SiUS30-1301
Field Setting from Condensing Unit
Field Setting
125
Procedures for charging additional refrigerant.
Additional refrigerant charge procedure (2)-by Additional refrigerant charge operation
About the system settings for additional refrigerant charge operation, refer to the [Service Precaution] label attached on the
Electrical Components Box lid in the condensing unit.
1. Fully open all stop valves (valve A and valve B must be left fully closed).
2. After 10 minutes, fully close liquid line stop valve and then,open the valve by turning 180°.
Start the additional refrigerant charge operation.
See [Service precautions] Label for detail.
If it is difficult to charge the refrigerant additionally, decrease the water temperature or warm the refrigerant tank.
(Warm the refrigerant tank with a stupe or a warm hot water of 40 degrees or less.)
3. After the system is charged with a specified amount of refrigerant, press the RETURN button (BS3) on the PCB (A1P) in
the condensing unit to stop the additional refrigerant charge operation.
4. Immediately open both liquid-side and gas-side stop valve.
(If do not open the stop valve immediately, liquid seal may cause the pipe to burst.)
Stop valve operation procedure
Do not open the stop valve until checking of device and installation conditions are completed. If the stop valve is left open
without turning on power, it may cause refrigerant to buildup in the compressor, leading to insulation degradation.
Opening stop valve
1. Remove the cap and turn the valve counterclockwise with the hexagon wrench (JISB4648).
2. Turn it until the shaft stops.
Do not apply excessive force to the stop valve. Doing so may break the valve body, as the valve is not a backseat type.
Always use the hexagon wrench.
3. Make sure to tighten the cap securely.
[Heat Pump system]
[Heat Recovery system]
Press
u
re
red
u
cing
v
al
v
e
N
itrogen
N
itrogen
Close
Close
R-410A
Close
Close
R-410A
Meas
u
ring instr
u
ment
Press
u
re
red
u
cing
v
al
v
e
Refrigerant
tank
W
ith
a siphon
Meas
u
ring instr
u
ment
Refrigerant
tank
W
ith
a siphon
Gas side
Charge hose
Charge hose
Discharge
gas side
V
al
v
e A
V
al
v
e A
V
al
v
e B
V
ac
uu
m p
u
mp
V
ac
uu
m p
u
mp
To Indoor
u
nit
Condensing
u
nit
Condensing
u
nit
To Indoor
u
nits /
Branch Selector
u
nits
Li
qu
id
side
Li
qu
id
side
S
u
ction
gas side
Condensing
u
nit
Stop
v
al
v
e ser
v
ice port
Dotted lines represent
onsite piping
Condensing
u
nit
Stop
v
al
v
e ser
v
ice port
Dotted lines represent
onsite piping
Caution