When attaching the drain pan heater

1) Attach the drain pan heater in accordance with the installation manual included with the drain pan heater.
2) Turn on SW6-1 on the PCB.

PCB

HEAT

COOL

4

3

2

1

6

5

E

D

C

B

A

ON

OFF

6

5

SW6

1

2

Turn on switch 1

Screw

Remove 
the switch 
cover

Pump Down Operation

In order to protect the environment, be sure to pump down when relocating or disposing of the unit. 

1) Remove the valve cap from the liquid stop valve and gas stop valve.
2) Begin forced cooling operation.
3) 

After 5 to 10 minutes, close the liquid stop valve with a hexagonal wrench.

4) After 2 to 3 minutes, close the gas stop valve and stop forced cooling operation.
5) Attach the valve cap once procedures are complete.

Gas 
stop valve

Valve cap

Hexagonal 
wrench

Close

Liquid 
stop valve

Service port

Forced cooling operation

[For FDMQ models]

 

„

Using the indoor unit’s remote controller

[For wired remote controller]

1) Set to COOL operation using the remote controller.
2) 

Press and hold the Cancel button for 4 seconds or longer. 

 

Service settings menu is displayed.

3) Select 

 Test Operation 

 in the service settings menu, and press 

the Menu/OK button. Basic screen returns and “Test Operation” is 
displayed at the bottom.

4) 

Press the On/Off button within 10 seconds, and the forced cooling 

operation starts.

•  Forced cooling operation will stop automatically after about 15 

minutes. To stop the operation, press the On/Off button.

Basic screen

1)
2)

Cool

Return

Clean the filter

Set to

Cool

68

F

Press and hold the Cancel 
button for 4 seconds or 
longer during backlight lit. 

Service Settings 

menu screen

3)

Setting

1/3

Service Settings

Test Operation

Maintenance Contact
Field Settings
Energy Saving Options
Prohibit Buttons
Min Setpoints Differential

Press the Menu/OK button.

4)

Set temperature

80

°F

Cool

Test Operation

Press the On/Off button 
(within 10 seconds).

01_EN_3P572321-4B.indd   11

2019/10/17   14:47:00

Summary of Contents for RXL18UMVJUA

Page 1: ...is Espa ol MODELS RXL18UMVJU RXL24UMVJU RXL18UMVJUA RXL24UMVJUA DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series Installation manual Manuel dinstallation Manual de instalaci n Manuel...

Page 2: ...tion hazard could occur leading to serious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can cause a severe shock hazard result...

Page 3: ...getting into the system b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet radiation R410A can contribut...

Page 4: ...n the life of the air conditioner 8 Since water will flow from the drain of the outdoor unit do not place under the unit anything which must be kept away from moisture NOTE Cannot be installed suspend...

Page 5: ...3m in order to avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur depending on how the unit is installed and the environment in which it is used 10ft 3m O D 5 8 i...

Page 6: ...orientation of the outdoor unit outlet side or use the air direction adjustment grille sold separately Outdoor Unit Installation 1 Installing the outdoor unit When installing the outdoor unit refer to...

Page 7: ...le Make sure that the are nut is tted Set exactly at the position shown below Flaring A Die A 0 0 020 inch 0 0 5mm Clutch type Flare tool for R410A 0 039 0 059 inch 1 0 1 5mm Clutch type Rigid type 0...

Page 8: ...n Gas side Piping size O D 5 8 inch 15 9mm O D 1 4 inch 6 4mm 1 15 16 inch 50mm or more 1 3 16 inch 30mm or more 0 039 inch 1 0mm C1220T O 0 031 inch 0 8mm C1220T O I D 5 8 13 16 inch 16 20mm I D 5 16...

Page 9: ...alve 7 To open the liquid stop valve turn the rod of the valve 90 counter clockwise using a hexagonal wrench Close it after 5 seconds and check for gas leakage Using soapy water check for gas leakage...

Page 10: ...ound crimp style terminal Screw A Arrow view A When connecting the inter unit wires to the terminal block using a single core wire be sure to curl the end of the lead Improper work may cause heat and...

Page 11: ...nd off when using facility settings Do not place humidifiers or other items which might raise the humidity in rooms where facility settings are being used A humidifier might cause dew condensation fro...

Page 12: ...ation For FDMQ models Using the indoor unit s remote controller For wired remote controller 1 Set to COOL operation using the remote controller 2 Press and hold the Cancel button for 4 seconds or long...

Page 13: ...stop the operation press Trial Operation and Testing When trial operation is conducted directly after the circuit breaker is turned on in some cases no air will be output for about 15 minutes in orde...

Page 14: ...Two dimensional bar code is a manufacturing code 3P572321 4B M19B231 1912 HT...

Reviews: