English

Installation Space Requirements

•  Position the unit on a horizontal surface.  

Any tilt in the unit should be 3° or less to the horizontal.

• 

Where a wall or other obstacle is in the path of the outdoor unit’s intake or exhaust airflow, follow the installation space 

requirements below.

•  For any of the below installation patterns, the wall height on the outlet side should be 47-1/4 inch (1200mm) or less.

More than

3-15/16 (100)

More than

13-3/4 (350)

Walls facing three sides

More than 3-15/16 (100)

More than 13-3/4 (350)

More than 

1-15/16 (50)

Wall facing one side

More than 

3-15/16 (100)

More than

13-3/4 (350)

Side view

47-1/4

(1200)

or less

Top view

More than 

1-15/16 (50)

More 

than 

3-15/16 

(100)

Walls facing two sides

More than 

1-15/16 (50)

More than 

13-3/4 

(350)

Top view

unit: inch (mm)

When installed as in the figure on the left, it is recommended to either 

change the orientation of the outdoor unit outlet side or use the air direction 
adjustment grille (sold separately).

Outdoor Unit Installation

1. 

Installing the outdoor unit

•  When installing the outdoor unit, refer to “

Precautions for Selecting a Location

” and the “

Outdoor Unit Installation 

Diagram

”.

•  If drain work is necessary, follow the procedures in “

2. Drain work

”.

2. 

Drain work

CAUTION

•  In cold areas, do not use a drain socket, drain caps (1,2) and a drain hose with the outdoor unit. (Drain water may freeze, 

impairing heating performance.)

• 

If the drain port is covered by a mounting base or floor 

surface, place additional foot bases of at least 1-1/4 
inch (30mm) in height under the outdoor unit’s feet.

1) Attach 

C

 drain cap (1) and 

D

 drain cap (2).

2) Attach 

B

 drain socket.

•  When attaching 

B

 drain socket to the bottom 

frame, make sure to connect the drain hose to the 

drain socket first.

Bottom frame

Drain cap

Pinch the bottom 
frame in.

Drain cap (1)

Drain cap (2)

D

Drain cap (2)

Air outlet side

B

Drain 
socket

C

D

Bottom frame

 Drain socket

Hose (available commercially,
inner dia. 5/8 ” (16mm))

B

01_EN_3P572321-4B.indd   5

2019/10/17   14:46:58

Summary of Contents for RXL18UMVJUA

Page 1: ...is Espa ol MODELS RXL18UMVJU RXL24UMVJU RXL18UMVJUA RXL24UMVJUA DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series Installation manual Manuel dinstallation Manual de instalaci n Manuel...

Page 2: ...tion hazard could occur leading to serious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can cause a severe shock hazard result...

Page 3: ...getting into the system b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet radiation R410A can contribut...

Page 4: ...n the life of the air conditioner 8 Since water will flow from the drain of the outdoor unit do not place under the unit anything which must be kept away from moisture NOTE Cannot be installed suspend...

Page 5: ...3m in order to avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur depending on how the unit is installed and the environment in which it is used 10ft 3m O D 5 8 i...

Page 6: ...orientation of the outdoor unit outlet side or use the air direction adjustment grille sold separately Outdoor Unit Installation 1 Installing the outdoor unit When installing the outdoor unit refer to...

Page 7: ...le Make sure that the are nut is tted Set exactly at the position shown below Flaring A Die A 0 0 020 inch 0 0 5mm Clutch type Flare tool for R410A 0 039 0 059 inch 1 0 1 5mm Clutch type Rigid type 0...

Page 8: ...n Gas side Piping size O D 5 8 inch 15 9mm O D 1 4 inch 6 4mm 1 15 16 inch 50mm or more 1 3 16 inch 30mm or more 0 039 inch 1 0mm C1220T O 0 031 inch 0 8mm C1220T O I D 5 8 13 16 inch 16 20mm I D 5 16...

Page 9: ...alve 7 To open the liquid stop valve turn the rod of the valve 90 counter clockwise using a hexagonal wrench Close it after 5 seconds and check for gas leakage Using soapy water check for gas leakage...

Page 10: ...ound crimp style terminal Screw A Arrow view A When connecting the inter unit wires to the terminal block using a single core wire be sure to curl the end of the lead Improper work may cause heat and...

Page 11: ...nd off when using facility settings Do not place humidifiers or other items which might raise the humidity in rooms where facility settings are being used A humidifier might cause dew condensation fro...

Page 12: ...ation For FDMQ models Using the indoor unit s remote controller For wired remote controller 1 Set to COOL operation using the remote controller 2 Press and hold the Cancel button for 4 seconds or long...

Page 13: ...stop the operation press Trial Operation and Testing When trial operation is conducted directly after the circuit breaker is turned on in some cases no air will be output for about 15 minutes in orde...

Page 14: ...Two dimensional bar code is a manufacturing code 3P572321 4B M19B231 1912 HT...

Reviews: