background image

English

15

9-6 Air tight test and vacuum drying

The units were checked for leaks by the manufacturer.
Confirm that the valves are firmly closed before Air tight test or vacuum 
drying.
To prevent entry of any impurities and ensure sufficient pressure resis-
tance, always use the special tools dedicated for R410A.

Air tight test:

 Make sure to use nitrogen gas.

(For the service port location, refer to the 
“Caution” label attached on the front panel 
[right] of the outside unit.)

(Refer to figure)

1.

[Service Precautions] label

2.

Control box cover

3.

[Caution] label

Pressurize the liquid and gas pipes to 
500 microns (do not pressurize more than 
500 microns). If the pressure does not drop 
within 24 hours, the system passes the test. If the pressure drops, 
check where the nitrogen leaks from.

Vacuum drying:

 Use a vacuum pump which can evacuate to 

500 microns.

1.

Evacuate the system from the liquid and gas pipes by using a 
vacuum pump for more than 2 hours and bring the system to 
500 microns or less. After keeping the system under that condi-
tion for more than 1 hour, check if the vacuum gauge rises or not. 
If it rises, the system may either contain moisture inside or have 
leaks.

2.

Following should be executed if there is a possibility of moisture 
remaining inside the pipe (if piping work is carried out during the 
raining season or over a long period of time rainwater may enter 
the pipe during work).
After evacuating the system for 2 hours, pressurize the system to 
7.25 psig (0.05 MPa) (vacuum break) with nitrogen gas and evac-
uate the system again using the vacuum pump for 1 hour to 
500 microns or less (vacuum drying). If the system cannot be 
evacuated to 500 microns within 2 hours, repeat the operation of 
vacuum break and vacuum drying.
Then, after leaving the system in vacuum for 1 hour, confirm that 
the vacuum gauge does not rise.

NOTE

Make sure to perform air tight test and vacuum drying using the service
ports of the stop valve shown in the table below.

9-7 Pipe insulation

After finishing the leak test and vacuum drying, the piping must be insu-
lated. Take into account the following points:

• Make sure to insulate the connection piping and refrigerant branch 

kits entirely. 

• Be sure to insulate the liquid-side, suction gas-side and discharge 

gas-side piping for the inter-unit piping and the refrigerant branch kits.
Not insulating them may cause leaking. (The gas piping can reach 
temperatures of 250°F (120°C). Be sure the insulation used can 
withstand such temperatures.)

• If you think the humidity around the cooling piping might exceed

86°F (30°C) and RH80%, reinforce the insulation on the cooling pip-
ing (at least 13/16 in. (20 mm) thick). Condensation might form on 
the surface of the insulation.

• If there is a possibility that condensation on the stop valve might drip 

down into the indoor unit through gaps in the insulation and piping 
because the outside unit is located higher than the indoor unit, etc., 
this must be prevented by caulking the connections, etc.

WARNING

• Be sure to insulate connection piping, as touching them can cause 

burns.

9-8 Checking of device and installation conditions

Be sure to check the followings.

1.

Make sure there is no faulty power supply wiring or loosing of a nut. 
See 

8. FIELD WIRING

.

2.

Make sure there is no faulty transmission wiring or loosing of a nut.
See 

8. FIELD WIRING

.

3.

Make sure there is no faulty refrigerant piping. 
See 

9. REFRIGERANT PIPING

.

4.

Make sure piping size is correct. 
See 

9-1 Selection of piping material

.

5.

Make sure insulation work is done. 
See 

9-7 Pipe insulation

.

6.

Make sure insulation resistance of main power supply circuit is not 
deteriorated. 
Using a megatester for 500 V, check that the insulation resistance of 
2 M

 or more is attained by applying a voltage of 500 V DC between 

power supply and ground terminals. Never use the megatester for 
the transmission wiring (between outside and indoor unit, outside 
and Cool/Heat selector and etc.).

9-9 Additional refrigerant charge

WARNING

• To avoid injury always use protective gloves and eye protection 

when charging refrigerant.

To avoid injury do not charge with unsuitable substances. Use only 
the appropriate refrigerant.

NOTE

Refrigerant cannot be charged until field wiring has been com-
pleted.
Refrigerant may only be charged after performing the leak test and
the vacuum drying (see above).
When charging a system, care shall be taken that its maximum per-
missible charge is never exceeded, in view of the danger of liquid
hammer.
Refrigerant containers shall be opened slowly.

TO AVOID COMPRESSOR BREAKDOWN. DO NOT CHARGE THE
REFRIGERANT MORE THAN THE SPECIFIED AMOUNT TO RAISE
THE CONDENSING PRESSURE.

• This outside unit is factory charged with refrigerant and depending 

on pipe sizes and pipe lengths some systems require additional 
charging of refrigerant.

• Determine the amount of refrigerant to be added by referring to the 

table, write it down on the included “Added Refrigerant” plate and 
attach it to the rear side of the front cover.
Note: refer to the example of connection for the amount to be added.

Additional refrigerant charge procedure (1)-normally

• Charge the refrigerant to the liquid pipe in its liquid state. Since 

R410A is a mixed refrigerant, its composition changes if charged in 
a state of gas and normal system operation would no longer be 
assured.

• Make sure to use installation tools you exclusively use on R410A 

installations to withstand the pressure and to prevent foreign materi-
als from mixing into the system.

1.

Before charging, check whether the tank has a siphon attached or not.

How to charge with the siphon tank.

Other ways of charging with the tank.

One outside unit installed

Liquid pipe stop valve
Discharge gas pipe stop valve
Suction gas pipe stop valve

Multiple outside units installed

Liquid pipe stop valve
Discharge gas pipe stop valve
Suction gas pipe stop valve
Oil-equalizing pipe stop valve

1

3

2

There is a siphon tube
inside, so there is no need
to turn the tank upside-down.

Charge with the tank upright.

Charge with the tank upside-down.

01_EN_3P365916_17C.fm  Page 15  Thursday, March 12, 2015  10:47 AM

Summary of Contents for RWEYQ72PCYD

Page 1: ...ion Keep this manual in a handy place for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant I installation Concerver ce manuel port e de ma...

Page 2: ...100 9 13 16 250 21 5 8 550 30 11 16 780 9 9 5 5 8 10 8 9 7 7 6 6 6 9 7 5 8 5 8 15 3 8 390 4 3 1 2 11 13 16 300 39 3 8 1000 35 7 16 900 19 11 16 500 Unit in mm 1 2 3 4 4 9 3 5 3 4 8 5 6 6 9 7 1 2 3 4...

Page 3: ...2 Q1 Q2 A1P F1 F2 F1 F2 Q1 Q2 A B C C H SELECTOR A5P 12 A B C C H SELECTOR A5P A B C A B C RWEYQ PCYD figure 10 A B C A B C F1 F1 F2 F2 Q1 Q2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 4 5...

Page 4: ...1 Q2 Q1 Q2 Q1 Q2 A1P A5P 1 4 8 9 5 6 6 6 2 3 RWEYQ PCYD A B C 7 1 4 5 2 3 3 4 3 X2M X1M F1 F2 F1 F2 Q1 Q2 X3M A1P A5P 1 2 RWEYQ PCYD A B C figure 13 figure 12 figure 11 A B C F1 F2 F1 F2 Q1 Q2 Q1 Q2 Q...

Page 5: ...em Heat recovery system 1 2 3 4 5 6 7 8 9 10 11 5 4 12 14 15 16 17 13 figure 17 A B C A B C 1 2 DS1 1 2 3 4 OFF ON O U T I N A1P A5P RWEYQ PCYD A B C A B C 1 DS1 1 2 3 4 OFF ON O U T I N A1P RWEYQ PCT...

Page 6: ...system 4 5 3 2 1 figure 24 1 11 1 2 2 4 3 4 3 5 5 R410A R410A 9 7 7 8 13 9 6 6 16 10 10 10 10 17 12 12 14 15 15 18 18 Heat pump system Heat recovery system 1 2 3 4 figure 26 figure 27 figure 23 1 15...

Page 7: ...d to alert against unsafe practices NOTE Indicates situations that may result in equipment or property damage accidents only DANGER Refrigerant gas is heavier than air and replaces oxygen A massive le...

Page 8: ...r Refrigerant Pip ing and follow the procedures Since R410A is a blend the required additional refrigerant must be charged in its liquid state If the refrigerant is charged in a state of gas its compo...

Page 9: ...5 F 20 35 C Water flow rate 15 9gpm 60L min or more During cooling operation when the outside temperature is very low it is possible that the thermostat switches off automatically in order to protect...

Page 10: ...ead Drain pipe in 1 2FPS 2 female Thread 1 2FPS 2 female Thread General RWEYQ216PCYD CTJ RWEYQ252PCYD CTJ Nominal cooling capacity 2 MBH 216 252 Nominal heating capacity 3 MBH 243 283 5 Nominal input...

Page 11: ...hazard could occur leading to serious injury or death Re fer to the chapter Caution for refrigerant leaks NOTE 1 An inverter air conditioner may cause electronic noise generated from AM broadcasting...

Page 12: ...water drainage channel around the foundation to con densate waste water from around the unit If the unit is to be installed on a roof check the strength of the roof and its drainage facilities first M...

Page 13: ...After the test run has been completed inspect the strainer at the inlet piping of the outside unit Clean it if it is dirty 7 3 Daily service and maintenance 1 Management of water quality The plate typ...

Page 14: ...rinse the inner part of the plate type heat exchanger with care using fresh and clean water 6 When using any cleaning agent sold in the market check in advance that such agent has no corrosive featur...

Page 15: ...re and close the cover firmly WARNING Never connect power supply wiring to the terminal block for remote controller wiring as this could damage the entire system Picking power supply and transmission...

Page 16: ...upply to transmission wiring terminal block Otherwise the entire system may break down Refer to figure 14 1 Branch 2 Subbranching For low noise operation it is necessary to get the optional Exter nal...

Page 17: ...th a non return valve 2 Make sure the pump oil does not flow oppositely into the system while the pump is not working 3 Use a vacuum pump which can evacuate to 500 microns 9 1 Selection of piping mate...

Page 18: ...ide of the flares and turn them three or four times at first Use ester oil or ether oil See the following table for tightening torque Applying too much torque may cause the flares to crack After all t...

Page 19: ...ween the outside unit connection piping kit or between the outside units exceeds 80 in 2m create a rise of 8 in 200mm or more in the gas piping within a length of 80 in 2m from the kit Pattern 1 Patte...

Page 20: ...i 23 3 lbs Total length ft m of liquid piping size at 7 8 0 235 lbs ft 0 37 N m Total length ft m of liquid piping size at 3 8 Total length ft m of liquid piping size at 1 4 Total length ft m of liqui...

Page 21: ...r unit etc this must be prevented by caulking the connections etc WARNING Be sure to insulate connection piping as touching them can cause burns 9 8 Checking of device and installation conditions Be s...

Page 22: ...alve operation procedure CAUTION Do not open the stop valve until 1 6 of 9 8 Checking of device and installation conditions are completed If the stop valve is left open without turning on power supply...

Page 23: ...ings made on a sub unit will be ignored After this close the control box cover Always perform configuration after turning ON the power supply To learn the setting method refer to the Service Precautio...

Page 24: ...Default value 3 Change 2 9 1 3 or 6 in function of required operation method during heating Malfunc tion code Installation error Remedial action E3 E4 F3 F6 UF U2 The stop valve of an out side unit i...

Page 25: ...stem containing a high sensible solution To activate this setting under heating operation change field set ting 2 9 to the appropriate value matching the requirements of the pre designed system contai...

Page 26: ...vate the mild comfort setting under heating operation change field setting 2 52 1 This setting is used in conjunction with setting 2 9 Eco The original refrigerant temperature target which is defined...

Page 27: ...imum concentration level in accordance with steps 1 to 4 below and take whatever action is necessary to comply 1 Calculate the amount of refrigerant lbs kg charged to each sys tem separately NOTE Wher...

Page 28: ...3P365916 17C EM14A009A 1503 HT...

Reviews: