9

English

Wiring

WARNING

• 

Do not use tapped wires, extension cords, or starburst connections, as they may cause overheating, electric shock, or fire.

•  Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the 

terminal block.) Doing so may cause electric shock or fire.

•  The circuit must be protected with safety devices in accordance with local and national codes, i.e. a circuit breaker.
•  Use an all-pole disconnection type circuit breaker with at least 1/8 inch (3mm) between the contact point gaps.
•  When carrying out wiring, take care not to pull at the conduit.
• 

Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.

CAUTION

Precautions to be taken for power supply wiring

•  When using stranded wires, make sure to use the round crimp-style 

terminal for connection to the power supply terminal block.

Stranded wire

Round crimp-style
terminal

Flat washer

Screw

Round 

crimp-style 

terminal

Good

Round crimp-
style terminal

Flat washer

Screw

Wrong

Flat washer

Round crimp-
style terminal

Screw

A

Arrow view 

A

•  When connecting the inter-unit wires to the terminal block using a single core wire, be sure to curl the end of the lead. 

Improper work may cause heat and fire.

Strip wire end
to this point.

Excessive strip length

may cause electric shock 

or current leakage.

Stripping wire at terminal block

Good

Wrong

Good

Wrong

•  Do not turn on the circuit breaker until all work is completed.

1) Strip the insulation from the wire (3/4 inch (20mm)).
2) Connect the inter-unit wires between the indoor and outdoor units so that the terminal numbers match. Tighten the 

terminal screws securely. It is recommended that a slot-head  screwdriver be used to tighten the screws. 

1

2

3

1 2 3

Follow local codes for wiring 

and safety devices between 

outdoor unit and power 

source.

Ground

Firmly fix the wires with 
the te

rminal screws.

Recommend using AWG14, stranded and 
insulated wire for connections between indoor and 
outdoor units.
Local code always supersedes recommendation.

Outdoor unit

Indoor 
unit

Power supply
60Hz 208-230V
20A

Firmly fix the 
wires with the 

terminal screws.

L

1

 L

2

NOTE

Take care to ensure that all wiring between indoor unit and outdoor unit has a consistent connection. Any splices can cause 
communication errors.

01_EN_3P572321-4B.indd   9

2019/10/17   14:46:59

Summary of Contents for RXL18UMVJUA

Page 1: ...is Espa ol MODELS RXL18UMVJU RXL24UMVJU RXL18UMVJUA RXL24UMVJUA DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series Installation manual Manuel dinstallation Manual de instalaci n Manuel...

Page 2: ...tion hazard could occur leading to serious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can cause a severe shock hazard result...

Page 3: ...getting into the system b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet radiation R410A can contribut...

Page 4: ...n the life of the air conditioner 8 Since water will flow from the drain of the outdoor unit do not place under the unit anything which must be kept away from moisture NOTE Cannot be installed suspend...

Page 5: ...3m in order to avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur depending on how the unit is installed and the environment in which it is used 10ft 3m O D 5 8 i...

Page 6: ...orientation of the outdoor unit outlet side or use the air direction adjustment grille sold separately Outdoor Unit Installation 1 Installing the outdoor unit When installing the outdoor unit refer to...

Page 7: ...le Make sure that the are nut is tted Set exactly at the position shown below Flaring A Die A 0 0 020 inch 0 0 5mm Clutch type Flare tool for R410A 0 039 0 059 inch 1 0 1 5mm Clutch type Rigid type 0...

Page 8: ...n Gas side Piping size O D 5 8 inch 15 9mm O D 1 4 inch 6 4mm 1 15 16 inch 50mm or more 1 3 16 inch 30mm or more 0 039 inch 1 0mm C1220T O 0 031 inch 0 8mm C1220T O I D 5 8 13 16 inch 16 20mm I D 5 16...

Page 9: ...alve 7 To open the liquid stop valve turn the rod of the valve 90 counter clockwise using a hexagonal wrench Close it after 5 seconds and check for gas leakage Using soapy water check for gas leakage...

Page 10: ...ound crimp style terminal Screw A Arrow view A When connecting the inter unit wires to the terminal block using a single core wire be sure to curl the end of the lead Improper work may cause heat and...

Page 11: ...nd off when using facility settings Do not place humidifiers or other items which might raise the humidity in rooms where facility settings are being used A humidifier might cause dew condensation fro...

Page 12: ...ation For FDMQ models Using the indoor unit s remote controller For wired remote controller 1 Set to COOL operation using the remote controller 2 Press and hold the Cancel button for 4 seconds or long...

Page 13: ...stop the operation press Trial Operation and Testing When trial operation is conducted directly after the circuit breaker is turned on in some cases no air will be output for about 15 minutes in orde...

Page 14: ...Two dimensional bar code is a manufacturing code 3P572321 4B M19B231 1912 HT...

Reviews: