English

3. 

Flaring the pipe end

WARNING

• 

Do not apply mineral oil to the flare.

•  Prevent mineral oil from getting into the system as this would reduce the service life of the units.
•  Never use piping which has been used for previous installations. Only use parts which are delivered with this unit.
•  Never install a dryer to this R410A unit in order to guarantee its service life.
•  The drying material may dissolve and damage the system.
• 

Incomplete flaring may result in refrigerant gas leakage.

CAUTION

•  Do not reuse joints which have been used once already.

1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing 

downward, so that the filings do not enter the 

pipe.

3) 

Put the flare nut on the pipe.

4) Flare the pipe.
5) 

Check that the flaring has been done correctly.

Check

The flare

s inner 

surface must be 
flaw-free.

When flaring, do 
not over-tighten 
and crack.

The pipe end must 
be evenly flared in 
a perfect circle.

Make sure that the 
flare nut is fitted.

Set exactly at the position shown below.

Flaring

A

Die

A

0-0.020 inch 

(0-0.5mm)

Clutch-type

Flare tool for R410A

0.039-0.059 inch 

(1.0-1.5mm)

Clutch-type (Rigid-type)

0.059-0.079 inch 

(1.5-2.0mm)

Wing-nut type (Imperial-type)

Conventional flare tool

Cut exactly at 
right angles.

 Remove burrs.

4. 

Refrigerant piping

CAUTION

• 

Use the flare nut fixed to the main unit. (This is to prevent the flare nut from cracking as a result of deterioration over time.)

• 

To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R410A.)

• 

Use a torque wrench when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.

• 

Align the centers of both flares and tighten the flare nuts 3 or 4 turns by hand, then tighten them fully with a spanner and a 

torque wrench.

Do not apply refrigeration 
oil to the outer surface.

Flare nut

Apply refrigeration  
oil only to the inner 

surface of the flare.

Do not apply refrigeration oil to 

the flare nut to avoid tightening 
with excessive torque.

Apply oil

T

orque wrench

Piping union

Flare nut

Spanner

Tighten

English

01_EN_3P572321-4B.indd   6

2019/10/17   14:46:59

Summary of Contents for RXL18UMVJUA

Page 1: ...is Espa ol MODELS RXL18UMVJU RXL24UMVJU RXL18UMVJUA RXL24UMVJUA DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series Installation manual Manuel dinstallation Manual de instalaci n Manuel...

Page 2: ...tion hazard could occur leading to serious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can cause a severe shock hazard result...

Page 3: ...getting into the system b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet radiation R410A can contribut...

Page 4: ...n the life of the air conditioner 8 Since water will flow from the drain of the outdoor unit do not place under the unit anything which must be kept away from moisture NOTE Cannot be installed suspend...

Page 5: ...3m in order to avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur depending on how the unit is installed and the environment in which it is used 10ft 3m O D 5 8 i...

Page 6: ...orientation of the outdoor unit outlet side or use the air direction adjustment grille sold separately Outdoor Unit Installation 1 Installing the outdoor unit When installing the outdoor unit refer to...

Page 7: ...le Make sure that the are nut is tted Set exactly at the position shown below Flaring A Die A 0 0 020 inch 0 0 5mm Clutch type Flare tool for R410A 0 039 0 059 inch 1 0 1 5mm Clutch type Rigid type 0...

Page 8: ...n Gas side Piping size O D 5 8 inch 15 9mm O D 1 4 inch 6 4mm 1 15 16 inch 50mm or more 1 3 16 inch 30mm or more 0 039 inch 1 0mm C1220T O 0 031 inch 0 8mm C1220T O I D 5 8 13 16 inch 16 20mm I D 5 16...

Page 9: ...alve 7 To open the liquid stop valve turn the rod of the valve 90 counter clockwise using a hexagonal wrench Close it after 5 seconds and check for gas leakage Using soapy water check for gas leakage...

Page 10: ...ound crimp style terminal Screw A Arrow view A When connecting the inter unit wires to the terminal block using a single core wire be sure to curl the end of the lead Improper work may cause heat and...

Page 11: ...nd off when using facility settings Do not place humidifiers or other items which might raise the humidity in rooms where facility settings are being used A humidifier might cause dew condensation fro...

Page 12: ...ation For FDMQ models Using the indoor unit s remote controller For wired remote controller 1 Set to COOL operation using the remote controller 2 Press and hold the Cancel button for 4 seconds or long...

Page 13: ...stop the operation press Trial Operation and Testing When trial operation is conducted directly after the circuit breaker is turned on in some cases no air will be output for about 15 minutes in orde...

Page 14: ...Two dimensional bar code is a manufacturing code 3P572321 4B M19B231 1912 HT...

Reviews: