Precautions on Installation

•  Check the strength and level of the installation surface so that the unit does not cause 

any operating vibrations or noise after installation.

• 

Fix the unit in place securely using foundation bolts, as in the figure. (Prepare 4 

sets of 5/16 inch (M8) or 3/8 inch (M10) foundation bolts, nuts and washers; all sold 
separately.)

•  It is best to screw in the foundation bolts until their ends are 3/4 inch (20mm) from the 

foundation surface.

3/4” (20mm)

Outdoor Unit Installation Diagram

Refrigerant piping must be protected from 
physical damage.
Install a plastic cover or equivalent.

In sites with poor drainage, 

use block bases for the 

outdoor unit.  

Adjust foot height until the unit 

is level. Otherwise, water 

leakage or pooling of water 

may occur.

Gas pipe

Liquid pipe

O.D. 1/4 inch (6.4mm)

0.32oz/ft (30g/m)

Max. allowable piping length

Max. allowable piping height
Additional refrigerant required for refrigerant 
pipe exceeding 32.8ft (10m) in length.

   *Be sure to add the proper amount of additional refrigerant.

Failure to do so may result in reduced performance.  

**The suggested shortest pipe length is 10ft (3m), in order to avoid 

noise from the outdoor unit and vibration.
(Mechanical noise and vibration may occur depending on how 
the unit is installed and the environment in which it is used.)

10ft (3m)

O.D. 5/8 inch

(15.9mm)

O.D. 1/2 inch

(12.7mm)

65-5/8ft (20m)

98-1/2ft (30m)

Min. allowable piping length

(Foot bolt-hole centers)

(From unit’s side)

**

*

Allow 11-13/16” (300mm) 
of work space below the 
ceiling surface.

9-13/16” (250mm) from wall

How to remove the stop 

valve cover

1) Remove the screw on the 

stop valve cover.

2) Slide the stop valve cover 

downward to remove it.

1) Insert the upper part of 

the stop valve cover into  

the outdoor unit.

2) Tighten the screw.

How to attach the stop 

valve cover

Stop valve cover

CAUTION

Keep the piping length between 
10ft (3m) and 98-1/2ft (30m). 

Wrap the insulation pipe with 

finishing tape from bottom to 

top.

Allow space for piping 

and electrical servicing.

4-15/16 inch 

(125mm)

RXL18

RXL24

If strong wind blows into the air 
discharge side from the front and 
there is a danger that the fan may be 
damaged, change the orientation of 
the air discharge side of the outdoor 
unit or use an air direction adjustment 
grille (sold separately).

If there is a danger of the unit falling or overturning, 

fix the unit with foundation bolts, or with wire or 

other means.

13-5/8 inch 

(346mm)

23-5/8 inch (600mm)

(Foot bolt-hole 

centers)

English

01_EN_3P572321-4B.indd   4

2019/10/17   14:46:58

Summary of Contents for RXL18UMVJUA

Page 1: ...is Espa ol MODELS RXL18UMVJU RXL24UMVJU RXL18UMVJUA RXL24UMVJUA DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series Installation manual Manuel dinstallation Manual de instalaci n Manuel...

Page 2: ...tion hazard could occur leading to serious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can cause a severe shock hazard result...

Page 3: ...getting into the system b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet radiation R410A can contribut...

Page 4: ...n the life of the air conditioner 8 Since water will flow from the drain of the outdoor unit do not place under the unit anything which must be kept away from moisture NOTE Cannot be installed suspend...

Page 5: ...3m in order to avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur depending on how the unit is installed and the environment in which it is used 10ft 3m O D 5 8 i...

Page 6: ...orientation of the outdoor unit outlet side or use the air direction adjustment grille sold separately Outdoor Unit Installation 1 Installing the outdoor unit When installing the outdoor unit refer to...

Page 7: ...le Make sure that the are nut is tted Set exactly at the position shown below Flaring A Die A 0 0 020 inch 0 0 5mm Clutch type Flare tool for R410A 0 039 0 059 inch 1 0 1 5mm Clutch type Rigid type 0...

Page 8: ...n Gas side Piping size O D 5 8 inch 15 9mm O D 1 4 inch 6 4mm 1 15 16 inch 50mm or more 1 3 16 inch 30mm or more 0 039 inch 1 0mm C1220T O 0 031 inch 0 8mm C1220T O I D 5 8 13 16 inch 16 20mm I D 5 16...

Page 9: ...alve 7 To open the liquid stop valve turn the rod of the valve 90 counter clockwise using a hexagonal wrench Close it after 5 seconds and check for gas leakage Using soapy water check for gas leakage...

Page 10: ...ound crimp style terminal Screw A Arrow view A When connecting the inter unit wires to the terminal block using a single core wire be sure to curl the end of the lead Improper work may cause heat and...

Page 11: ...nd off when using facility settings Do not place humidifiers or other items which might raise the humidity in rooms where facility settings are being used A humidifier might cause dew condensation fro...

Page 12: ...ation For FDMQ models Using the indoor unit s remote controller For wired remote controller 1 Set to COOL operation using the remote controller 2 Press and hold the Cancel button for 4 seconds or long...

Page 13: ...stop the operation press Trial Operation and Testing When trial operation is conducted directly after the circuit breaker is turned on in some cases no air will be output for about 15 minutes in orde...

Page 14: ...Two dimensional bar code is a manufacturing code 3P572321 4B M19B231 1912 HT...

Reviews: