Outdoor Unit Installation

Cautions on pipe handling

•  Protect the open end of the pipe from dust and moisture.
•  All pipe bends should be as gentle as possible. Use a pipe bender for bending.

Selection of copper and heat insulation materials

When using commercial copper pipes and fittings, observe the following:

•  Insulation material: Polyethylene foam 

Heat transfer rate: 0.041 to 0.052W/mK (0.024 to 0.030Btu/fth°F) (0.035 to 
0.045kcal/mh°C)

 

Be sure to use insulation that is designed for use with HVAC Systems.

• 

ACR Copper only.

•  Be sure to insulate both the gas and liquid piping and observe the insulation 

dimensions as below.

Be sure to 
place a cap.

Wall

Rain

If no flare cap is 

available, cover 

the flare mouth 

with tape to 
keep dirt and 
water out.

Piping size

Minimum bend radius

Piping thickness

Thermal insulation size

Thermal insulation 

thickness

Gas side

O.D. 3/8 inch

(9.5mm)

1-3/16 inch (30mm) 

or more

0.031 inch (0.8mm)

(C1220T-O)

I.D. 15/32-19/32 inch

(12-15mm)

13/32 inch

(10mm) Min.

Liquid side

O.D. 1/4 inch

(6.4mm)

1-3/16 inch (30mm) 

or more

0.031 inch (0.8mm)

(C1220T-O)

I.D. 5/16-13/32 inch

(8-10mm)

•  Use separate thermal insulation pipes for gas and liquid refrigerant pipes.
• 

Using finishing tape, bundle and wrap the indoor unit piping and drain hose 

together so that the drain hose is below the other piping.

Finishing tape

Gas pipe

Drain hose

Liquid pipe

Liquid pipe 
insulation

Gas pipe 
insulation

5. 

Pressure test and evacuating system

WARNING

• 

Make sure that air or any matter other than refrigerant (R32) does not get into the refrigeration cycle.

•  If refrigerant gas leaks should occur, ventilate the room as soon and as much as possible.
•  R32, as well as other refrigerants, should always be recovered and never be released directly into the environment.
• 

Use tools for R32 or R410A (such as the gauge manifold, charging hose, or vacuum pump adapter).

CAUTION

• 

It is highly recommended that you do not open/close the stop valves when the outdoor temperature is below −5°F (−21°C) 

as this may result in refrigerant leakage.

01_EN_3P686856-1.indd   7

2022/04/20   9:15:05

Summary of Contents for RXM09WVJU9

Page 1: ...ais Espa ol MODELS RXM09WVJU9 RXM12WVJU9 DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R32 Split Series Installation manual Manuel d installation Manual de instalaci n 00_CV_3P686856 1 indd 1 2022 0...

Page 2: ...lly in basements and an asphyxiation hazard could occur leading to serious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can ca...

Page 3: ...event condensation Be careful when transporting the product Do not turn off the power immediately after stopping operation Always wait for at least 5 minutes before turning off the power Otherwise wat...

Page 4: ...itioner 8 Since water will flow from the drain of the outdoor unit do not place anything under the unit which must be kept away from moisture 9 A location where flammable gas does not leak Position at...

Page 5: ...s How to remove the stop valve cover 1 Remove the screw on the stop valve cover 2 Slide the stop valve cover downward to remove it How to attach the stop valve cover 1 Insert the upper part of the sto...

Page 6: ...t is recommended to either change the orientation of the outdoor unit outlet side or use the air direction adjustment grille sold separately Outdoor Unit Installation 1 Installing the outdoor unit Whe...

Page 7: ...are tool Clutch type Clutch type Rigid type Wing nut type Imperial type A 0 0 020 inch 0 0 5mm 0 039 0 059 inch 1 0 1 5mm 0 059 0 079 inch 1 5 2 0mm Flaring 4 Refrigerant piping CAUTION Use the flare...

Page 8: ...C1220T O I D 15 32 19 32 inch 12 15mm 13 32 inch 10mm Min Liquid side O D 1 4 inch 6 4mm 1 3 16 inch 30mm or more 0 031 inch 0 8mm C1220T O I D 5 16 13 32 inch 8 10mm Use separate thermal insulation...

Page 9: ...ifold and stop vacuum pumping Maintain this condition for a few minutes to make sure that the compound pressure gauge pointer does not swing back 1 6 Remove the valve caps from the liquid stop valve a...

Page 10: ...connection to the power supply terminal block Place the round crimp style terminals on the wires up to the covered part and secure in place Round crimp style terminal Stranded wire Screw Flat washer S...

Page 11: ...ate Screws Screws Conduit mounting cover Ground This air conditioner must be grounded For grounding follow all local and state electrical codes Facility Setting cooling at low outdoor temperature WARN...

Page 12: ...1 Remove the top plate of the outdoor unit 4 screws 2 Remove the Electric wiring box cover 3 Cut the jumper J4 of the PCB inside Hook 3 places Cut the jumper J4 Electrical wiring box cover When attach...

Page 13: ...ct and press for confirmation 3 Press and select the COOL operation 4 Press to turn on the system Forced cooling operation will stop automatically after about 30 minutes To stop the operation press Tr...

Page 14: ...3P686856 1 M21B535 2205 HT The two dimensional bar code is a manufacturing code 00_CV_3P686856 1 indd 2 2022 02 15 9 41 18...

Reviews: