Installation manual

11

RR+RQ71+10 RR+RQ71~125B7W1B

Split System air conditioners

4PW19370-1C

Specifications of standard wiring components

T

EST

 

OPERATION

Be sure to fully open the liquid-side and gas-side stop valves.

For details on test operation, refer to the indoor unit installation
manual.

Pre-run checks

Test run

1

Make sure the liquid and gas shut-off valves are open.

Be sure to close the frontside panel before operation, as not
doing so can cause electric shock.
-

The refrigerant pressure may not rise, even if the shut-off 
valve is opened after an air purge is performed using a 
vacuum pump.
This is because the indoor unit refrigerant piping is closed off
with electric valves inside. This will not create any problems
during operation.

2

Be sure to set it to cooling and press the operation switch.

3

Press the inspection/test-run switch on the remote control to put
the machine into test-run mode.

4

Make sure the compressor is not starting and stopping during
the test-run by listening. If it is starting and stopping,
immediately stop the machine using the remote controller, and
check the refrigerant level, etc. There may be some sort of
malfunction.

5

At first test-run of the unit, the valves are checked if they are not
closed. Therefore the unit starts in cooling mode (even if the
remote controller is set to heating mode) for about 2-3 minutes
and then switches automatically to heating mode. The remote
controller will always display heating mode.

Precautions regarding test-runs

If the remote control shows E0, E3 or E4 as an error code, there
is a possibility that either the shut-off valve is closed, or the
outlet vent is closed.

For a reverse phase in case of W1 units, U1 will be displayed on
the remote controller of the indoor unit. 
For a missing phase in case of W1 units, E0 or E6 will be
displayed on the remote controller of the indoor unit.
Operation will be impossible with either one of these
phenomena. If this happens, turn off the power, re-check the
wiring and switch the position of two of the three electrical wires.
(If operation is not possible, do not under any circumstances
force the electromagnetic contactor on.)

If the error code E6 is displayed on the remote contoller, check
for voltage imbalance.

If the error code U4 or UF is displayed on the remote contoller,
check the inter-unit branch wiring connection.

Diagnosis

On the remote controller LCD
If the machine stops due to some malfunction, you can diagnose
the problem using the error code displayed on the remote
controller.

-

The malfunction code should be looked up in the installation 
manual for the indoor unit.

-

Depending on the indoor unit or outdoor unit type, error 
codes may not be displayed.

D

ISPOSAL

 

REQUIREMENTS

Dismantling of the unit, treatment of the refrigerant, oil and any other
parts should be done in accordance with the relevant local and
national regulations.

Power supply

Model

Field 

fuse 

Wire type

(1)

(1) Only in protected pipes, use H07RN-F when protected pipes are not used.

Size

Wire type 

of wiring 

between the 

units

RR71B7V3B

32 A

H05VV-U3G

Wiring size 

must comply 

with the 

applicable 

local and 

national code

H05VV-U4G2.5

RQ71B7V3B

RR100B7V3B

40 A

RQ100B7V3B

RR71B7W1B

16 A

H05VV-U5G

RQ71B7W1B

RR100B7W1B

RQ100B7W1B

RR125B7W1B

20 A

RQ125B7W1B

Items to check

Electrical wiring
Inter-unit wiring
Ground wire

Is the wiring as mentioned on the wiring
diagram?
Make sure no wiring has been forgotten and that
there are no missing phases or reverse phases.

Is the unit properly grounded?

Are any of the wiring attachment screws loose?

Refrigerant piping

Is the size of the piping appropriate?

Is the insulation material for the piping attached
securely?
Are both the liquid and gas pipes insulated?

Are the shut-off valves for both the liquid side and
the gas side open?

Extra refrigerant

Did you write down the extra refrigerant and the
refrigerant piping length?

 Opening direction

A

Liquid side

B

Gas side

Remove the cap and turn 
counterclockwise with a 
hex wrench until it stops

A

B

Error code

Description

E6

Compressor current overload

J2

Electric current sensor malfunction

Summary of Contents for RQ100B7V3B

Page 1: ...INSTALLATION MANUAL RR71B7V3B RR100B7V3B RR71B7W1B RR100B7W1B RR125B7W1B RQ71B7V3B RQ100B7V3B RQ71B7W1B RQ100B7W1B RQ125B7W1B Split System air conditioners...

Page 2: ...1 1 2 4 5 2 4 5 9 7 6 6 8 3 3 1 3 2 4 5 A B A E B C D H H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B2 C C D1...

Page 3: ...zate n conformitate cu instruc iunile noastre 19 skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili 20 on vastavuses j rgmis t e standardi te...

Page 4: ...m not exceeding the limit please consult with your distributor If the leaked amount exceeds the limit it may cause an oxygen deficiency accident Be sure to use only the specified accessories and parts...

Page 5: ...ning conductor or telephone earth wire Incomplete grounding may cause electric shocks Gas pipe Ignition or explosion may occur if the gas leaks Water pipe Hard vinyl tubes are not effective grounds Li...

Page 6: ...a foundation of concrete blocks etc the height of the foundation should be maximum 150 mm 5 If you install the unit on a frame please install a waterproof plate within 150 mm of the underside of the...

Page 7: ...omply with relevant local and national regulations The minimal pipe thickness for R 410A piping must be in accordance with the table below O Annealed 1 2H Half hard Suction side obstacle Obstacle is p...

Page 8: ...g cure the piping with a pinch or taping Great caution is needed when passing copper tubes through walls In case of simultanious operating system Upward and downward piping should be performed at the...

Page 9: ...only a torque wrench is used when loosening or tightening flare nuts always lock the shut off valve with a wrench and then use a torque wrench Do not place wrenches on the valve cover Do not apply fo...

Page 10: ...e and outside and first screw the nut 3 or 4 turns by hand Coat here with ether or ester oil After completing the installation carry out a gas leak inspection of the piping connections with nitrogen a...

Page 11: ...t 4 Weighing machine 5 Vacuum pump 6 Stop valve 7 Main pipe 8 Branched pipes 9 Pipe branching kit optional 1 Evacuate the pipes and check vacuum 1 No pressure increase for 1 minute 1 Use a 2 stage vac...

Page 12: ...uming can not be executed completely using such port Position of service port Heat pump Heat pump units have 2 ports on the piping One between the liquid receiver and the electronic expansion valve an...

Page 13: ...cover securely 1 Switch box 2 Stop valve mounting plate 3 Ground 4 Power supply and ground wiring 5 Wiring between units 6 Tie wrap When cables are routed from the unit a protection sleeve for the co...

Page 14: ...appens turn off the power re check the wiring and switch the position of two of the three electrical wires If operation is not possible do not under any circumstances force the electromagnetic contact...

Page 15: ...circuit R1T Thermistor air R2T Thermistor coil R3T Thermistor discharge RC Signal receiver circuit S1PH Pressure switch HIGH S1PL Pressure switch LOW SD Safety devices input T1A Transformer 220 240 V...

Page 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWEN19370 1C...

Reviews: