background image

4

Remarks:

Front connection:

Make sure to close the piping intake hole again after
installation work.

Bottom Connection:

Remove the knock out hole by drilling the 2 concave recesses
with a Ø 6mm drill (see figure). Afterwards, paint the edges to
avoid rusting.

A Knock out hole
B Drill
C Concave recess

Liquid side:
Provide a liquid side pipe (field supply), and
connect it to the stop valve. Take care not to
allow it to touch the gas side pipe.

Gas side:
Cut the gas side accessory pipe and make connection using
an elbow (field supply).

A = cutting position

Operating stop valve: refer to figure 7

To open:

1. Remove the cap (1) and turn the shaft (2) counterclockwise

with hexagon socket screw keys.

2. Turn it all the way until the shaft stops.
3. Tighten the cap firmly.

To close:

1. Remove the cap and turn the shaft clockwise.
2. Tighten the shaft firmly until it reaches the sealed area (4) of

the body.

3. Tighten the cap firmly.

Note

-

Refer to the table for stop valve tightening torques.

-

Be sure to use both a spanner and a torque wrench when
connecting or disconnecting pipes to or from the unit.

-

Use a charging hose with push rod when using the service
port (5).

-

Check for refrigerant gas leakage after tightening the cap.

-

Make sure to keep the valve open during operation.

Precautions for connecting pipes

When the outdoor unit is installed above the indoor unit the
following can occur:

1. The condensated water on the stop valve can move to the

indoor unit. To avoid this, please cover the stop valve with
sealing material.

2. If the temperature is higher than 30

°

C and the humidity is

higher than RH 80%, then the thickness of the sealing
materials should be at least 20mm in order to avoid
condensation on the surface of the sealing.

Please refer to the table for the dimensions for processing
flares and for the tightening torques. (Too much tightening will
end up in splitting of the flare.)

When connecting the flare nut, coat the flare both inside and
outside with refrigerant oil (R22), ether or ester oil (R407C)
and initially tighten by hand before tightening firmly.

Make sure to flow nitrogen gas through the pipe when
brazing.

Great caution is needed when passing copper tubes through
walls.

In case of simultaneous operation system

Upward and downward piping should be performed at the
main piping line.

Use branch piping kit (optional) for branching refrigerant
pipes.

Precautions to be taken. (For details, refer to the manual
attached to branch piping kit.)

*1. Install the branch pipes horizontally (Maximum inclination:

20 degrees or less)

*2. Length of branch pipe to the indoor unit should be as short

as possible.

*3. Try to keep lengths of both branch pipes to the indoor unit

equal.

±

100mm

±

167mm

A

Stop valve tightening torques

R(Y)(P)200

R(Y)(P)250

980~1470 N•cm (100~150 kgf•cm)

1960~2450 N•cm

2940~3430 N•cm

(200~250 kgf.cm)

(300~350 kgf.cm)

Service port (5)

Valve cap (1)

Liquid pipe

Gas pipe

3920~4410 N•cm (400~450 kgf.cm)

R=0.4~0.8

45

° ±

2

90

°±

0.5

A

A dimensions for

processing flares (mm)

Flare nut tightening torque

Piping size

Flare shape

3270~3990 N•cm

(333~407 kgf•cm)

6180~7540 N•cm

(630~770 kgf•cm)

9720~11860 N•cm

(989.8~1208 kgf•cm)

12.0 ~ 12.4

18.6 ~ 19.0

22.9 ~ 23.3

Ø 9.5

Ø 15.9

Ø 19.1

Application of refrigerant oil
(for R407C ether or ester oil should be used)

Take measures against contamination when installing pipes.
Prevent foreign materials like moisture and other impurities
from mixing into the system.

Protection method

More than a month

Pinch the pipe

Outdoor unit

Indoor

Less than a month

Regardless of the period

Pinch or tape the pipe

Place

Installation period

4950~6030 N•cm

(504~616 kgf•cm)

15.4 ~ 15.8

Ø 12.7

Summary of Contents for RP200B7W1

Page 1: ...English Split System air conditioners INSTALLATION MANUAL Installation manual Split System air conditioners R200F7W1 R250F7W1 RY200F7W1 RY250F7W1 RP200B7W1 RP250B7W1 RYP200B7W1 RYP250B7W1...

Page 2: ...ljer f ljande standard er eller andra normgivande dokument under f ruts ttning att anv ndning sker i verensst mmelse med v ra instruktioner respektive utstyr er i overensstemmelse med f lgende standar...

Page 3: ...H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 1 2 3 4 6 H1 L1 H1 H2 L7 L1 L6 L5 L4 L3 L2 5 B A C E D H 7 5 1 2 3 4...

Page 4: ...1 5 4 A B 2 3 9 11 3 2 1 3 2 1 P2 P1 3 2 1 P2 P1 3 2 1 P2 P1 3N 50Hz 400V L3 N N L3 L2 L1 L1 L2 l ll lll M S S 1 2 3 3 2 1 P2 P1 S 3 1 2 4 5 5 3 8 R22 R407C 6 5 4 2 1 3 R22 R407C 8 6 5 4 2 1 3 9 7 A...

Page 5: ...e R407C is a mixed refrigerant the required additional refrigerant must be charged in its liquid state If the refrigerant is in state of gas its composition changes and the system will not work proper...

Page 6: ...he unit 3 If you install the unit on a frame please install a waterproof plate within 150mm of the underside of the unit in order to prevent the invasion of water from the lower direction 4 When insta...

Page 7: ...liquid oil hammer the oil circulation will decrease To solve these phenomena provide oil traps in the gas pipe every 15m if the level difference H is more than 15m See figure 6 A outdoor unit B indoor...

Page 8: ...rface of the sealing Please refer to the table for the dimensions for processing flares and for the tightening torques Too much tightening will end up in splitting of the flare When connecting the fla...

Page 9: ...or 1 minute 2 Break the vacuum with a minimum of 2 bar of nitrogen 3 Conduct leak test by applying soap water etc to the connect ing part of the pipes 4 Discharge Nitrogen 5 Evacuate and check vacuum...

Page 10: ...en ON button on the remote controller is pressed and it will not operate Turn off the main power supply switch and turn it on again in need of operation ELECTRICAL WIRING WORK All wiring must be perfo...

Page 11: ...OW DO NOT OPERATE THE UNIT BY SHORT CIRCUITING S1LP USE COPPER CONDUCTORS ONLY L1 RED L2 WHITE L3 BLACK N BLUE A1P A2P PRINTED CIRCUIT BOARD BS1 PUSH BUTTON FORCED DEFROST PUMP DOWN C1R C2R CAPACITOR...

Page 12: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW10932 1A...

Reviews: