13. CAUTION FOR REFRIGERANT LEAKS

DANGER

Refrigerant gas is heavier than air and replaces oxygen. A massive 
leak could lead to oxygen depletion, especially in basements, and 
an asphyxiation hazard could occur leading to serious injury or 
death.

(Points to note in connection with refrigerant leaks)

Introduction

The installer and system specialist shall secure safety against 
leakage according to local regulations or standards. The following 
standards may be applicable if local regulations are not available.

The VRV System, like other air conditioning systems, uses R410A as 
refrigerant. R410A itself is an entirely safe non-toxic, non-combustible 
refrigerant. Nevertheless care must be taken to ensure that air condi-
tioning facilities are installed in a room which is sufficiently large. This 
assures that the maximum concentration level of refrigerant gas is not 
exceeded, in the unlikely event of major leak in the system and this in 
accordance to the local applicable regulations and standards.

Maximum concentration level

The maximum charge of refrigerant and the calculation of the maximum 
concentration of refrigerant is directly related to the humanly occupied 
space in to which it could leak.

The unit of measurement of the concentration is lbs./ft.

3

 (kg/m

3

) (the 

weight in lbs. (kg) of the refrigerant gas in 1 ft.

3

 (1 m

3

) volume of the 

occupied space).

Compliance to the local applicable regulations and standards for the 
maximum allowable concentration level is required.

1.

direction of the refrigerant flow

2.

room where refrigerant leak has occurred (outflow of all the 
refrigerant from the system)

Pay a special attention to the place, such as a basement, etc. 
where refrigerant can stay, since refrigerant is heavier than air.

Procedure for checking maximum concentration

Check the maximum concentration level in accordance with steps 1 to 4 
below and take whatever action is necessary to comply.

1.

Calculate the amount of refrigerant (lbs. (kg)) charged to each sys-
tem separately.

NOTE

Where a single refrigerant facility is divided into 2 entirely indepen-
dent refrigerant systems then use the amount of refrigerant with 
which each separate system is charged.

2.

Calculate the smallest room volume (ft.

3

 (m

3

))

In case like the following, calculate the volume of (A), (B) as a single 
room or as the smallest room.

A.

Where there are no smaller room divisions

B.

Where there is a room division but there is an opening 
between the rooms sufficiently large to permit a free flow of 
air back and forth.

1.

opening between rooms

2.

partition 

(Where there is an opening without a door or where there are open-
ings above and below the door which are each equivalent in size to 
0.15% or more of the floor area.)

3.

Calculating the refrigerant density using the results of the calcula-
tions in steps 1 and 2 above.

If the result of the above calculation exceeds the maximum concen-
tration level then make similar calculations for the second then third 
smallest room and so until the result falls short of the maximum con-
centration.

4.

Dealing with the situations where the result exceeds the maximum 
concentration level.
Where the installation of a facility results in a concentration in excess 
of the maximum concentration level then it will be necessary to 
revise the system. Please consult your Daikin supplier.

amount of refriger-
ant in a single unit 
system (amount of 
refrigerant with 
which the system 
is charged before 
leaving the factory)

+

additional charging 
amount (amount of 
refrigerant added 
locally in accordance 
with the length or 
diameter of the refrig-
erant piping)

=

total amount 
of refriger-
ant (lbs. (kg)) 
in the system

2

1

total volume of refrigerant in the 
refrigerant system

maximum concen-
tration level 

(lbs./ft.

3

 (kg/m

3

))

size (ft.

3

 

 

(m

3

)) of smallest room in 

which there is an indoor unit 
installed

1

2

01_EN_3P365916_17C.fm  Page 21  Thursday, March 12, 2015  10:47 AM

Summary of Contents for RWEYQ72PCYD

Page 1: ...ion Keep this manual in a handy place for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant I installation Concerver ce manuel port e de ma...

Page 2: ...100 9 13 16 250 21 5 8 550 30 11 16 780 9 9 5 5 8 10 8 9 7 7 6 6 6 9 7 5 8 5 8 15 3 8 390 4 3 1 2 11 13 16 300 39 3 8 1000 35 7 16 900 19 11 16 500 Unit in mm 1 2 3 4 4 9 3 5 3 4 8 5 6 6 9 7 1 2 3 4...

Page 3: ...2 Q1 Q2 A1P F1 F2 F1 F2 Q1 Q2 A B C C H SELECTOR A5P 12 A B C C H SELECTOR A5P A B C A B C RWEYQ PCYD figure 10 A B C A B C F1 F1 F2 F2 Q1 Q2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 4 5...

Page 4: ...1 Q2 Q1 Q2 Q1 Q2 A1P A5P 1 4 8 9 5 6 6 6 2 3 RWEYQ PCYD A B C 7 1 4 5 2 3 3 4 3 X2M X1M F1 F2 F1 F2 Q1 Q2 X3M A1P A5P 1 2 RWEYQ PCYD A B C figure 13 figure 12 figure 11 A B C F1 F2 F1 F2 Q1 Q2 Q1 Q2 Q...

Page 5: ...em Heat recovery system 1 2 3 4 5 6 7 8 9 10 11 5 4 12 14 15 16 17 13 figure 17 A B C A B C 1 2 DS1 1 2 3 4 OFF ON O U T I N A1P A5P RWEYQ PCYD A B C A B C 1 DS1 1 2 3 4 OFF ON O U T I N A1P RWEYQ PCT...

Page 6: ...system 4 5 3 2 1 figure 24 1 11 1 2 2 4 3 4 3 5 5 R410A R410A 9 7 7 8 13 9 6 6 16 10 10 10 10 17 12 12 14 15 15 18 18 Heat pump system Heat recovery system 1 2 3 4 figure 26 figure 27 figure 23 1 15...

Page 7: ...d to alert against unsafe practices NOTE Indicates situations that may result in equipment or property damage accidents only DANGER Refrigerant gas is heavier than air and replaces oxygen A massive le...

Page 8: ...r Refrigerant Pip ing and follow the procedures Since R410A is a blend the required additional refrigerant must be charged in its liquid state If the refrigerant is charged in a state of gas its compo...

Page 9: ...5 F 20 35 C Water flow rate 15 9gpm 60L min or more During cooling operation when the outside temperature is very low it is possible that the thermostat switches off automatically in order to protect...

Page 10: ...ead Drain pipe in 1 2FPS 2 female Thread 1 2FPS 2 female Thread General RWEYQ216PCYD CTJ RWEYQ252PCYD CTJ Nominal cooling capacity 2 MBH 216 252 Nominal heating capacity 3 MBH 243 283 5 Nominal input...

Page 11: ...hazard could occur leading to serious injury or death Re fer to the chapter Caution for refrigerant leaks NOTE 1 An inverter air conditioner may cause electronic noise generated from AM broadcasting...

Page 12: ...water drainage channel around the foundation to con densate waste water from around the unit If the unit is to be installed on a roof check the strength of the roof and its drainage facilities first M...

Page 13: ...After the test run has been completed inspect the strainer at the inlet piping of the outside unit Clean it if it is dirty 7 3 Daily service and maintenance 1 Management of water quality The plate typ...

Page 14: ...rinse the inner part of the plate type heat exchanger with care using fresh and clean water 6 When using any cleaning agent sold in the market check in advance that such agent has no corrosive featur...

Page 15: ...re and close the cover firmly WARNING Never connect power supply wiring to the terminal block for remote controller wiring as this could damage the entire system Picking power supply and transmission...

Page 16: ...upply to transmission wiring terminal block Otherwise the entire system may break down Refer to figure 14 1 Branch 2 Subbranching For low noise operation it is necessary to get the optional Exter nal...

Page 17: ...th a non return valve 2 Make sure the pump oil does not flow oppositely into the system while the pump is not working 3 Use a vacuum pump which can evacuate to 500 microns 9 1 Selection of piping mate...

Page 18: ...ide of the flares and turn them three or four times at first Use ester oil or ether oil See the following table for tightening torque Applying too much torque may cause the flares to crack After all t...

Page 19: ...ween the outside unit connection piping kit or between the outside units exceeds 80 in 2m create a rise of 8 in 200mm or more in the gas piping within a length of 80 in 2m from the kit Pattern 1 Patte...

Page 20: ...i 23 3 lbs Total length ft m of liquid piping size at 7 8 0 235 lbs ft 0 37 N m Total length ft m of liquid piping size at 3 8 Total length ft m of liquid piping size at 1 4 Total length ft m of liqui...

Page 21: ...r unit etc this must be prevented by caulking the connections etc WARNING Be sure to insulate connection piping as touching them can cause burns 9 8 Checking of device and installation conditions Be s...

Page 22: ...alve operation procedure CAUTION Do not open the stop valve until 1 6 of 9 8 Checking of device and installation conditions are completed If the stop valve is left open without turning on power supply...

Page 23: ...ings made on a sub unit will be ignored After this close the control box cover Always perform configuration after turning ON the power supply To learn the setting method refer to the Service Precautio...

Page 24: ...Default value 3 Change 2 9 1 3 or 6 in function of required operation method during heating Malfunc tion code Installation error Remedial action E3 E4 F3 F6 UF U2 The stop valve of an out side unit i...

Page 25: ...stem containing a high sensible solution To activate this setting under heating operation change field set ting 2 9 to the appropriate value matching the requirements of the pre designed system contai...

Page 26: ...vate the mild comfort setting under heating operation change field setting 2 52 1 This setting is used in conjunction with setting 2 9 Eco The original refrigerant temperature target which is defined...

Page 27: ...imum concentration level in accordance with steps 1 to 4 below and take whatever action is necessary to comply 1 Calculate the amount of refrigerant lbs kg charged to each sys tem separately NOTE Wher...

Page 28: ...3P365916 17C EM14A009A 1503 HT...

Reviews: