background image

13

6-4 Leak test and vacuum drying

The units were checked for leaks by the manufacturer.
Confirm that the valves are firmly closed before pressure test or vacu-
uming.
To prevent entry of any impurities and ensure sufficient pressure resis-
tance, always use the special tools dedicated for R410A.

Air tight test and vacuum drying

Air tight test: Make sure to use nitrogen gas.
(For the service port location, refer to the “Cau-
tion” label attached on the front panel [right] of
the outdoor unit.)

(Refer to figure)

1.

[Service precautions]
Label location

2.

Electric parts box lid

3.

[Caution]
Label location

Pressurize the liquid, suction gas and 
discharge gas pipes to 551 psi 
(do not pressurize more than 551 psi). If the pressure does not drop 
within 24 hours, the system passes the test. If the pressure drops, 
check where the nitrogen leaks from.

Vacuum drying: Use a vacuum pump which can evacuate to 
–14.6 psi.

1.

Evacuate the system from the liquid, suction gas and discharge
gas pipes by using a vacuum pump for more than 2 hours and
bring the system to –14.6 psi. After keeping the system under that
condition for more than 1 hour, check if the vacuum gauge rises
or not. If it rises, the system may either contain moisture inside or
have leaks.

2.

Following should be executed if there is a possibility of moisture
remaining inside the pipe (if piping work is carried out during the
raining season or over a long period of time rainwater may enter
the pipe during work).
After evacuating the system for 2 hours, pressurize the system to
7.25psi (vacuum break) with nitrogen gas and evacuate the sys-
tem again using the vacuum pump for 1 hour to –14.6 psi (vac-
uum drying). If the system cannot be evacuated to –14.6 psi
within 2 hours, repeat the operation of vacuum break and vac-
uum drying.
Then, after leaving the system in vacuum for 1 hour, confirm that
the vacuum gauge does not rise.

NOTE

Make sure to perform air tight test and vacuum drying using the service
ports of the stop valve shown in the table below.

Stop valve operation procedure

Introduction
Confirm the sizes of the stop valves connected to the system referring
to the table below.

Opening stop valve

1.

Remove the cap and turn the valve counterclockwise with the hexa-
gon wrench.

2.

Turn it until the shaft stops.
Do not apply excessive force to the stop valve. Doing so may break

the valve body, as the valve is not a backseat type. Always use the

special tool.

3.

Make sure to tighten the cap securely.

Closing stop valve

1.

Remove the cap and turn the valve clockwise with the hexagon
wrench.

2.

Securely tighten the valve until the shaft contacts the main body
seal.

3.

Make sure to tighten the cap securely.

∗ 

For the tightening torque, refer to the table below. 

Tightening torque

(Refer to figure 22)

 

1.

Service port

2.

Cap

3.

Hexagon hole

4.

Shaft

5.

Seal

〈〈〈〈

Caution

〉〉〉〉

Always use a charge hose for service port connection.

After tightening the cap, check that no refrigerant leaks are present.

When loosening a flare nut, always use two wrenches in combina-

tion. When connecting the piping, always use a spanner and torque

wrench in combination to tighten the flare nut.

When connecting a flare nut, coat the 
flare (inner and outer faces) with ether 
oil or ester oil and hand-tighten the nut 
3 to 4 turns as the initial tightening. 

FLARE SHAPE and FLARENUT TIGHTENING TORQUE

〈〈〈〈

Precautions when connecting pipes

〉〉〉〉

See the following table for flare part machining dimensions.

When connecting the flare nuts, apply refrigerant oil to the inside and 

outside of the flares and turn them three or four times at first.

 

(Use ester oil or ether oil.)

See the following table for tightening torque.

(Applying too much torque may cause the flares to crack.)

After all the piping has been connected, use nitrogen to perform a 

gas leak check.

One outdoor unit installed

Liquid line stop valve
Discharge gas line stop valve
Suction gas line stop valve

Multiple outdoor units installed

Liquid line stop valve
Discharge gas line stop valve
Suction gas line stop valve
Oil-equalizing line stop valve

Q96 type

Liquid line stop valve

φ 

3/8”

Suction gas line stop valve

φ 

7/8”

Discharge gas line stop valve

φ 

3/4”

1

3

2

Stop 

valve 

size

Tightening torque ft.-Ibf (Turn clockwise to close)

Shaft (valve body)

Cap 

(valve lid)

Service 

port

Flare nut

Suction 

gas line 

piping 

attached to 

unit (1)

φ

1/4”

3.98-4.87

Hexagon 
wrench
4 mm

9.96-12.17

8.48-10.25

10.3-

12.5

-

φ

3/8”

24.1-

29.4

-

φ

3/4”

9.96-12.17

Hexagon 
wrench
6mm

17.33-20.28

71.6-

87.8

-

φ

7/8”

19.91-24.34

Hexagon 
wrench
10mm

26.55-32.45

-

16.23-

20.65

pipe size (in.)

tightening

torque (ft.-Ibf)

A (in.)

flare shape (in.)

φ

3/8

24.1 - 29.4

0.504 - 0.520

φ

1/2

36.5 - 44.5

0.638 - 0.654

φ

5/8

45.6 - 55.6

0.760 - 0.776

Torque wrench

Spanner

Piping union

Flare nut

R=0.016-0.031

45  ±2

90 ±2

A

01_EN_3P114261-10Y.fm  Page 13  Thursday, June 16, 2005  3:14 PM

Summary of Contents for REYQ192MTJU

Page 1: ...EL REYQ96MTJU REYQ192MTJU Read these instructions carefully before installation Keep this manual in a handy place for future reference This manual should be left with the equipment owner 00_CV_3P11426...

Page 2: ...al 1 1 2 2 1 3 1 1 1 1 in H1 59 H1 59 X H2 19 5 8 H2 19 5 8 Y A 19 5 8 A 19 5 8 X 2 B1 11 3 4 B2 3 7 8 B1 11 3 4 Y 2 B2 3 7 8 Y 2 60 5 3 1 4 2 2 in 40 4 0 40 6 0 60 60 6 3 5 7 3 4 1 2 8 28 7 16 29 3 1...

Page 3: ...stalled 2 1 3 5 6 8 4 7 One outdoor unit installed One outdoor unit installed 1 2 4 5 6 3 7 1 2 4 5 6 3 1 2 3 4 5 6 7 8 9 16 10 11 15 14 12 17 13 1 2 3 4 5 6 13 18 12 20 16 16 9 10 11 17 8 19 7 1 2 3...

Page 4: ...1 2 3 5 7 10 8 1 4 6 9 2 3 1 2 1 2 3 4 5 A B C F1 F2 F1 F2 Q1 Q2 A B C F1 F1 F2 F2 Q1 Q2 2 1 C H SELECTOR TO IN D UNIT TO OUT D UNIT TO MULTI UNIT A1P IN D OUT D BS F1 F1 F2 F2 F1 F2 F1 F2 F1 F2 F1 F2...

Page 5: ...e unit on a foundation strong enough to withstand the weight of the unit A foundation of insufficient strength may result in the equipment falling and causing injuries Carry out the specified installa...

Page 6: ...t that the outdoor unit be used as a shelter by small ani mals Small animals making contact with electrical parts can cause mal functions smoke or fire Please instruct the customer to keep the area ar...

Page 7: ...lamp 1 Clamp 2 Clamp 3 Suction gas line piping attached to unit 1 Quantity 9 pcs 2 pcs 1 pc 1 pc Shape Name Suction gas line piping attached to unit 2 Suction gas line piping attached to unit 3 Discha...

Page 8: ...AND HANDLING THE UNIT At delivery the package should be checked and any damage should be reported immediately to the carrier claims agent When handling the unit take into account the following 1 Fragi...

Page 9: ...size referring to chapter Example of connection The wall thickness of the refrigerant piping should comply with relevant local and national regulations 3 Make sure to use the particular branches of pi...

Page 10: ...ate adversely affecting the refrigerant piping system NOTE The pressure regulator for the nitrogen released when doing the brazing should be set to 2 9 psi or less Refer to figure 9 1 Refrigerant pipi...

Page 11: ...topping outdoor unit Change to pattern 1 or pattern 2 UnitA Unit B Unit B UnitA to indoor unit Change as shown in the figure below to indoor unit to indoor unit to indoor unit Oilcollectstotheoutdooru...

Page 12: ...er of outdoor units Branch kit name Outdoor unit capacity type Refrigerant branch kit name indoor capacity index Refrigerant branch kit name In case of 3 pipes In case of 2 pipes 1 15 _ If the outdoor...

Page 13: ...ly excessive force to the stop valve Doing so may break the valve body as the valve is not a backseat type Always use the special tool 3 Make sure to tighten the cap securely Closing stop valve 1 Remo...

Page 14: ...n unsuitable substance may cause explosions and accidents so always ensure that the appropriate refrigerant R410A is charged Refrigerant containers shall be opened slowly Always use protective gloves...

Page 15: ...or the power cord 7 2 Power circuit and cable requirements A power circuit see table below must be provided for connection of the unit This circuit must be protected with the required safety devices i...

Page 16: ...wire 10 When wiring exercise sufficient caution not to detach the acoustic insulators from the compressor CAUTION Precautions when laying power wiring Use round pressure terminals for connections to t...

Page 17: ...necting wiring between the outdoor units in the same pipe line must be connected to the Q1 Q2 Out Multi terminals Con necting the wires to the Out Out terminals results in system mal function The wiri...

Page 18: ...the configuration on the parent unit Any settings made on a child unit will be ignored Always perform configuration after turning ON the power To learn the setting method refer to the Service Precauti...

Page 19: ...f refrigerant Ib charged to each system separately NOTE Where a single refrigerant facility is divided into 2 entirely indepen dent refrigerant systems then use the amount of refrigerant with which ea...

Page 20: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 3P114261 10Y EM04A002A 0506 HT 00_CV_3P114261 10Y fm Page 5 Thursday June 16 2005 4 31 PM...

Reviews: