Field Setting from Condensing Unit
SiUS30-1301
122
Field Setting
Detailed Setting Procedure and Demand Control
1. Setting mode 1 (H1P OFF)
(1) In setting mode 2, press the BS1 (MODE button) once.
Setting mode 1 is entered and H1P lights OFF.
During the setting mode 1 is displayed, “In demand control” is displayed.
2. Setting mode 2 (H1P ON)
(1) In setting 1, press the BS1 (MODE button) for 5 seconds or more.
Setting mode 2 is entered and H1P ON.
(2) Press the BS2 (SET button) several times and match the LED display with the setting No. you want.
(3) Press the BS3 (RETURN button) once, and the present setting content is displayed.
Press the BS2 (SET button) several times and match the LED display with the setting content (as shown below) you
want.
(4) Press the BS3 (RETURN button) twice.
Returns to (1).
(5) Press the BS1 (MODE button) once.
Returns to the setting mode 1 and turns H1P OFF.
(1)
(2)
(3)
k
: ON
h
: OFF
l
: BLINK
Setting
No.
Setting
Contents
Setting No. indication
Setting No. indication
Setting
contents
Setting contents indication (Initial setting)
H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
H1P H2P H3P H4P H5P H6P H7P
12
Demand
setting
NO (Factory
setting)
l
YES
l
30
Demand
setting 1
60
%
of
rated power
consumption
l
70
%
of
rated power
consumption
(Factory
setting)
l
80
%
of
rated power
consumption
l
32
Normal
demand
setting
OFF
(Factory
setting)
l
Continuous
demand 1
fixed
l
Setting mode indication section
Setting No. indication section
Set contents indication section