Precautions on electrical wiring work

Before obtaining access to terminal devices, all supply circuits
must be interrupted. 

Use only copper wires.

The wiring between the indoor unit and outdoor unit must be for
230 V.

Do not turn on the main switch until all the wiring is completed.
Make sure that the main switch has a contact separation of at
least 3 mm in all poles.

For W1
Make sure to connect power supply cables in normal phase. If
connected in reverse phase, the remote controller of the indoor
unit indicates "U1" and the equipment cannot operate. Change
any two of the three power supply cables (L1, L2, L3) to correct
phase.
If the contact in the magnetic switch should be forcibly turned on
while the equipment is inoperative, the compressor will burn out.
Never try to forcibly turn on the contact.

Never squeeze bundled cables into a unit.

Fix cables so that cables do not make contact with the pipes
(especially on high pressure side).

Secure the electrical wiring with clamping material as shown in
the figure below so that it does not come in contact with the
piping, particulary on the high-pressure side.
Make sure no external pressure is applied to the terminal
connectors.

Secure the wiring in the order shown below.

1

Secure the ground wire to the shut-off valve attachment plate so
that it does not slide.

2

Secure the ground wire to the shut-off valve attachment plate
one more time along with the electric wiring and the inter-unit
wiring.

Lay the electrical wiring so that the front cover does not rise up
when doing wiring work and attach the front cover securely.

1

Switch box

2

Stop valve mounting plate

3

Ground

4

Power supply and ground wiring

5

Wiring between units

6

Tie-wrap 

When cables are routed from the unit, a protection sleeve for the
conduits (PG-insertions) can be inserted at the knock-out hole.

(See figure 6)

1

Wire

2

Bush

3

Nut

4

Frame

5

Hose

A

Inside

B

Outside

When you do not use a wire conduit, be sure to protect the wires
with vinyl tubes to prevent the edge of the knock-out hole from
cutting the wires.

Follow the electric wiring diagram for electrical wiring works.

Form the wires and fix the cover firmly so that the cover may be
fit in properly.

Precautions on wiring of power supply and inter-unit 
wiring

Use a round crimp-style terminal for
connection to the power supply
terminal board. In case it cannot be
used due to unavoidable reasons,
be sure to observe the following
instruction.
-

Do not connect wires of different gauge to the same power 
supply terminal. (Looseness in the connection may cause 
overheating.)

-

When connecting wires of the same gauge, connect them 
according to the figure below.

Use the correct screwdriver to tighten the terminal screws.
Small screwdrivers can damage the screw head and prevent
appropriate tightening.

Over-tightening the terminal screws can damage the screws.

See the table below for tightening torques for the terminal
screws.

Refer to the installation manual attached to the indoor unit for
wiring of indoor units, etc.

Attach an earth leak detector and fuse to the power supply line.

(See figure 8)

In wiring, make certain that prescribed wires are used, carry out
complete connections, and fix the wires so that outside forces
are not applied to the terminals.

1

5

4

6

2

3

V3-type

W1-type

Tightening torque (N•m)

M4

(X1M)

1.2~1.8

M5

(X1M)

2.0~3.0

M5

(EARTH)

3.0~4.0

I

Pair

II

Twin

III

Triple

M

Master

S

Slave

1

Earth leak detector

2

Fuse

3

Remote controller

Summary of Contents for RQ100B7V3B

Page 1: ...INSTALLATION MANUAL RR71B7V3B RR100B7V3B RR71B7W1B RR100B7W1B RR125B7W1B RQ71B7V3B RQ100B7V3B RQ71B7W1B RQ100B7W1B RQ125B7W1B Split System air conditioners...

Page 2: ...1 1 2 4 5 2 4 5 9 7 6 6 8 3 3 1 3 2 4 5 A B A E B C D H H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B2 C C D1...

Page 3: ...zate n conformitate cu instruc iunile noastre 19 skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili 20 on vastavuses j rgmis t e standardi te...

Page 4: ...m not exceeding the limit please consult with your distributor If the leaked amount exceeds the limit it may cause an oxygen deficiency accident Be sure to use only the specified accessories and parts...

Page 5: ...ning conductor or telephone earth wire Incomplete grounding may cause electric shocks Gas pipe Ignition or explosion may occur if the gas leaks Water pipe Hard vinyl tubes are not effective grounds Li...

Page 6: ...a foundation of concrete blocks etc the height of the foundation should be maximum 150 mm 5 If you install the unit on a frame please install a waterproof plate within 150 mm of the underside of the...

Page 7: ...omply with relevant local and national regulations The minimal pipe thickness for R 410A piping must be in accordance with the table below O Annealed 1 2H Half hard Suction side obstacle Obstacle is p...

Page 8: ...g cure the piping with a pinch or taping Great caution is needed when passing copper tubes through walls In case of simultanious operating system Upward and downward piping should be performed at the...

Page 9: ...only a torque wrench is used when loosening or tightening flare nuts always lock the shut off valve with a wrench and then use a torque wrench Do not place wrenches on the valve cover Do not apply fo...

Page 10: ...e and outside and first screw the nut 3 or 4 turns by hand Coat here with ether or ester oil After completing the installation carry out a gas leak inspection of the piping connections with nitrogen a...

Page 11: ...t 4 Weighing machine 5 Vacuum pump 6 Stop valve 7 Main pipe 8 Branched pipes 9 Pipe branching kit optional 1 Evacuate the pipes and check vacuum 1 No pressure increase for 1 minute 1 Use a 2 stage vac...

Page 12: ...uming can not be executed completely using such port Position of service port Heat pump Heat pump units have 2 ports on the piping One between the liquid receiver and the electronic expansion valve an...

Page 13: ...cover securely 1 Switch box 2 Stop valve mounting plate 3 Ground 4 Power supply and ground wiring 5 Wiring between units 6 Tie wrap When cables are routed from the unit a protection sleeve for the co...

Page 14: ...appens turn off the power re check the wiring and switch the position of two of the three electrical wires If operation is not possible do not under any circumstances force the electromagnetic contact...

Page 15: ...circuit R1T Thermistor air R2T Thermistor coil R3T Thermistor discharge RC Signal receiver circuit S1PH Pressure switch HIGH S1PL Pressure switch LOW SD Safety devices input T1A Transformer 220 240 V...

Page 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWEN19370 1C...

Reviews: