refrigerant gas pipe’s surface temperature reaches 110°C max.
Choose heat insulation materials that will withstand this temperature.

2) Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below.  

3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.

Gas side

Liquid side

Gas pipe thermal 

insulation

Liquid pipe thermal 

insulation

O.D. 9.5mm

O.D. 6.4mm

I.D. 12-15mm

I.D. 8-10mm

Thickness 0.8mm

Thickness 10mm Min.

3

5

6

2

1

4

Please fill in with indelible ink, 

n

1

  the factory refrigerant charge of the product, 

n

2

  the additional refrigerant amount charged in the field and

n

1  +  2

  the total refrigerant charge 

on the refrigerant charge label supplied with the product.

Important information regarding the refrigerant used

This product contains fluorinated greenhouse gases covered by 
the Kyoto Protocol. Do not vent gases into the atmosphere.

Refrigerant type:

R410A

GWP

(1)

 value:

1975

 

(1) 

GWP = global warming potential 

1

factory refrigerant charge of the 
product: 
see unit name plate 

2

additional refrigerant amount 
charged in the field 

3

total refrigerant charge 

4

Contains fluorinated greenhouse 
gases covered by the Kyoto 
Protocol

5

outdoor unit

6

refrigerant cylinder and manifold 
for charging

The filled out label must be adhered in the 
proximity of the product charging port (e.g. 
onto the inside of the stop valve cover).

Wall

If no flare cap is 
available, cover the 
flare mouth with 
tape to keep dirt or 
water out.

Be sure to 
place a cap.

Rain

Piping bundle diagram

Finishing tape

Liquid pipe insulation

Inter-unit wiring

Gas pipe 
insulation

Gas pipe

Humidifying 
hose

C

Drain hose

Liquid pipe

Seal the edge of the 
insulation if there is a 
possibility that the 
condensation from the 
shut-off valve might 
drip onto the indoor 
unit through the gap 
between the insulation 
and the pipe.

01_EN_3P190651-2C.fm  Page 7  Tuesday, March 13, 2007  4:35 PM

Summary of Contents for RXR28EV1B9

Page 1: ...V1B9 Installation manual R410A Split series Montaj k lavuzlar R410A Split serisi Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Montagehandleiding R410A Split syst...

Page 2: ...TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ E...

Page 3: ...e on the electrical covers or panels Install covers over the wires Incomplete cover installation may cause terminal overheating electrical shock or fire If any refrigerant has leaked out during the in...

Page 4: ...s to prevent interference to images and sounds Noises may be heard even if they are more than 3 meter away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere o...

Page 5: ...e from entering it until it is connected to the indoor unit and outdoor unit ducts Do not bend the humidifying hose more than 90 C C C C C D E F C C C No refrigerant needs to be added if the piping do...

Page 6: ...drain water may freeze impairing heating performance 3 Flaring the pipe end 1 Cut the pipe end with a pipe cutter 2 Remove burrs with the cut surface facing downward so that the chips do not enter the...

Page 7: ...onment 4 Use a vacuum pump for R410A exclusively Using the same vacuum pump for different refrigerants may damage the vacuum pump or the unit If using additional refrigerant perform air purging from t...

Page 8: ...tion 3 Do vacuum pumping and make sure that the compound pressure gauge reads 0 1MPa 76cmHg The vacuum pump should run for at least 10 min 4 Close gauge manifold s low pressure valve Lo and stop vacuu...

Page 9: ...t n 2 the additional refrigerant amount charged in the field and n 1 2 the total refrigerant charge on the refrigerant charge label supplied with the product Important information regarding the refrig...

Page 10: ...o the outdoor humidifying duct 2 Apply a binding band to prevent the humidifying hose from coming off 2 Connecting the cut humidifying hoses When installing the cut humidifying hoses follow the instru...

Page 11: ...m the wire 20mm 2 Connect the connection wires between the indoor and outdoor units so that the termi nal numbers match Tighten the terminal screws securely We recommend a flathead screwdriver be used...

Page 12: ...ooling heating function Refrigerant gas and liquid pipes and indoor drain hose extension are ther mally insulated Water leakage Draining line is properly installed Water leakage System is properly ear...

Page 13: ...0704 HT 3P190651 2C M06B104C Two dimensional bar code is a code for manufacturing...

Reviews: