Installation Space Requirements

•  Position the unit on a horizontal surface. Any tilt in the unit should be 3° or less to the horizontal.
• 

Where a wall or other obstacle is in the path of the outdoor unit’s intake or exhaust airflow, follow the installation space requirements 

below.

• 

For any of the below installation patterns, the wall height on the outlet side should be 47-1/4 inch (1200mm) or less.

• 

Secure as much installation space around the unit as the location allows, as more space will result in more efficient operation.

Wall facing one side

Walls facing three sides

Walls facing two sides

More than 

3-15/16 (100)

More than 

13-3/4 (350)

More than 

1-15/16 (50)

Side view

Top view

Top view

unit: inch (mm)

More than 3-15/16 (100)

More than 13-3/4 (350)

47-1/4
(1200)

or less

More than

3-15/16 (100)

More than 

13-3/4 

(350)

More than 

1-15/16 (50)

More 
than 

3-15/16 
(100)

More than 

1-15/16 (50)

More than

13-3/4 (350)

When installed as in the figure on the left, it is recommended to either 

change the orientation of the outdoor unit outlet side or use the air direction 

adjustment grille (sold separately).

Outdoor Unit Installation

1. 

Installing the outdoor unit

•  When installing the outdoor unit, refer to “

Precautions for Selecting a Location

” on page 3 and the “

Outdoor Unit 

Installation Diagram

” on page 4.

•  If drain work is necessary, follow the procedures below.

2. 

Drain work

CAUTION

• 

In cold areas, do not use a drain socket, drain caps (1, 2) and a drain hose with the outdoor unit. (Drain water may freeze, 
impairing heating performance.)

• 

If the drain port is covered by a mounting base or floor 
surface, place additional foot bases of at least 1-1/4 
inch (30mm) in height under the outdoor unit’s feet.

1) 

Attach 

B

 drain cap (1) and 

C

 drain cap (2).

2) 

Attach 

A

 drain socket.

•  When attaching 

A

 drain socket to the bottom 

frame, make sure to connect the drain hose to the 

drain socket first.

A  Drain socket

A  Drain socket

Bottom frame

Hose (available commercially, 

inner dia. 5/8” (16mm))

Bottom frame

Drain cap

Pinch the bottom 
frame in.

C  Drain cap (2)

C  Drain cap (2)

B

 Drain cap (1)

Air outlet side

01_EN_3P686856-1.indd   5

2022/04/20   9:15:05

Summary of Contents for RXM09WVJU9

Page 1: ...ais Espa ol MODELS RXM09WVJU9 RXM12WVJU9 DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R32 Split Series Installation manual Manuel d installation Manual de instalaci n 00_CV_3P686856 1 indd 1 2022 0...

Page 2: ...lly in basements and an asphyxiation hazard could occur leading to serious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can ca...

Page 3: ...event condensation Be careful when transporting the product Do not turn off the power immediately after stopping operation Always wait for at least 5 minutes before turning off the power Otherwise wat...

Page 4: ...itioner 8 Since water will flow from the drain of the outdoor unit do not place anything under the unit which must be kept away from moisture 9 A location where flammable gas does not leak Position at...

Page 5: ...s How to remove the stop valve cover 1 Remove the screw on the stop valve cover 2 Slide the stop valve cover downward to remove it How to attach the stop valve cover 1 Insert the upper part of the sto...

Page 6: ...t is recommended to either change the orientation of the outdoor unit outlet side or use the air direction adjustment grille sold separately Outdoor Unit Installation 1 Installing the outdoor unit Whe...

Page 7: ...are tool Clutch type Clutch type Rigid type Wing nut type Imperial type A 0 0 020 inch 0 0 5mm 0 039 0 059 inch 1 0 1 5mm 0 059 0 079 inch 1 5 2 0mm Flaring 4 Refrigerant piping CAUTION Use the flare...

Page 8: ...C1220T O I D 15 32 19 32 inch 12 15mm 13 32 inch 10mm Min Liquid side O D 1 4 inch 6 4mm 1 3 16 inch 30mm or more 0 031 inch 0 8mm C1220T O I D 5 16 13 32 inch 8 10mm Use separate thermal insulation...

Page 9: ...ifold and stop vacuum pumping Maintain this condition for a few minutes to make sure that the compound pressure gauge pointer does not swing back 1 6 Remove the valve caps from the liquid stop valve a...

Page 10: ...connection to the power supply terminal block Place the round crimp style terminals on the wires up to the covered part and secure in place Round crimp style terminal Stranded wire Screw Flat washer S...

Page 11: ...ate Screws Screws Conduit mounting cover Ground This air conditioner must be grounded For grounding follow all local and state electrical codes Facility Setting cooling at low outdoor temperature WARN...

Page 12: ...1 Remove the top plate of the outdoor unit 4 screws 2 Remove the Electric wiring box cover 3 Cut the jumper J4 of the PCB inside Hook 3 places Cut the jumper J4 Electrical wiring box cover When attach...

Page 13: ...ct and press for confirmation 3 Press and select the COOL operation 4 Press to turn on the system Forced cooling operation will stop automatically after about 30 minutes To stop the operation press Tr...

Page 14: ...3P686856 1 M21B535 2205 HT The two dimensional bar code is a manufacturing code 00_CV_3P686856 1 indd 2 2022 02 15 9 41 18...

Reviews: