background image

5

E

VACUATING

The units were checked for leaks by the manufacturer.

The refrigerant lines fitted in site are to be checked for leaks by
the fitter.

Confirm that the valves are firmly closed before pressure test or
vacuuming.

Do not purge the air with refrigerants. Use a vacuum
pump to vacuum the installation. No additional refrigerant
is provided for air purging.

Air tight test and vacuum drying (take special care for
R407C units): refer to figure 11

A Pair system
B Simultaneous operation system
1 Pressure gauge
2 Nitrogen
3 Refrigerant
4 Weighing machine
5 Vacuum pump
6 Stop valve
7 Main pipe
8 Branched pipes
9 Pipe branching kit (optional)

Air tight test: make sure to use nitrogen gas. Pressurize the
liquid and gas pipes to 3.3MPa (do not pressurize more than
3.3MPa). If the pressure drops, check where the nitrogen
comes from.

Vacuum drying: use a vacuum pump which can evacuate to
-100.7kPa (5Torr, -755mmHg).

1. Evacuate the system from the liquid and gas pipes by

using a vacuum pump for more than 2 hours and bring the
system to -100.7kPa. After keeping the system under that
condition for more than one hour, check if the vacuum
gauge rises or not. If it rises, the system may either contain
moisture inside or have leaks.

2. Following should be executed if there is a possibility of

moisture remaining in the pipe (if piping work is carried out
during the raining season or over a long period of time,
rainwater may enter the pipe during work).
After evacuating the system for 2 hours, pressurize the
system to 0.05MPa (vacuum break) with nitrogen gas and
evacuate the system again using the vacuum pump for
1 hour to -100.7kPa (vacuum drying). If the system cannot
be evacuated to -100.7kPa within 2 hours, repeat the
operation of vacuum break and vacuum drying.
Then after leaving the system in vacuum for 1 hour,
confirm that the vacuum gauge does not rise.

Leak test

1. Evacuate the pipes and check vacuum. (No pressure increase

for 1 minute.)

2. Break the vacuum with a minimum of 2 bar of nitrogen.
3. Conduct leak test by applying soap water, etc. to the connect-

ing part of the pipes.

4. Discharge Nitrogen.
5. Evacuate and check vacuum again.
6. Open the stop valve and inject the refrigerant into the refrig-

erant pipe and into the indoor unit.

7. Leak test must satisfy EN 378-2.

C

HARGING

 

REFRIGERANT

This unit requires additional charging of refrigerant according to
the length of pipe connected at the site. Concerning R407C
refrigerant: charge the refrigerant to the liquid pipe in its liquid
state. Since R407C is a mixed refrigerant, its composition
changes if charged in a state of gas and normal system operation
would no longer be assured.
Concerning L1~L7 (see tables below), refer to figures 2~5.

1. Additional charging of refrigerant

The R22 cooling units (R200/R250) do not require any
additional charging of refrigerant.

The R22 heatpump units (RY200/RY250) and the R407C
units (R(Y)P200 / R(Y)P250) require additional charging of
refrigerant, according to the length of pipe connected at the
site.

Find the correct amount of additional refrigerant to charge ‘G’
(kg) using one of the following formulas.

If G<0: no addition is required.

Pair system: refer to figure 2

L1 (m)

one way length of liquid pipe

Simultaneous operation system
(Twin, Triple, Double Twin: refer to figures 2~5)

- L1 (m)

one way length of main liquid pipe

- L2~L7 (m) one way length of branched liquid pipes

R407C:

R407C

R22

R(P)200

G = (L1-30) x 0.06

G= 0

R(P)250

G = (L1-30) x 0.09

G= 0

RY(P)200

G = (L1-30) x 0.10

G= (L1-7.5) x 0.03

RY(P)250

G = (L1-30) x 0.14

G= (L1-7.5) x 0.05

RP200

G = (L1-30) x 0.06 + L2 x A + L3 x A + L4 x A + L5 x A + L6 x A + L7 x A

RP250

G = (L1-30) x 0.09 + L2 x A + L3 x A + L4 x A + L5 x A + L6 x A + L7 x A

RYP200 G = (L1-30) x 0.10 + L2 x A + L3 x A + L4 x A + L5 x A + L6 x A + L7 x A
RYP250 G = (L1-30) x 0.14 + L2 x A + L3 x A + L4 x A + L5 x A + L6 x A + L7 x A

Branched pipe

A

RP200,250

Ø 9.5

0.03 kg/m

RYP200,250

Ø 6.4

0.03 kg/m

Ø 9.5

0.05 kg/m

R22:

R200

G = 0

R250

G = 0

RY200

G = (L1-7.5) x 0.03 + L2 x A + L3 x A + L4 x A + L5 x A + L6 x A + L7 x A

RY250

G = (L1-7.5) x 0.05 + L2 x A + L3 x A + L4 x A + L5 x A + L6 x A + L7 x A

Branched pipe

A

RY200,250

Ø 6.4

0.005 kg/m

Ø 9.5

0.015 kg/m

Summary of Contents for RP200B7W1

Page 1: ...English Split System air conditioners INSTALLATION MANUAL Installation manual Split System air conditioners R200F7W1 R250F7W1 RY200F7W1 RY250F7W1 RP200B7W1 RP250B7W1 RYP200B7W1 RYP250B7W1...

Page 2: ...ljer f ljande standard er eller andra normgivande dokument under f ruts ttning att anv ndning sker i verensst mmelse med v ra instruktioner respektive utstyr er i overensstemmelse med f lgende standar...

Page 3: ...H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 1 2 3 4 6 H1 L1 H1 H2 L7 L1 L6 L5 L4 L3 L2 5 B A C E D H 7 5 1 2 3 4...

Page 4: ...1 5 4 A B 2 3 9 11 3 2 1 3 2 1 P2 P1 3 2 1 P2 P1 3 2 1 P2 P1 3N 50Hz 400V L3 N N L3 L2 L1 L1 L2 l ll lll M S S 1 2 3 3 2 1 P2 P1 S 3 1 2 4 5 5 3 8 R22 R407C 6 5 4 2 1 3 R22 R407C 8 6 5 4 2 1 3 9 7 A...

Page 5: ...e R407C is a mixed refrigerant the required additional refrigerant must be charged in its liquid state If the refrigerant is in state of gas its composition changes and the system will not work proper...

Page 6: ...he unit 3 If you install the unit on a frame please install a waterproof plate within 150mm of the underside of the unit in order to prevent the invasion of water from the lower direction 4 When insta...

Page 7: ...liquid oil hammer the oil circulation will decrease To solve these phenomena provide oil traps in the gas pipe every 15m if the level difference H is more than 15m See figure 6 A outdoor unit B indoor...

Page 8: ...rface of the sealing Please refer to the table for the dimensions for processing flares and for the tightening torques Too much tightening will end up in splitting of the flare When connecting the fla...

Page 9: ...or 1 minute 2 Break the vacuum with a minimum of 2 bar of nitrogen 3 Conduct leak test by applying soap water etc to the connect ing part of the pipes 4 Discharge Nitrogen 5 Evacuate and check vacuum...

Page 10: ...en ON button on the remote controller is pressed and it will not operate Turn off the main power supply switch and turn it on again in need of operation ELECTRICAL WIRING WORK All wiring must be perfo...

Page 11: ...OW DO NOT OPERATE THE UNIT BY SHORT CIRCUITING S1LP USE COPPER CONDUCTORS ONLY L1 RED L2 WHITE L3 BLACK N BLUE A1P A2P PRINTED CIRCUIT BOARD BS1 PUSH BUTTON FORCED DEFROST PUMP DOWN C1R C2R CAPACITOR...

Page 12: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW10932 1A...

Reviews: