background image

English

10

 CAUTION (2)

When connecting the connection wires to the terminal board using a single core wire, be sure to perform curling. 
Problems with the work may cause heat and fires. 

Test Run and Final Check

1.

Trial operation and testing.

• Measure the supply voltage and make sure that it falls in the specified range.
• See “Test Run and Final Check” in the installation manual that came with the indoor unit for details on how to perform the 

test run and what to check for.

2.

Test items. 

Test Items

Symptom

(diagnostic display on RC)

Check

Outdoor unit is installed properly on a solid base.

Fall, vibration, noise

No refrigerant gas leaks.

Incomplete cooling/heating 
function

Refrigerant gas and liquid pipes and indoor drain hose extension are ther-
mally insulated.

Water leakage

Draining line is properly installed.

Water leakage

System is properly earthed.

Electrical leakage

The specified wires are used for interconnecting wire connections.

Inoperative or burn damage

Outdoor unit’s air intake or exhaust has clear path of air.
Stop valves are opened.

Incomplete cooling/heating 
function

2) Use the following method when installing the round crimp-style terminal. 

Arrow view 

<Ground terminal installation>

1) Use the following method when installing a single core wire.

A single core wire

Flat washer

Screw

Arrow view 

Flat washer

Screw

Round 
crimp-style 
terminal

Good

Round crimp-
style terminal

Flat washer

Screw

Wrong

Flat washer

Round crimp-
style terminal

Screw

Stripping wire at terminal block

01_EN_3P190651-2C.fm  Page 10  Tuesday, March 13, 2007  4:35 PM

Summary of Contents for RXR28EV1B9

Page 1: ...V1B9 Installation manual R410A Split series Montaj k lavuzlar R410A Split serisi Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Montagehandleiding R410A Split syst...

Page 2: ...TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ E...

Page 3: ...e on the electrical covers or panels Install covers over the wires Incomplete cover installation may cause terminal overheating electrical shock or fire If any refrigerant has leaked out during the in...

Page 4: ...s to prevent interference to images and sounds Noises may be heard even if they are more than 3 meter away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere o...

Page 5: ...e from entering it until it is connected to the indoor unit and outdoor unit ducts Do not bend the humidifying hose more than 90 C C C C C D E F C C C No refrigerant needs to be added if the piping do...

Page 6: ...drain water may freeze impairing heating performance 3 Flaring the pipe end 1 Cut the pipe end with a pipe cutter 2 Remove burrs with the cut surface facing downward so that the chips do not enter the...

Page 7: ...onment 4 Use a vacuum pump for R410A exclusively Using the same vacuum pump for different refrigerants may damage the vacuum pump or the unit If using additional refrigerant perform air purging from t...

Page 8: ...tion 3 Do vacuum pumping and make sure that the compound pressure gauge reads 0 1MPa 76cmHg The vacuum pump should run for at least 10 min 4 Close gauge manifold s low pressure valve Lo and stop vacuu...

Page 9: ...t n 2 the additional refrigerant amount charged in the field and n 1 2 the total refrigerant charge on the refrigerant charge label supplied with the product Important information regarding the refrig...

Page 10: ...o the outdoor humidifying duct 2 Apply a binding band to prevent the humidifying hose from coming off 2 Connecting the cut humidifying hoses When installing the cut humidifying hoses follow the instru...

Page 11: ...m the wire 20mm 2 Connect the connection wires between the indoor and outdoor units so that the termi nal numbers match Tighten the terminal screws securely We recommend a flathead screwdriver be used...

Page 12: ...ooling heating function Refrigerant gas and liquid pipes and indoor drain hose extension are ther mally insulated Water leakage Draining line is properly installed Water leakage System is properly ear...

Page 13: ...0704 HT 3P190651 2C M06B104C Two dimensional bar code is a code for manufacturing...

Reviews: