background image

8 Troubleshooting

Installation and operation manual

12

REYQ8~20+REMQ5U7Y1B

VRV IV+ heat recovery

4P546222-1B – 2020.10

▪ If repairs to the product are necessary within the warranty period,

contact your dealer and keep the warranty card at hand.

7.2.2

Recommended maintenance and
inspection

Since  dust  collects  when  using  the  unit  for  several  years,
performance  of  the  unit  will  deteriorate  to  some  extent.  As  taking
apart and cleaning interiors of units requires technical expertise and
in  order  to  ensure  the  best  possible  maintenance  of  your  units,  we
recommend to enter into a maintenance and inspection contract on
top  of  normal  maintenance  activities.  Our  network  of  dealers  has
access  to  a  permanent  stock  of  essential  components  in  order  to
keep your unit in operation as long as possible. Contact your dealer
for more information.

When asking your dealer for an intervention, always state:

▪ The complete model name of the unit.

▪ The manufacturing number (stated on the nameplate of the unit).

▪ The installation date.

▪ The symptoms or malfunction, and details of the defect.

WARNING

▪ Do  NOT  modify,  disassemble,  remove,  reinstall  or

repair  the  unit  yourself  as  incorrect  dismantling  or
installation may cause an electric shock or fire. Contact
your dealer.

▪ In case of accidental refrigerant leaks, make sure there

are  no  naked  flames.  The  refrigerant  itself  is  entirely
safe,  non-toxic  and  non-combustible,  but  it  will
generate  toxic  gas  when  it  accidentally  leaks  into  a
room  where  combustible  air  from  fan  heaters,  gas
cookers,  etc.  is  present.  Always  have  qualified  service
personnel  confirm  that  the  point  of  leakage  has  been
repaired or corrected before resuming operation.

8

Troubleshooting

If one of the following malfunctions occur, take the measures shown
below and contact your dealer.

WARNING

Stop  operation  and  shut  off  the  power  if  anything
unusual occurs (burning smells etc.).

Leaving  the  unit  running  under  such  circumstances  may
cause breakage, electric shock or fire. Contact your dealer.

The system MUST be repaired by a qualified service person.

Malfunction

Measure

If a safety device such as a fuse, a
breaker or an earth leakage breaker
frequently actuates or the ON/OFF
switch does NOT properly work.

Turn OFF the main power
switch.

If water leaks from the unit.

Stop the operation.

The operation switch does NOT work
well.

Turn OFF the power
supply.

If the user interface display indicates the
unit number, the operation lamp flashes
and the malfunction code appears.

Notify your installer and
report the malfunction
code.

If  the  system  does  NOT  operate  properly  except  for  the  above
mentioned cases and none of the above mentioned malfunctions is
evident,  investigate  the  system  in  accordance  with  the  following
procedures.

Malfunction

Measure

If the system does not
operate at all.

▪ Check  if  there  is  no  power  failure.  Wait

until  power  is  restored.  If  power  failure
occurs  during  operation,  the  system
automatically  restarts  immediately  after
power is restored.

▪ Check if no fuse has blown or breaker is

activated.  Change  the  fuse  or  reset  the
breaker if necessary.

If the system goes into
fan only operation, but
as soon as it goes into
heating or cooling
operation, the system
stops.

▪ Check  if  air  inlet  or  outlet  of  outdoor  or

indoor  unit  is  not  blocked  by  obstacles.
Remove  any  obstacles  and  make  sure
the air can flow freely.

▪ Check if the user interface display shows

 (time to clean the air filter). (Refer to

"7  Maintenance  and  service"

  [

4

  11]  and

"Maintenance" in the indoor unit manual.)

The system operates
but cooling or heating
is insufficient.

▪ Check  if  air  inlet  or  outlet  of  outdoor  or

indoor  unit  is  not  blocked  by  obstacles.
Remove  any  obstacles  and  make  sure
the air can flow freely.

▪ Check if the air filter is not clogged (refer

to  "Maintenance"  in  the  indoor  unit
manual).

▪ Check the temperature setting.

▪ Check the fan speed setting on your user

interface.

▪ Check for open doors or windows. Close

doors and windows to prevent wind from
coming in.

▪ Check if there are too many occupants in

the room during cooling operation. Check
if  the  heat  source  of  the  room  is
excessive.

▪ Check  if  direct  sunlight  enters  the  room.

Use curtains or blinds.

▪ Check if the air flow angle is proper.

If  after  checking  all  above  items,  it  is  impossible  to  fix  the  problem
yourself, contact your installer and state the symptoms, the complete
model name of the unit (with manufacturing number if possible) and
the installation date (possibly listed on the warranty card).

8.1

Error codes: Overview

In case a malfunction code appears on the indoor unit user interface
display,  contact  your  installer  and  inform  the  malfunction  code,  the
unit  type,  and  serial  number  (you  can  find  this  information  on  the
nameplate of the unit).

For  your  reference,  a  list  with  malfunction  codes  is  provided.  You
can, depending on the level of the malfunction code, reset the code
by pushing the ON/OFF button. If not, ask your installer for advice.

Main code

Contents

External protection device was activated

EEPROM failure (indoor)

Drain system malfunction (indoor)

Fan motor malfunction (indoor)

Swing flap motor malfunction (indoor)

Expansion valve malfunction (indoor)

Drain malfunction (indoor unit)

Filter dust chamber malfunction (indoor)

Capacity setting malfunction (indoor)

Summary of Contents for REYQ8U7Y1B

Page 1: ...lation and operation manual VRV IV heat recovery English Installation and operation manual VRV IV heat recovery REYQ8U7Y1B REYQ10U7Y1B REYQ12U7Y1B REYQ14U7Y1B REYQ16U7Y1B REYQ18U7Y1B REYQ20U7Y1B REMQ5...

Page 2: ...p niejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respective Direktive z vsemi spremembami Direktiivid koos muudatustega Direktyvose su papildymais Direkt v s un to papildin...

Page 3: ...vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota...

Page 4: ...lay shows 88 14 8 2 16 Symptom The compressor in the outdoor unit does not stop after a short heating operation 14 8 2 17 Symptom The inside of an outdoor unit is warm even when the unit has stopped 1...

Page 5: ...st read before installing Format Paper in the box of the outdoor unit Outdoor unit installation and operation manual Installation and operation instructions Format Paper in the box of the outdoor unit...

Page 6: ...e side Do NOT use taped wires stranded conductor wires extension cords or connections from a star system They can cause overheating electrical shock or fire Do NOT install a phase advancing capacitor...

Page 7: ...nsuring this product is disposed of correctly you will help to prevent potential negative consequences for the environment and human health For more information contact your installer or local authori...

Page 8: ...vice personnel confirm that the point of leakage has been repaired or corrected before resuming operation WARNING Stop operation and shut off the power if anything unusual occurs burning smells etc Le...

Page 9: ...ly is turned off during operation operation will restart automatically after the power turns back on again 6 2 2 About cooling heating fan only and automatic operation Changeover cannot be made with a...

Page 10: ...ration if the room temperature is low 20 C 6 3 2 To use the dry program WITHOUT cool heat changeover remote control switch To start 1 Press the operation mode selector button on the user interface sev...

Page 11: ...e Only the master user interface can select heating or cooling mode 7 Maintenance and service NOTICE NEVER inspect or service the unit by yourself Ask a qualified service person to perform this work W...

Page 12: ...he malfunction code If the system does NOT operate properly except for the above mentioned cases and none of the above mentioned malfunctions is evident investigate the system in accordance with the f...

Page 13: ...ation System mismatch Wrong type of indoor units combined Indoor unit malfunction Connection malfunction over indoor units or type mismatch Centralised address duplication Malfunction in communication...

Page 14: ...ise is heard In order to prevent oil and refrigerant from remaining in the system a small amount of refrigerant is kept flowing 8 2 10 Symptom Noise of air conditioners Indoor unit outdoor unit A cont...

Page 15: ...E O6 4 x 0 022 105 CR 130 50 CR 105 50 CR 70 70 CR 85 85 CR 105 105 CR 130 8HP Total indoor unit capacity connection ratio CR 10 12HP 14 16HP 18 20HP 2 0 1 5 1 5 1 2 1 5 1 1 0 7 1 0 0 5 0 5 0 3 0 5 0...

Page 16: ...on the heating capacity can go up till 168 kW and in cooling till 150 kW The outdoor unit is designed to work in heating mode at ambient temperatures from 20 C WB to 15 5 C WB and in cooling mode at a...

Page 17: ...cal component box of the outdoor unit 417 For service purposes the pushbuttons on the main PCB need to be accessed To access these pushbuttons the electrical component box cover does not need to be op...

Page 18: ...t piping 14 1 1 Refrigerant piping requirements NOTICE Refrigerant R410A requires strict cautions for keeping the system clean and dry Foreign materials including mineral oils or moisture should be pr...

Page 19: ...Piping between refrigerant branch kit and indoor unit e Indoor unit Size up HP class Liquid piping outer diameter size mm 5 8 9 5 12 7 10 12 14 12 7 15 9 16 18 22 15 9 19 1 24 26 34 19 1 22 2 36 54 T...

Page 20: ...the piping between outdoor units as shown in the 4 correct possibilities of the figure below a b b b a b b b a b a b a b a a a 200 mm a To indoor unit b Oil collects to the outmost outdoor unit when...

Page 21: ...outdoor unit Install the joints horizontally so that the caution label a attached to the joint comes to the top Do not tilt the joint more than 7 5 see view A Do not install the joint vertically see v...

Page 22: ...ce port cover securely For the tightening torque refer to the table below Check for refrigerant leaks after tightening the service port cover Tightening torques Stop valve size mm Tightening torque N...

Page 23: ...ait to apply setting 2 21 until the outdoor unit has finished the initialisation Leak test and vacuum drying Checking the refrigerant piping involves Checking for any leakages in the refrigerant pipin...

Page 24: ...o perform vacuum drying To remove all moisture from the system proceed as follows 1 Evacuate the system for at least 2 hours to a target vacuum of 100 7 kPa 1 007 bar 5 Torr absolute 2 Check that with...

Page 25: ...ible when Hydrobox units are connected to the system To speed up the refrigerant charging process it is in case of larger systems recommended to first pre charge a portion of refrigerant through the l...

Page 26: ...ing installation Installation and operation manual 26 REYQ8 20 REMQ5U7Y1B VRV IV heat recovery 4P546222 1B 2020 10 Inch piping Metric piping Piping Weight factor Piping Weight factor 22 2 mm 0 37 22 m...

Page 27: ...rigerant overcharge happened recover refrigerant to reach R Q Step 2 3 Close valves C D and A Open valve B to the liquid line Execute pre charging amount Q kg Disconnect the manifold from the gas line...

Page 28: ...en valve A Charge remaining amount of refrigerant P kg R Q P Depending on ambient conditions the unit will decide to perform autocharge operation in heating or cooling mode Close valve A Push BS3 to s...

Page 29: ...ditional refrigerant amount via setting 2 14 Go to test run Following codes appear e 2 indoor temperature out of range and e 3 outdoor temperature out of range Push BS1 to leave program Charging is fi...

Page 30: ...is connected to the piping inside the unit The unit s internal piping is already factory charged with refrigerant so be careful when connecting the charge hose After adding the refrigerant do not for...

Page 31: ...mperature range for leak detection operation Retry when ambient conditions are satisfied Outdoor unit is out of temperature range for leak detection operation Retry when ambient conditions are satisfi...

Page 32: ...EYQ40 14556 REYQ42 14735 REYQ44 15094 REYQ46 15634 REYQ48 16172 REYQ50 17071 REYQ52 17969 REYQ54 18868 INFORMATION Multi units are standard combinations 15 2 Safety device requirements The power suppl...

Page 33: ...smission wiring Q1 Q2 c Plastic bracket d Field supplied clamps 15 5 To connect the transmission wiring The wiring from the indoor units must be connected to the F1 F2 In Out terminals on the PCB in t...

Page 34: ...has to be removed Close the hole to avoid small animals or dirt from entering 15 8 To connect the power supply The power supply MUST be clamped to the plastic bracket using field supplied clamp mater...

Page 35: ...an be monitored as well Mode 2 field settings Mode 2 is used to change the field settings of the system Consulting the current field setting value and changing the current field setting value is possi...

Page 36: ...e process push BS1 to return to the default situation no indication on 7 segment displays blank refer to To access mode 1 or 2 436 16 1 5 To use mode 1 Mode 1 is used to set basic settings and to moni...

Page 37: ...heating comfort setting 16 1 8 Mode 2 Field settings 2 0 Cool Heat selection setting 2 0 Description 0 default Each individual outdoor unit can select Cool Heat operation by Cool Heat selector if ins...

Page 38: ...the outdoor unit exceeds 50 m the setting 2 49 has to be changed to 1 16 1 9 To connect the PC configurator to the outdoor unit X 2 7 A a b c 2 3 4 5 H J S T X27A A1P a PC b Cable EKPCCAB c Outdoor u...

Page 39: ...has been bypassed Internal wiring Visually check the electrical component box and the inside of the unit for loose connections or damaged electrical components Pipe size and pipe insulation Be sure th...

Page 40: ...operation will be possible after 5 minutes 17 5 Correcting after abnormal completion of the test run The test operation is only completed if there is no malfunction code displayed on the user interfac...

Page 41: ...PCB X21A Check connection on PCB or actuator Electronic expansion valve malfunction lower heat exchanger Y3E main PCB X23A Check connection on PCB or actuator Electronic expansion valve malfunction su...

Page 42: ...ection on PCB or actuator Upper heat exchanger gas temperature sensor R8T main PCB X29A Check connection on PCB or actuator Lower heat exchanger gas temperature sensor R9T main PCB X29A Check connecti...

Page 43: ...tem test run An error occurred during the test run Re execute the test run Test run aborted Re execute the test run Test run aborted due to communication issues Check the communication wires and re ex...

Page 44: ...de Leak detection function related Unit is not prepared to execute leak detection operation Refer to requirements to be able to execute leak detection operation Indoor unit is out of temperature range...

Page 45: ...h obstacles F Front side Suction side In case of an installation site where sides A B C D have obstacles the wall heights of sides A C have no impact on service space dimensions Refer to the figure ab...

Page 46: ...manual 46 REYQ8 20 REMQ5U7Y1B VRV IV heat recovery 4P546222 1B 2020 10 20 2 Piping diagram Outdoor unit Piping diagram 5 12 HP a b d e c a Stop valve liquid b Service port c Stop valve high pressure...

Page 47: ...on and operation manual 47 REYQ8 20 REMQ5U7Y1B VRV IV heat recovery 4P546222 1B 2020 10 Piping diagram 14 20 HP a b d e c a Stop valve liquid b Service port c Stop valve high pressure low pressure d S...

Page 48: ...es S1PH S2PH for 14 20 HP only 6 For 5 12 HP When using the optional accessory refer to the installation manual of the optional accessory 6 For 14 20 HP connector X1A M2F is red connector X2A M2F is w...

Page 49: ...or for optional accessories X10A Connector bottom plate heater Legend for wiring diagram 14 20 HP A1P Printed circuit board main A2P A5P Printed circuit board noise filter A3P A6P Printed circuit boar...

Page 50: ...inverter cooling Y6E Electronic expansion valve auto charge Y2S Solenoid valve liquid pipe Y3S Solenoid valve high pressure low pressure gas pipe Y4S Solenoid valve heat exchanger lower Y5S Solenoid v...

Page 51: ......

Page 52: ...4P546222 1B 2020 10 Copyright 2018 Daikin 4P546222 1 B 0000000Z Verantwortung f r Energie und Umwelt...

Reviews: