7
1-3 Standard supplied accessories
∗
Use the flare nut attached to the discharge gas stop valve for the “dis-
charge gas line piping attached to unit” (1).
(Refer to figure 21)
1.
Operation manual
Installation manual
Clamp
2.
Attached pipe
1-4 Option accessory
To install the outdoor unit, the following optional parts are also required.
• Refrigerant branching kit (For R410A only: Always use an
appropriate kit dedicated for your system.)
for 3 pipes
for 2 pipes
• Outdoor unit multi connection piping kit (For R410A only:
Always use an appropriate kit dedicated for your system.)
∗
To select an optimum refrigerant branching kit, refer to
“
6. Refrigerant Piping
”.
1-5 Technical specifications (1)
(1) Refer to the engineering data book for the complete list of specifications.
(2) The nominal cooling capacity is based on:
- indoor temperature: 80°FDB / 67°FWB
- outdoor temperature: 95°FDB
- pipe length: 25ft.
- level difference: 0ft.
(3) The nominal heating capacity is based on:
- indoor temperature: 70°FDB
- outdoor temperature: 47°FDB / 43°FWB
- pipe length: 25ft.
- level difference: 0ft.
(4) The nominal input includes total input of the unit: compressor, fan motor and con-
trol circuit.
1-6 Electrical specifications (1)
2. MAIN COMPONENTS
For main components and function of the main components, refer to the
Engineering Data Book.
3. SELECTION OF LOCATION
This unit, both indoor and outdoor, is suitable for installation in a com-
mercial and light industrial environment.
If installed as a household
appliance it could cause electromagnetic interference.
The VRV OUTDOOR units should be installed in a location that meets
the following requirements:
1.
The foundation is strong enough to support the weight of the unit and
the floor is flat to prevent vibration and noise generation.
Name
Clamp (1)
Clamp (2)
Clamp (3)
Suction gas line
piping attached to
unit (1)
Quantity
9 pcs.
2 pcs.
1 pc.
1 pc.
Shape
Name
Suction gas line
piping attached to unit
(2)
Suction gas line
piping attached to
unit (3)
Discharge gas line
piping attached to
unit (1)
∗
Quantity
1 pc.
1 pc.
1 pc.
Shape
Name
Discharge gas
line piping
attached to unit
(2)
Discharge gas
line piping
attached to unit
(3)
Vinyl tube
Others
Quantity
1 pc.
1 pc.
1 pc.
•
Operation
manual
•
Installation
manual
•
Additional
refrigerant
charge
label
Shape
REFNET header
-
KHRP25M33H KHRP25M72H
REFNET joint
KHRP25M22T
KHRP25M33T
KHRP25M72TU
REFNET header KHRP26M22H KHRP26M33H KHRP26M72H
REFNET joint
KHRP26M22T
KHRP26M33T
KHRP26M72TU
Number of outdoor units connected
2 units
Kit name
BHFP26M90U
Small
Large
General
REYQ96MTJU
REYQ192MTJU
Nominal cooling capacity
(2)
(MBh)
96
192
Nominal heating capacity
(3)
(MBh)
108
216
Nominal input cooling /
heating (4)
(kW)
8.67 / 9.19
17.34 / 18.38
Dimensions H×W×D
(inch)
64
×
48-7/8
×
30-1/8 (64
×
48-7/8
×
30-1/8) +
(64
×
48-7/8
×
30-1/8)
Mass
(Ib.)
650
650+650
Connections
Refrigerant suction gas pipe
(inch)
7/8
1-1/8
Refrigerant discharge gas
pipe
(inch)
3/4
7/8
Refrigerant liquid pipe
(inch)
3/8
5/8
Compressor
REYQ96MTJU
REYQ192MTJU
Oil type
-
Synthetic(ether)oil
Synthetic(ether)oil
Oil charge volume
(I)
1.9+1.6
(1.9+1.6)+(1.9+1.6)
Crankcase heater
(W)
33+33
(33+33)+(33+33)
Refrigerant type
-
R410A
R410A
Refrigerant charge
(Ib.)
27.3
27.3+27.3
Condenser
REYQ96MTJU
REYQ192MTJU
Nominal air flow
(CFM)
7400
7400+7400
Fan motor output
(W)
750
750+750
Model
REYQ96MTJU
REYQ192MTJU
Power supply
Phase
-
3
~
3
~
Frequency
(Hz)
60
60
Voltage
(V)
208-230
208-230
Voltage torerance
(%)
±10
±10
Recommended fuses
(A)
70
70+70
Compressor
Phase
-
3
~
3
~
Frequency
(Hz)
60
60
Voltage
(V)
208-230
208-230
Nominal running current
(A)
10.1+13.1
(10.1+13.1)+(10.1+13.1)
Model
REYQ96MTJU
REYQ192MTJU
Control and fan motor
Type
Voltage
(V)
208-230
208-230
Nominal running current
(A)
4.5
4.5+4.5
01_EN_3P114261-10Y.fm Page 7 Thursday, June 16, 2005 3:14 PM