Field Setting from Remote Controller
SiUS30-1301
98
Field Setting
In the Case of FXFQ36
Airflow Direction Setting
Set the airflow direction of indoor units as given in the table below. (Set when optional air outlet blocking pad has been
installed.) The second code No. is factory setting to “01.”
Setting of Airflow Direction Adjustment Range
Make the following airflow direction setting according to the respective purpose.
Some indoor unit models are not equipped with draft prevention (upward) function.
Setting of the Static Pressure Selection (for FXDQ model)
Setting of Humidifier / Air Purifier Fan Tap (for FXTQ model)
Residual Operation Time (for FXTQ model)
Mode No.
First code
No.
Second
code No.
Setting
Ceiling height
4-way Outlets 3-way Outlets 2-way Outlets
13 (23)
0
01
Standard (N)
Lower than
10-1/2 ft
Lower than
11-12/18 ft
Lower than
13-25/32 ft
02
High Ceiling (H)
Lower than
11-12/18 ft
Lower than
13-1/8 ft
Lower than
13-25/32 ft
03
Higher Ceiling (S)
Lower than
13-25/32 ft
Lower than
13-25/32 ft
—
Mode No.
First Code No.
Second Code No.
Setting
13 (23)
1
01
F: 4-direction airflow
02
T: 3-direction airflow
03
W: 2-direction airflow
Mode No.
First Code No.
Second Code No.
Setting
13 (23)
4
01
Upward (Draft prevention)
02
Standard
03
Downward (Ceiling soiling prevention)
Model No.
First Code No.
Second Code No.
External static pressure
13 (23)
5
01
Standard (0.002 psi)
02
High static pressure (0.006 psi)
Mode No.
First Code No.
Second Code No.
Setting
14 (24)
4
01
Remote controller setting
02
H tap
Mode No.
First Code No.
Second Code No.
Setting
14 (24)
5
01
30 seconds
02
60 seconds
03
120 seconds