Installation manual

R(Y)200F7W1
R(Y)250F7W1
R(Y)P200B7W1
R(Y)P250B7W1

Before installation ..................................................................... 1

Selecting installation site .......................................................... 2

Precautions on installation ....................................................... 2

Installation servicing space ...................................................... 2

Refrigerant pipe size and allowable pipe length ...................... 3

Precautions on refrigerant piping ............................................. 3

Evacuating ................................................................................ 5

Charging refrigerant ................................................................. 5

Electrical wiring work ................................................................ 6

Test operation ........................................................................... 7

Disposal requirements .............................................................. 7

Wiring diagram ......................................................................... 7

READ THESE INSTRUCTIONS CAREFULLY BEFORE
INSTALLATION. KEEP THIS MANUAL IN A HANDY PLACE
FOR FUTURE REFERENCE.
IMPROPER INSTALLATION OR ATTACHMENT OF EQUIP-
MENT OR ACCESSORIES COULD RESULT IN ELECTRIC
SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR OTHER
DAMAGE TO THE EQUIPMENT. BE SURE ONLY TO USE
ACCESSORIES MADE BY DAIKIN WHICH ARE SPECIFIC-
ALLY DESIGNED FOR USE WITH THE EQUIPMENT AND
HAVE THEM INSTALLED BY A PROFESSIONAL.
IF UNSURE OF INSTALLATION PROCEDURES OR USE,
ALWAYS CONTACT YOUR DAIKIN DEALER FOR ADVICE
AND INFORMATION.

B

EFORE

 

INSTALLATION

Precautions

For R407C units only

The new refrigerant requires strict cautions for keeping the
system clean, dry and tight.
a. Clean and dry.
Foreign materials (including mineral oils or moisture) should
be prevented from getting mixed into the system.
b. Tight.
Read the chapter ‘Precautions on refrigerant piping’ carefully
and follow these procedures correctly.
Since design pressure is 3.3MPa or 33bar (for R22 units
3.0MPA or 30bar), pipes of larger wall thickness may be
required.

Since R407C is a mixed refrigerant, the required additional
refrigerant must be charged in its liquid state. (If the
refrigerant is in state of gas, its composition changes and the
system will not work properly).

The connected indoor units must be indoor units designed
exclusively for R407C. If indoor units for R22 are connected,
normal operation cannot be assured.

page

Split System air conditioners

Installation

For installation of the indoor unit(s), refer to the indoor unit
installation manual.

This outdoor unit requires the pipe branching kit (optional)
when used as the outdoor unit for the simultaneous operation
system. Refer to catalogues for details.

Never operate the unit without the thermistor (R3T), burning
of the compressor may result.

When closing the service panels, take care that the tightening
torque does not exceed 4.1Nm.

Accessories

Check if the following accessories (gas pipes) are included with
your unit.

Handling

The units are packed in a wooden crate and attached on a
wooden pallet.
At delivery, the package should be checked and any damage
should be reported immediately to the carrier claims agent.
When handling the unit, take into account the following:

1.

Fragile, handle the unit with care.

Keep the unit upright in order to avoid compressor
damage.

2. Lift the unit preferably with a crane and 2 belts (1) of at least

8m long.

3. When lifting the unit with a crane, always use protectors (2)

to prevent belt damage and pay attention to the position of the
unit’s centre of gravity.

4. Bring the unit as close to its final installation position in its

original package to prevent damage during transport.

2

1

Summary of Contents for RP200B7W1

Page 1: ...English Split System air conditioners INSTALLATION MANUAL Installation manual Split System air conditioners R200F7W1 R250F7W1 RY200F7W1 RY250F7W1 RP200B7W1 RP250B7W1 RYP200B7W1 RYP250B7W1...

Page 2: ...ljer f ljande standard er eller andra normgivande dokument under f ruts ttning att anv ndning sker i verensst mmelse med v ra instruktioner respektive utstyr er i overensstemmelse med f lgende standar...

Page 3: ...H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 1 2 3 4 6 H1 L1 H1 H2 L7 L1 L6 L5 L4 L3 L2 5 B A C E D H 7 5 1 2 3 4...

Page 4: ...1 5 4 A B 2 3 9 11 3 2 1 3 2 1 P2 P1 3 2 1 P2 P1 3 2 1 P2 P1 3N 50Hz 400V L3 N N L3 L2 L1 L1 L2 l ll lll M S S 1 2 3 3 2 1 P2 P1 S 3 1 2 4 5 5 3 8 R22 R407C 6 5 4 2 1 3 R22 R407C 8 6 5 4 2 1 3 9 7 A...

Page 5: ...e R407C is a mixed refrigerant the required additional refrigerant must be charged in its liquid state If the refrigerant is in state of gas its composition changes and the system will not work proper...

Page 6: ...he unit 3 If you install the unit on a frame please install a waterproof plate within 150mm of the underside of the unit in order to prevent the invasion of water from the lower direction 4 When insta...

Page 7: ...liquid oil hammer the oil circulation will decrease To solve these phenomena provide oil traps in the gas pipe every 15m if the level difference H is more than 15m See figure 6 A outdoor unit B indoor...

Page 8: ...rface of the sealing Please refer to the table for the dimensions for processing flares and for the tightening torques Too much tightening will end up in splitting of the flare When connecting the fla...

Page 9: ...or 1 minute 2 Break the vacuum with a minimum of 2 bar of nitrogen 3 Conduct leak test by applying soap water etc to the connect ing part of the pipes 4 Discharge Nitrogen 5 Evacuate and check vacuum...

Page 10: ...en ON button on the remote controller is pressed and it will not operate Turn off the main power supply switch and turn it on again in need of operation ELECTRICAL WIRING WORK All wiring must be perfo...

Page 11: ...OW DO NOT OPERATE THE UNIT BY SHORT CIRCUITING S1LP USE COPPER CONDUCTORS ONLY L1 RED L2 WHITE L3 BLACK N BLUE A1P A2P PRINTED CIRCUIT BOARD BS1 PUSH BUTTON FORCED DEFROST PUMP DOWN C1R C2R CAPACITOR...