•  When piping work is complete, it is necessary to perform a pressure test 

and evacuate system with a vacuum pump.

•  If using additional refrigerant, purge the air from the refrigerant pipes and 

indoor unit using a vacuum pump, then charge additional refrigerant.

• 

Use a hexagonal wrench (3/16 inch (4mm)) to operate the stop valve rod.

•  All refrigerant pipe joints should be tightened with a torque wrench to the 

specified tightening torque.

Compound 

pressure gauge

Pressure 
meter

High-pressure 

valve

Gauge 
manifold

Low-pressure 

valve

Charging 

hoses

Vacuum pump

Service port

Valve caps

Liquid 
stop 
valve

Gas stop valve

1) Pressurize the liquid pipe and gas pipe from the service ports of each stop valve to 604psi (4.17MPa) (do not pressurize 

more than 604psi (4.17MPa)) for 1 hour minimum, 24 hours recommended. If there is a pressure drop, check for leaks, 

make repairs and perform the pressure test again.

2) Connect the gauge manifold’s charging hose to the gas stop valve’s service port.
3) Fully open the low-pressure valve (Lo) on the gauge manifold and fully close the high-pressure valve (Hi).

 

(High-pressure valve will require no further operation.)

4) Evacuate system using vacuum pump to below 500 microns for 1 hour minimum.
5) Close the low-pressure valve (Lo) on the gauge manifold and stop vacuum pumping.

 

(Maintain this condition for a few minutes to make sure that the compound pressure gauge pointer does not swing 

back.)*

1

6) 

Remove the valve caps from the liquid stop valve and gas stop valve.

7) To open the liquid stop valve, turn the rod of the valve 90° counter-clockwise using a hexagonal wrench.

 

Close it after 5 seconds, and check for gas leakage.

 

Using soapy water, check for gas leakage from the indoor unit’s flare and outdoor unit’s flare and valve rods.

 

After the check is complete, wipe all soapy water off.*

2

8) 

Disconnect the charging hoses from the service port for the gas stop valve, then fully open the liquid and gas stop valves. 

(Do not attempt to turn the valve rods further than they can go.)

9) Tighten the valve caps and service port caps for the liquid and gas stop valves with a torque wrench to the specified 

torques. 
Refer to 

“4. Refrigerant piping”

 on page 6 for details.

*

1

  If the compound pressure gauge pointer swings back, the refrigerant may have water content or there may be a loose 

pipe joint. 

Check all pipe joints and retighten nuts as needed, then repeat steps 3) through 5).

*

2

 

 Under no circumstances shall potential sources of ignition be used in the searching for or detection of 
refrigerant leaks.  

A halide torch (or any other detector using a naked flame) shall not be used.

 

Do not use substances containing chlorine and electronic leak detection for gas leak detection.

English

01_EN_3P686856-1.indd   8

2022/04/20   9:15:05

Summary of Contents for RXM09WVJU9

Page 1: ...ais Espa ol MODELS RXM09WVJU9 RXM12WVJU9 DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R32 Split Series Installation manual Manuel d installation Manual de instalaci n 00_CV_3P686856 1 indd 1 2022 0...

Page 2: ...lly in basements and an asphyxiation hazard could occur leading to serious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can ca...

Page 3: ...event condensation Be careful when transporting the product Do not turn off the power immediately after stopping operation Always wait for at least 5 minutes before turning off the power Otherwise wat...

Page 4: ...itioner 8 Since water will flow from the drain of the outdoor unit do not place anything under the unit which must be kept away from moisture 9 A location where flammable gas does not leak Position at...

Page 5: ...s How to remove the stop valve cover 1 Remove the screw on the stop valve cover 2 Slide the stop valve cover downward to remove it How to attach the stop valve cover 1 Insert the upper part of the sto...

Page 6: ...t is recommended to either change the orientation of the outdoor unit outlet side or use the air direction adjustment grille sold separately Outdoor Unit Installation 1 Installing the outdoor unit Whe...

Page 7: ...are tool Clutch type Clutch type Rigid type Wing nut type Imperial type A 0 0 020 inch 0 0 5mm 0 039 0 059 inch 1 0 1 5mm 0 059 0 079 inch 1 5 2 0mm Flaring 4 Refrigerant piping CAUTION Use the flare...

Page 8: ...C1220T O I D 15 32 19 32 inch 12 15mm 13 32 inch 10mm Min Liquid side O D 1 4 inch 6 4mm 1 3 16 inch 30mm or more 0 031 inch 0 8mm C1220T O I D 5 16 13 32 inch 8 10mm Use separate thermal insulation...

Page 9: ...ifold and stop vacuum pumping Maintain this condition for a few minutes to make sure that the compound pressure gauge pointer does not swing back 1 6 Remove the valve caps from the liquid stop valve a...

Page 10: ...connection to the power supply terminal block Place the round crimp style terminals on the wires up to the covered part and secure in place Round crimp style terminal Stranded wire Screw Flat washer S...

Page 11: ...ate Screws Screws Conduit mounting cover Ground This air conditioner must be grounded For grounding follow all local and state electrical codes Facility Setting cooling at low outdoor temperature WARN...

Page 12: ...1 Remove the top plate of the outdoor unit 4 screws 2 Remove the Electric wiring box cover 3 Cut the jumper J4 of the PCB inside Hook 3 places Cut the jumper J4 Electrical wiring box cover When attach...

Page 13: ...ct and press for confirmation 3 Press and select the COOL operation 4 Press to turn on the system Forced cooling operation will stop automatically after about 30 minutes To stop the operation press Tr...

Page 14: ...3P686856 1 M21B535 2205 HT The two dimensional bar code is a manufacturing code 00_CV_3P686856 1 indd 2 2022 02 15 9 41 18...

Reviews: