6

English

3. 

Flaring the pipe end

WARNING

• 

Do not apply mineral oil to the flare.

•  Prevent mineral oil from getting into the system as this would reduce the service life of the units.
•  Never use piping which has been used for previous installations. Only use parts which are delivered with this unit.
•  Never install a dryer to this R32 unit in order to guarantee its service life.
•  The drying material may dissolve and damage the system.
• 

Improper flaring may result in refrigerant gas leakage.

CAUTION

•  Do not reuse joints which have been used once already.

1) Cut the pipe end with a pipe cutter.
2) 

Remove burrs with the cut surface facing 

downward, so that the filings do not enter the 

pipe.

3) Put the flare nut on the pipe.
4) 

Flare the pipe.

5) Check that the flaring has been done correctly.

Cut exactly at 

right angles.

Remove 
burrs.

The flare’s inner 

surface must be 

flaw-free.

The pipe end must 

be evenly flared in a 

perfect circle.

Make sure that the 

flare nut is fitted.

When flaring, do not 
over-tighten and 

crack.

Check

Set exactly at the position shown below.

A

Die

Flare tool for  

R32 or R410A

Conventional flare tool

Clutch-type

Clutch-type 

 

(Rigid-type)

Wing-nut type 

(Imperial-type)

A

0-0.020 inch

(0-0.5mm)

0.039-0.059 inch

(1.0-1.5mm)

0.059-0.079 inch

(1.5-2.0mm)

Flaring

4. 

Refrigerant piping

CAUTION

• 

Use the flare nut fixed to the main unit. (This is to prevent the flare nut from cracking as a result of deterioration over time.)

• 

To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R32 or R410A.)

• 

Use a torque wrench when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.

• 

Align the centers of both flares and tighten the flare nuts 3 or 4 turns by hand, then tighten them fully with a spanner and a 

torque wrench.

Apply oil

Do not apply refrigeration 
oil to the outer surface.

Do not apply refrigeration 

oil to the flare nut to 

avoid tightening with 

excessive torque.

Apply refrigeration 
oil only to the inner 

surface of the flare.

Flare nut

Tighten

Torque wrench

Spanner

Piping union

Flare nut

Tightening torque

Piping connection

Flare nut

Gas side

Liquid side

3/8 inch (9.5mm)

1/4 inch (6.4mm)

24-1/8–29-1/2lbf • ft 

(32.7-39.9N • m)

10-1/2–12-3/4lbf • ft 

(14.2-17.2N • m)

Valve cap

Width across flats

7/8 inch (22mm)

16–20-1/4lbf • ft 

 

(21.6-27.4N • m)

Service port cap

8–10-7/8lbf • ft

(10.7-14.7N • m)

English

01_EN_3P686856-1.indd   6

2022/04/20   9:15:05

Summary of Contents for RXM09WVJU9

Page 1: ...ais Espa ol MODELS RXM09WVJU9 RXM12WVJU9 DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R32 Split Series Installation manual Manuel d installation Manual de instalaci n 00_CV_3P686856 1 indd 1 2022 0...

Page 2: ...lly in basements and an asphyxiation hazard could occur leading to serious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can ca...

Page 3: ...event condensation Be careful when transporting the product Do not turn off the power immediately after stopping operation Always wait for at least 5 minutes before turning off the power Otherwise wat...

Page 4: ...itioner 8 Since water will flow from the drain of the outdoor unit do not place anything under the unit which must be kept away from moisture 9 A location where flammable gas does not leak Position at...

Page 5: ...s How to remove the stop valve cover 1 Remove the screw on the stop valve cover 2 Slide the stop valve cover downward to remove it How to attach the stop valve cover 1 Insert the upper part of the sto...

Page 6: ...t is recommended to either change the orientation of the outdoor unit outlet side or use the air direction adjustment grille sold separately Outdoor Unit Installation 1 Installing the outdoor unit Whe...

Page 7: ...are tool Clutch type Clutch type Rigid type Wing nut type Imperial type A 0 0 020 inch 0 0 5mm 0 039 0 059 inch 1 0 1 5mm 0 059 0 079 inch 1 5 2 0mm Flaring 4 Refrigerant piping CAUTION Use the flare...

Page 8: ...C1220T O I D 15 32 19 32 inch 12 15mm 13 32 inch 10mm Min Liquid side O D 1 4 inch 6 4mm 1 3 16 inch 30mm or more 0 031 inch 0 8mm C1220T O I D 5 16 13 32 inch 8 10mm Use separate thermal insulation...

Page 9: ...ifold and stop vacuum pumping Maintain this condition for a few minutes to make sure that the compound pressure gauge pointer does not swing back 1 6 Remove the valve caps from the liquid stop valve a...

Page 10: ...connection to the power supply terminal block Place the round crimp style terminals on the wires up to the covered part and secure in place Round crimp style terminal Stranded wire Screw Flat washer S...

Page 11: ...ate Screws Screws Conduit mounting cover Ground This air conditioner must be grounded For grounding follow all local and state electrical codes Facility Setting cooling at low outdoor temperature WARN...

Page 12: ...1 Remove the top plate of the outdoor unit 4 screws 2 Remove the Electric wiring box cover 3 Cut the jumper J4 of the PCB inside Hook 3 places Cut the jumper J4 Electrical wiring box cover When attach...

Page 13: ...ct and press for confirmation 3 Press and select the COOL operation 4 Press to turn on the system Forced cooling operation will stop automatically after about 30 minutes To stop the operation press Tr...

Page 14: ...3P686856 1 M21B535 2205 HT The two dimensional bar code is a manufacturing code 00_CV_3P686856 1 indd 2 2022 02 15 9 41 18...

Reviews: