background image

2

S

ELECTING

 

INSTALLATION

 

SITE

1. Select an installation site where the following conditions are

satisfied and that meets with your customer’s approval.

Places which are well-ventilated.

Places where the unit does not bother next-door neighbours.

Safe places which can withstand the unit’s weight and
vibration and where the unit can be installed level.

Places where there is no possibility of flammable gas or
product leak.

Places where servicing space can be well ensured.

Places where the indoor and outdoor units’ piping and
wiring lengths come within the allowable ranges.

Places where water leaking from the unit cannot cause
damage to the location (e.g. in case of a blocked drain
pipe).

Precautions

Do not install or operate the unit in rooms mentioned below.

a. Where mineral oil like cutting oil is present.
b. Where the air contains high levels of salt such as that near

the ocean.

c. Where sulphurous gas is present such as that in areas of

hot spring.

d. Where voltage fluctuates a lot such as that in factories.
e. In vehicles or vessels.
f. Where high concentrations of oil vapour or spray are

present such as that in kitchens.

g. Where machines generating electromagnetic waves are

present.

h. Where acidic or alkaline vapour is present.

2. Prepare a water drainage channel around the foundation, to

drain waste water from around the unit.

3. If you install the unit on a frame, please install a waterproof

plate within 150mm of the underside of the unit in order to
prevent the invasion of water from the lower direction.

4. When installing the unit in a place frequently exposed to

snow, pay special attention to the following:

Elevate the foundation as high as possible.

Remove the rear suction grille to prevent snow from accu-
mulating on the rear fins.

5. If you install the unit on a building frame, please install a

waterproof plate (within 150mm of the underside of the unit)
in order to avoid the drainwater dripping. (See figure).

P

RECAUTIONS

 

ON

 

INSTALLATION

Check the strength and level of the installation ground so that
the unit will not cause any operating vibration or noise after
installation.

Unpacking and placing the unit
a) Remove the wooden crate from the unit.
b) Remove the 4 screws fixing the unit to the pallet.
c) The unit must be installed on a solid longitudinal founda-

tion (steelbeam frame or concrete). Maximum height of the
foundation is 150mm.

d) Lift the unit from the pallet and place it on its installation

position.

In accordance with the foundation drawing in the figure, fix the
unit securely by means of the foundation bolts. (Prepare four
sets of M12 foundation bolts, nuts and washers each which
are available on the market.)

It is best to screw in the foundation bolts until their length are
20mm from the foundation surface.

I

NSTALLATION

 

SERVICING

 

SPACE

Refer to figure 1 for the required dimensions (mm). Choose one
of the 2 possibilities.

Summary of Contents for RP200B7W1

Page 1: ...English Split System air conditioners INSTALLATION MANUAL Installation manual Split System air conditioners R200F7W1 R250F7W1 RY200F7W1 RY250F7W1 RP200B7W1 RP250B7W1 RYP200B7W1 RYP250B7W1...

Page 2: ...ljer f ljande standard er eller andra normgivande dokument under f ruts ttning att anv ndning sker i verensst mmelse med v ra instruktioner respektive utstyr er i overensstemmelse med f lgende standar...

Page 3: ...H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 1 2 3 4 6 H1 L1 H1 H2 L7 L1 L6 L5 L4 L3 L2 5 B A C E D H 7 5 1 2 3 4...

Page 4: ...1 5 4 A B 2 3 9 11 3 2 1 3 2 1 P2 P1 3 2 1 P2 P1 3 2 1 P2 P1 3N 50Hz 400V L3 N N L3 L2 L1 L1 L2 l ll lll M S S 1 2 3 3 2 1 P2 P1 S 3 1 2 4 5 5 3 8 R22 R407C 6 5 4 2 1 3 R22 R407C 8 6 5 4 2 1 3 9 7 A...

Page 5: ...e R407C is a mixed refrigerant the required additional refrigerant must be charged in its liquid state If the refrigerant is in state of gas its composition changes and the system will not work proper...

Page 6: ...he unit 3 If you install the unit on a frame please install a waterproof plate within 150mm of the underside of the unit in order to prevent the invasion of water from the lower direction 4 When insta...

Page 7: ...liquid oil hammer the oil circulation will decrease To solve these phenomena provide oil traps in the gas pipe every 15m if the level difference H is more than 15m See figure 6 A outdoor unit B indoor...

Page 8: ...rface of the sealing Please refer to the table for the dimensions for processing flares and for the tightening torques Too much tightening will end up in splitting of the flare When connecting the fla...

Page 9: ...or 1 minute 2 Break the vacuum with a minimum of 2 bar of nitrogen 3 Conduct leak test by applying soap water etc to the connect ing part of the pipes 4 Discharge Nitrogen 5 Evacuate and check vacuum...

Page 10: ...en ON button on the remote controller is pressed and it will not operate Turn off the main power supply switch and turn it on again in need of operation ELECTRICAL WIRING WORK All wiring must be perfo...

Page 11: ...OW DO NOT OPERATE THE UNIT BY SHORT CIRCUITING S1LP USE COPPER CONDUCTORS ONLY L1 RED L2 WHITE L3 BLACK N BLUE A1P A2P PRINTED CIRCUIT BOARD BS1 PUSH BUTTON FORCED DEFROST PUMP DOWN C1R C2R CAPACITOR...

Page 12: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW10932 1A...

Reviews: