background image

16

English

2.

After the vacuum drying is finished, charge the additional refrigerant 
in its liquid state through the liquid pipe stop valve service port. Tak-
ing into account following instructions:

Check that gas and liquid pipe stop valves are closed.

Stop the compressor and charge the specified weight of refriger-
ant.

(If the outside unit is not in operation and the total amount cannot be 
charged, follow the Additional refrigerant charge procedure (2) 
shown below.)

NOTE

Procedures for charging additional refrigerant.

(Refer to figure 24)

1.

Pressure reducing valve

2.

Nitrogen

3.

Refrigerant tank

4.

With a siphon

5.

Measuring instrument

6.

Vacuum pump

7.

Valve A

8.

Valve B

9.

Charge hose

10.

Outside unit

11.

Gas side

12.

Liquid side

13.

Discharge gas side

14.

Suction gas side

15.

Stop valve service port

16.

To indoor unit

17.

To indoor units / Branch Selector units

18.

Dotted lines represent onsite piping

Additional refrigerant charge procedure (2)-by Additional refriger-
ant charge operation

To learn the system settings for additional refrigerant charging, refer to 
the [Service Precautions] label attached on the back of the control box 
cover in the outside unit.

1.

Fully open all stop valves (valve A and valve B must be left
fully closed).

2.

After ten minutes, fully close liquid pipe stop valve and then, open 
the valve by turning 180°.
Start the additional refrigerant charge operation.
See [Service Precautions] label for detail.
If it is difficult to charge the refrigerant additionally, decrease the 
water temperature or warm the refrigerant tank.
(Warm the refrigerant tank with a stupe or a warm hot water of 
104°F (40°C) or less.)

3.

After the system is charged with a specified amount of refrigerant, 
press the RETURN button (BS3) on the printed circuit board (A1P) 
in the outside unit to stop the additional refrigerant charge operation.

4.

Immediately open both liquid and gas pipe stop valve.
(If the stop valve is not opened immediately, liquid seal may 
cause the pipes to burst.)

NOTE

If the refrigerant cylinder is siphonal, set it upright while charging 
additional refrigerant.

9-10 Stop valve operation procedure

CAUTION

Do not open the stop valve until 1-6 of “9-8 Checking of device and 
installation conditions” are completed. If the stop valve is left open 
without turning on power supply, it may cause refrigerant to buildup 
in the compressor, leading to insulation degradation.

Opening stop valve

1.

Remove the cap and turn the valve counterclockwise with the hexa-
gon wrench.

2.

Turn it until the shaft stops.
Do not apply excessive force to the stop valve. Doing so may break 
the valve body, as the valve is not a backseat type. Always use the 
special tool.

3.

Make sure to tighten the cap securely.

Closing stop valve

1.

Remove the cap and turn the valve clockwise with the hexagon 
wrench.

2.

Securely tighten the valve until the shaft contacts the main body 
seal.

3.

Make sure to tighten the cap securely.

∗ 

For the tightening torque, refer to the table on the below.

Tightening torque

(Refer to figure 25)

 

1.

Service port

2.

Cap

3.

Hexagon hole

4.

Shaft

5.

The main body seal

Caution

• Do not damage the cap sealing.
• Always use a charge hose for service port connection.
• After tightening the cap, check that no refrigerant leaks are present.
• After working, securely tighten the cover of service port without fail 

by specified torque.

• When loosening a flare nut, always use two wrenches in combina-

tion. When connecting the piping, always use a spanner and torque 
wrench in combination to tighten the flare nut.

• When connecting a flare nut, coat the flare (inner and outer faces) 

with ether oil or ester oil and hand-tighten the nut 3 to 4 turns as the 
initial tightening.

• Do not forget to open the stop valve before starting operation.

 

(Refer to figure 26)

1.

Remove the cap and turn the valve counterclockwise with 
the hexagon wrenches until it stops.

2.

Discharge gas side

3.

Liquid side

4.

Suction gas side

5.

Never remove the partition flange for any reason.

6.

Full close on the suction gas side

Stop 

valve size

Tightening torque (ft.·lbf. (N·m)) (Turn clockwise to close)

Shaft

(valve body)

Cap 

(valve 

cover)

Service port Flare nut

Gas side 

accessory 

pipe (1)

Liquid 

side

3.98-4.87

(5.4-6.6)

Hexagonal 

wrench 

1/8 in. (4 mm)

9.95-12.17

(13.5-16.5)

8.48-10.25

(11.5-13.9)

24.1-29.4

(32.7-39.9)

_

Gas 

side

19.91-24.33

(27-33)

Hexagonal 

wrench 

3/8 in. (10 mm)

26.54-32.44

(36-44)

8.48-10.25

(11.5-13.9)

_

16.22-20.65

(22-28)

01_EN_3P365916_17C.fm  Page 16  Thursday, March 12, 2015  10:47 AM

Summary of Contents for RWEYQ72PCYD

Page 1: ...ion Keep this manual in a handy place for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant I installation Concerver ce manuel port e de ma...

Page 2: ...100 9 13 16 250 21 5 8 550 30 11 16 780 9 9 5 5 8 10 8 9 7 7 6 6 6 9 7 5 8 5 8 15 3 8 390 4 3 1 2 11 13 16 300 39 3 8 1000 35 7 16 900 19 11 16 500 Unit in mm 1 2 3 4 4 9 3 5 3 4 8 5 6 6 9 7 1 2 3 4...

Page 3: ...2 Q1 Q2 A1P F1 F2 F1 F2 Q1 Q2 A B C C H SELECTOR A5P 12 A B C C H SELECTOR A5P A B C A B C RWEYQ PCYD figure 10 A B C A B C F1 F1 F2 F2 Q1 Q2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 4 5...

Page 4: ...1 Q2 Q1 Q2 Q1 Q2 A1P A5P 1 4 8 9 5 6 6 6 2 3 RWEYQ PCYD A B C 7 1 4 5 2 3 3 4 3 X2M X1M F1 F2 F1 F2 Q1 Q2 X3M A1P A5P 1 2 RWEYQ PCYD A B C figure 13 figure 12 figure 11 A B C F1 F2 F1 F2 Q1 Q2 Q1 Q2 Q...

Page 5: ...em Heat recovery system 1 2 3 4 5 6 7 8 9 10 11 5 4 12 14 15 16 17 13 figure 17 A B C A B C 1 2 DS1 1 2 3 4 OFF ON O U T I N A1P A5P RWEYQ PCYD A B C A B C 1 DS1 1 2 3 4 OFF ON O U T I N A1P RWEYQ PCT...

Page 6: ...system 4 5 3 2 1 figure 24 1 11 1 2 2 4 3 4 3 5 5 R410A R410A 9 7 7 8 13 9 6 6 16 10 10 10 10 17 12 12 14 15 15 18 18 Heat pump system Heat recovery system 1 2 3 4 figure 26 figure 27 figure 23 1 15...

Page 7: ...d to alert against unsafe practices NOTE Indicates situations that may result in equipment or property damage accidents only DANGER Refrigerant gas is heavier than air and replaces oxygen A massive le...

Page 8: ...r Refrigerant Pip ing and follow the procedures Since R410A is a blend the required additional refrigerant must be charged in its liquid state If the refrigerant is charged in a state of gas its compo...

Page 9: ...5 F 20 35 C Water flow rate 15 9gpm 60L min or more During cooling operation when the outside temperature is very low it is possible that the thermostat switches off automatically in order to protect...

Page 10: ...ead Drain pipe in 1 2FPS 2 female Thread 1 2FPS 2 female Thread General RWEYQ216PCYD CTJ RWEYQ252PCYD CTJ Nominal cooling capacity 2 MBH 216 252 Nominal heating capacity 3 MBH 243 283 5 Nominal input...

Page 11: ...hazard could occur leading to serious injury or death Re fer to the chapter Caution for refrigerant leaks NOTE 1 An inverter air conditioner may cause electronic noise generated from AM broadcasting...

Page 12: ...water drainage channel around the foundation to con densate waste water from around the unit If the unit is to be installed on a roof check the strength of the roof and its drainage facilities first M...

Page 13: ...After the test run has been completed inspect the strainer at the inlet piping of the outside unit Clean it if it is dirty 7 3 Daily service and maintenance 1 Management of water quality The plate typ...

Page 14: ...rinse the inner part of the plate type heat exchanger with care using fresh and clean water 6 When using any cleaning agent sold in the market check in advance that such agent has no corrosive featur...

Page 15: ...re and close the cover firmly WARNING Never connect power supply wiring to the terminal block for remote controller wiring as this could damage the entire system Picking power supply and transmission...

Page 16: ...upply to transmission wiring terminal block Otherwise the entire system may break down Refer to figure 14 1 Branch 2 Subbranching For low noise operation it is necessary to get the optional Exter nal...

Page 17: ...th a non return valve 2 Make sure the pump oil does not flow oppositely into the system while the pump is not working 3 Use a vacuum pump which can evacuate to 500 microns 9 1 Selection of piping mate...

Page 18: ...ide of the flares and turn them three or four times at first Use ester oil or ether oil See the following table for tightening torque Applying too much torque may cause the flares to crack After all t...

Page 19: ...ween the outside unit connection piping kit or between the outside units exceeds 80 in 2m create a rise of 8 in 200mm or more in the gas piping within a length of 80 in 2m from the kit Pattern 1 Patte...

Page 20: ...i 23 3 lbs Total length ft m of liquid piping size at 7 8 0 235 lbs ft 0 37 N m Total length ft m of liquid piping size at 3 8 Total length ft m of liquid piping size at 1 4 Total length ft m of liqui...

Page 21: ...r unit etc this must be prevented by caulking the connections etc WARNING Be sure to insulate connection piping as touching them can cause burns 9 8 Checking of device and installation conditions Be s...

Page 22: ...alve operation procedure CAUTION Do not open the stop valve until 1 6 of 9 8 Checking of device and installation conditions are completed If the stop valve is left open without turning on power supply...

Page 23: ...ings made on a sub unit will be ignored After this close the control box cover Always perform configuration after turning ON the power supply To learn the setting method refer to the Service Precautio...

Page 24: ...Default value 3 Change 2 9 1 3 or 6 in function of required operation method during heating Malfunc tion code Installation error Remedial action E3 E4 F3 F6 UF U2 The stop valve of an out side unit i...

Page 25: ...stem containing a high sensible solution To activate this setting under heating operation change field set ting 2 9 to the appropriate value matching the requirements of the pre designed system contai...

Page 26: ...vate the mild comfort setting under heating operation change field setting 2 52 1 This setting is used in conjunction with setting 2 9 Eco The original refrigerant temperature target which is defined...

Page 27: ...imum concentration level in accordance with steps 1 to 4 below and take whatever action is necessary to comply 1 Calculate the amount of refrigerant lbs kg charged to each sys tem separately NOTE Wher...

Page 28: ...3P365916 17C EM14A009A 1503 HT...

Reviews: