2
S
ELECTING
INSTALLATION
SITE
1. Select an installation site where the following conditions are
satisfied and that meets with your customer’s approval.
•
Places which are well-ventilated.
•
Places where the unit does not bother next-door neighbours.
•
Safe places which can withstand the unit’s weight and
vibration and where the unit can be installed level.
•
Places where there is no possibility of flammable gas or
product leak.
•
Places where servicing space can be well ensured.
•
Places where the indoor and outdoor units’ piping and
wiring lengths come within the allowable ranges.
•
Places where water leaking from the unit cannot cause
damage to the location (e.g. in case of a blocked drain
pipe).
Precautions
•
Do not install or operate the unit in rooms mentioned below.
a. Where mineral oil like cutting oil is present.
b. Where the air contains high levels of salt such as that near
the ocean.
c. Where sulphurous gas is present such as that in areas of
hot spring.
d. Where voltage fluctuates a lot such as that in factories.
e. In vehicles or vessels.
f. Where high concentrations of oil vapour or spray are
present such as that in kitchens.
g. Where machines generating electromagnetic waves are
present.
h. Where acidic or alkaline vapour is present.
2. Prepare a water drainage channel around the foundation, to
drain waste water from around the unit.
3. If you install the unit on a frame, please install a waterproof
plate within 150mm of the underside of the unit in order to
prevent the invasion of water from the lower direction.
4. When installing the unit in a place frequently exposed to
snow, pay special attention to the following:
•
Elevate the foundation as high as possible.
•
Remove the rear suction grille to prevent snow from accu-
mulating on the rear fins.
5. If you install the unit on a building frame, please install a
waterproof plate (within 150mm of the underside of the unit)
in order to avoid the drainwater dripping. (See figure).
P
RECAUTIONS
ON
INSTALLATION
•
Check the strength and level of the installation ground so that
the unit will not cause any operating vibration or noise after
installation.
•
Unpacking and placing the unit
a) Remove the wooden crate from the unit.
b) Remove the 4 screws fixing the unit to the pallet.
c) The unit must be installed on a solid longitudinal founda-
tion (steelbeam frame or concrete). Maximum height of the
foundation is 150mm.
d) Lift the unit from the pallet and place it on its installation
position.
•
In accordance with the foundation drawing in the figure, fix the
unit securely by means of the foundation bolts. (Prepare four
sets of M12 foundation bolts, nuts and washers each which
are available on the market.)
•
It is best to screw in the foundation bolts until their length are
20mm from the foundation surface.
I
NSTALLATION
SERVICING
SPACE
Refer to figure 1 for the required dimensions (mm). Choose one
of the 2 possibilities.