Wiring

WARNING

•  Do not ground units to water pipes, gas pipes, telephone wires, or lightning rods as incomplete grounding can cause a 

severe shock hazard resulting in severe injury or death. 

Additionally, grounding to gas pipes could cause a gas leak and potential explosion causing severe injury or death.

• 

Do not use tapped wires, extension cords, or starburst connections, as they may cause overheating, electric shock, or fire.

•  Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the 

terminal block.) Doing so may cause electric shock or fire.

•  The circuit must be protected with safety devices in accordance with local and national codes, i.e. a circuit breaker.
• 

Use an all-pole disconnection type circuit breaker with at least 1/8 inch (3mm) between the contact point gaps.

•  When carrying out wiring, take care not to pull at the conduit.
• 

Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.

•  Do not turn on the circuit breaker until all work is completed.

CAUTION

Precautions to be taken for power supply wiring

Recommend stranded cable for interunit wiring. Local code always supersedes recommendation.

• 

For stranded wires, make sure to use the round crimp-style terminal for 
connection to the power supply terminal block. Place the round crimp-

style terminals on the wires up to the covered part and secure in place. 

Round crimp-style 

terminal

Stranded wire

Screw

Flat washer

Screw

Screw

Flat washer

Flat washer

Good

Wrong

A

Round 

crimp-style 

terminal

Round crimp-style 

terminal

Round crimp-style 

terminal

Arrow view 

A

• 

If solid core wire must be used, be sure to curl the end of the lead. Improper work may cause heat and fire.

Good

Good

Stripping wire at terminal block

Wrong

Wrong

Strip wire end 
to this point.

Excessive strip length 

may cause electric shock 
or current leakage.

1) Strip the insulation from the wire (3/4 inch (20mm)).
2) Connect the inter-unit wires between the indoor and outdoor units so that the terminal numbers match. Tighten the 

terminal screws securely. It is recommended that a slot-head  screwdriver be used to tighten the screws. 

1

2

3

1 2 3

L

1

 L

2

GR

Recommend using AWG14, stranded and insulated 
wire for connections between indoor and outdoor units.
Local code always supersedes recommendation.

Firmly fix the wires with 

the terminal screws.

Indoor 
unit

Outdoor 

unit

Ground

Firmly fix the wires with 

the terminal screws.

Power supply 

60Hz 208-230V

15A

Follow local codes for 
wiring and safety 
devices between 
outdoor unit and power 
source.

NOTE

Take care to ensure that all wiring between indoor unit and outdoor unit has a consistent connection. Any splices can cause 
communication errors.

01_EN_3P686856-1.indd   9

2022/04/20   9:15:06

Summary of Contents for RXM09WVJU9

Page 1: ...ais Espa ol MODELS RXM09WVJU9 RXM12WVJU9 DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R32 Split Series Installation manual Manuel d installation Manual de instalaci n 00_CV_3P686856 1 indd 1 2022 0...

Page 2: ...lly in basements and an asphyxiation hazard could occur leading to serious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can ca...

Page 3: ...event condensation Be careful when transporting the product Do not turn off the power immediately after stopping operation Always wait for at least 5 minutes before turning off the power Otherwise wat...

Page 4: ...itioner 8 Since water will flow from the drain of the outdoor unit do not place anything under the unit which must be kept away from moisture 9 A location where flammable gas does not leak Position at...

Page 5: ...s How to remove the stop valve cover 1 Remove the screw on the stop valve cover 2 Slide the stop valve cover downward to remove it How to attach the stop valve cover 1 Insert the upper part of the sto...

Page 6: ...t is recommended to either change the orientation of the outdoor unit outlet side or use the air direction adjustment grille sold separately Outdoor Unit Installation 1 Installing the outdoor unit Whe...

Page 7: ...are tool Clutch type Clutch type Rigid type Wing nut type Imperial type A 0 0 020 inch 0 0 5mm 0 039 0 059 inch 1 0 1 5mm 0 059 0 079 inch 1 5 2 0mm Flaring 4 Refrigerant piping CAUTION Use the flare...

Page 8: ...C1220T O I D 15 32 19 32 inch 12 15mm 13 32 inch 10mm Min Liquid side O D 1 4 inch 6 4mm 1 3 16 inch 30mm or more 0 031 inch 0 8mm C1220T O I D 5 16 13 32 inch 8 10mm Use separate thermal insulation...

Page 9: ...ifold and stop vacuum pumping Maintain this condition for a few minutes to make sure that the compound pressure gauge pointer does not swing back 1 6 Remove the valve caps from the liquid stop valve a...

Page 10: ...connection to the power supply terminal block Place the round crimp style terminals on the wires up to the covered part and secure in place Round crimp style terminal Stranded wire Screw Flat washer S...

Page 11: ...ate Screws Screws Conduit mounting cover Ground This air conditioner must be grounded For grounding follow all local and state electrical codes Facility Setting cooling at low outdoor temperature WARN...

Page 12: ...1 Remove the top plate of the outdoor unit 4 screws 2 Remove the Electric wiring box cover 3 Cut the jumper J4 of the PCB inside Hook 3 places Cut the jumper J4 Electrical wiring box cover When attach...

Page 13: ...ct and press for confirmation 3 Press and select the COOL operation 4 Press to turn on the system Forced cooling operation will stop automatically after about 30 minutes To stop the operation press Tr...

Page 14: ...3P686856 1 M21B535 2205 HT The two dimensional bar code is a manufacturing code 00_CV_3P686856 1 indd 2 2022 02 15 9 41 18...

Reviews: