Field Setting from Remote Controller
SiUS30-1301
100
Field Setting
2.4.3 Centralized Control Group No. Setting
BRC1E Type
In order to conduct the centralized remote control using the central remote controller and the unified ON/OFF controller,
Group No. settings should be made by group using the operating remote controller.
Make Group No. settings for centralized remote control using the operating remote controller.
Note:
For wireless remote controller, see the following.
For setting group No. of Heat reclaim ventilator and wiring adaptor for other air conditioners, etc., refer to the installation
manual attached.
NOTICE
Enter the group No. and installation place of the indoor unit into the attached installation table. Be sure to keep the
installation table with the operation manual for maintenance.
(1) <Basic screen>
1.
Press and hold Cancel button for 4 seconds or more.
Service Settings menu in displayed.
(2) <Service Settings menu screen>
2.
Select
, and press Menu/OK button.
Group Address screen is displayed.
(3) <Group Address>
3.
Select Group Address (Group), and press Menu/OK button.
Group Address (Group) screen is displayed.
(3) <Group Address (Group)>
4.
Select the group No. by using
(Up/Down) button.
Press Menu/OK button.
Group Address