12

English

Pump Down Operation

In order to protect the environment, be sure to pump down when 
relocating or disposing of the unit. 

1) 

Remove the valve caps from the liquid stop valve and gas stop valve.

2) 

Begin forced cooling operation.

3) After 5 to 10 minutes, close the liquid stop valve with a hexagonal wrench.
4) 

After 2 to 3 minutes, close the gas stop valve and stop forced cooling operation.

5) 

Attach the valve caps once procedures are complete.

Liquid 
stop valve

Hexagonal 

wrench

Valve cap

Close

Gas  
stop valve

Forced cooling operation

 

„

Using the indoor unit ON/OFF switch 

Press the indoor unit ON/OFF switch for at least 5 seconds. (The operation will start.) 

•  Forced cooling operation will stop automatically after about 15 minutes. 

To stop the operation, press the indoor unit ON/OFF switch.

 

„

Using the indoor unit’s remote controller

1) 

Press 

 , 

 and 

 at the same time. 

2) 

Press 

 , select “ 

 ”, and press 

 for confirmation.

3) 

Press 

 and select the COOL operation.

4) 

Press 

 to turn on the system.

•  Forced cooling operation will stop automatically after about 30 minutes. To stop the operation, press 

 .

Trial Operation and Testing

1. 

Trial operation and testing

Refer to the installation manual for the indoor unit.

2. 

Test items

Test items

Symptom

Check

Indoor and outdoor units are installed securely.

Fall, vibration, noise

No refrigerant gas leaks.

Incomplete cooling/heating function

Refrigerant gas and liquid pipes and indoor drain hose extension are 

thermally insulated.

Water leakage

Draining line is properly installed.

Water leakage

System is properly grounded.

Electrical leakage

Only specified wires are used for all wiring, and all wires are connected 

correctly.

No operation or burn damage

Indoor or outdoor unit’s air inlet or air outlet are unobstructed.

Incomplete cooling/heating function

Stop valves are opened.

Incomplete cooling/heating function

Indoor unit properly receives remote control commands.

No operation

English

01_EN_3P686856-1.indd   12

2022/04/20   9:15:07

Summary of Contents for RXM09WVJU9

Page 1: ...ais Espa ol MODELS RXM09WVJU9 RXM12WVJU9 DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R32 Split Series Installation manual Manuel d installation Manual de instalaci n 00_CV_3P686856 1 indd 1 2022 0...

Page 2: ...lly in basements and an asphyxiation hazard could occur leading to serious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can ca...

Page 3: ...event condensation Be careful when transporting the product Do not turn off the power immediately after stopping operation Always wait for at least 5 minutes before turning off the power Otherwise wat...

Page 4: ...itioner 8 Since water will flow from the drain of the outdoor unit do not place anything under the unit which must be kept away from moisture 9 A location where flammable gas does not leak Position at...

Page 5: ...s How to remove the stop valve cover 1 Remove the screw on the stop valve cover 2 Slide the stop valve cover downward to remove it How to attach the stop valve cover 1 Insert the upper part of the sto...

Page 6: ...t is recommended to either change the orientation of the outdoor unit outlet side or use the air direction adjustment grille sold separately Outdoor Unit Installation 1 Installing the outdoor unit Whe...

Page 7: ...are tool Clutch type Clutch type Rigid type Wing nut type Imperial type A 0 0 020 inch 0 0 5mm 0 039 0 059 inch 1 0 1 5mm 0 059 0 079 inch 1 5 2 0mm Flaring 4 Refrigerant piping CAUTION Use the flare...

Page 8: ...C1220T O I D 15 32 19 32 inch 12 15mm 13 32 inch 10mm Min Liquid side O D 1 4 inch 6 4mm 1 3 16 inch 30mm or more 0 031 inch 0 8mm C1220T O I D 5 16 13 32 inch 8 10mm Use separate thermal insulation...

Page 9: ...ifold and stop vacuum pumping Maintain this condition for a few minutes to make sure that the compound pressure gauge pointer does not swing back 1 6 Remove the valve caps from the liquid stop valve a...

Page 10: ...connection to the power supply terminal block Place the round crimp style terminals on the wires up to the covered part and secure in place Round crimp style terminal Stranded wire Screw Flat washer S...

Page 11: ...ate Screws Screws Conduit mounting cover Ground This air conditioner must be grounded For grounding follow all local and state electrical codes Facility Setting cooling at low outdoor temperature WARN...

Page 12: ...1 Remove the top plate of the outdoor unit 4 screws 2 Remove the Electric wiring box cover 3 Cut the jumper J4 of the PCB inside Hook 3 places Cut the jumper J4 Electrical wiring box cover When attach...

Page 13: ...ct and press for confirmation 3 Press and select the COOL operation 4 Press to turn on the system Forced cooling operation will stop automatically after about 30 minutes To stop the operation press Tr...

Page 14: ...3P686856 1 M21B535 2205 HT The two dimensional bar code is a manufacturing code 00_CV_3P686856 1 indd 2 2022 02 15 9 41 18...

Reviews: